7.4 Nonpotable Water Systems, Identification, and Reclaimed Water
Key Takeaways
- IPC 608.9.2 requires nonpotable distribution piping to be purple and embossed, stamped or marked CAUTION: NONPOTABLE WATER - DO NOT DRINK, or installed with purple identification tape or wrap.
- IPC 608.9.2 requires pipe identification to be repeated at intervals not exceeding 25 feet and at each point where the piping passes through a wall, floor or roof.
- IPC 608.9.1 requires nonpotable outlet signage with letters not less than 0.5 inch in height, in contrasting colors, plus the Figure 608.9.1 do-not-drink pictograph.
- IPC 1301.2.2 requires nonpotable water used for water closet and urinal flushing to be filtered by a 100-micron or finer filter.
- IPC 608.10 permits water used for cooling equipment or other processes to be reused for flushing water closets and urinals or for irrigation, provided it is not sprayed onto areas open to public use.
Why identification is a safety system
Every other rule in Chapter 7 of this guide prevents nonpotable water from entering the potable system. Identification prevents the opposite failure: a future plumber, maintenance technician or homeowner mistaking a nonpotable line for a potable one and tapping it. Buildings outlive the people who built them, so the marking has to survive.
Signage at outlets — IPC 608.9.1
Nonpotable water outlets, such as hose connections, open-ended pipes and faucets, shall be identified with signage that reads: "Nonpotable water is utilized for [application name]. CAUTION: NONPOTABLE WATER - DO NOT DRINK."
Requirements for the sign:
- Words legibly and indelibly printed on a tag or sign of corrosion-resistant waterproof material, or indelibly printed on the fixture.
- Letters not less than 0.5 inch in height.
- Colors in contrast to the background.
- In addition to the wording, the pictograph in Figure 608.9.1 ("do not drink") must appear.
Pipe labeling and marking — IPC 608.9.2
| Requirement | Rule |
|---|---|
| Color | Nonpotable distribution piping shall be purple |
| Marking | Embossed, integrally stamped or marked "CAUTION: NONPOTABLE WATER - DO NOT DRINK", or installed with purple identification tape or wrap |
| Content | Identification includes the contents of the piping system and an arrow indicating direction of flow |
| Hazard | Hazardous piping systems shall also contain information addressing the nature of the hazard |
| Interval | Repeated at intervals not exceeding 25 feet and at each point where the piping passes through a wall, floor or roof |
| Visibility | Lettering readily observable within the room or space where the piping is located |
608.9.2.1 Color: the identification color must be discernible and consistent throughout the building, and purple identifies reclaimed, rain and graywater distribution systems.
608.9.2.2 Lettering size scales with pipe diameter, per Table 608.9.2.2:
| Pipe diameter | Background color field length | Letter size |
|---|---|---|
| 3/4 to 1-1/4 inch | 8 inches | 0.5 inch |
| 1-1/2 to 2 inch | 8 inches | 0.75 inch |
| 2-1/2 to 6 inch | 12 inches | 1.25 inch |
| 8 to 10 inch | 24 inches | 2.5 inch |
| Over 10 inch | 32 inches | 3.5 inch |
Nonpotable water systems — IPC Chapter 13
Chapter 13 covers nonpotable water systems generally: graywater, rainwater, reclaimed water and on-site treated nonpotable water. Colorado adopts IPC Chapters 2 through 13, so Chapter 13 is part of the Colorado Plumbing Code.
Core rules:
- 1301.2.2 Filtration: nonpotable water used for water closet and urinal flushing applications shall be filtered by a 100-micron or finer filter.
- 1301.3 Identification: nonpotable distribution piping is identified per 608.9.2.
- 1301.4 Materials: nonpotable piping conforms to the material tables for the application.
- Storage tanks must be covered, labeled, and protected from contamination, with overflows and drains that cannot cross-connect.
- Makeup water to a nonpotable storage tank from the potable system must be protected by an air gap — never a mechanical device on an open tank.
IPC 608.12 Potable water tanks requires potable tanks to be enclosed and covered; 608.4 requires overflow, relief valve and waste discharge pipes from pumps, filters, softeners and tanks handling potable water to terminate through an air gap.
Definitions that matter
- Graywater (IPC 202): waste discharged from lavatories, bathtubs, showers, clothes washers and laundry trays. It excludes water closet, urinal, kitchen sink, dishwasher and utility sink waste.
- Reclaimed water: nonpotable water that has been derived from the treatment of wastewater by a facility or system duly authorized by the authority having jurisdiction.
- Blackwater: waste containing bodily or other biological wastes, as from water closets, urinals, kitchen sinks, dishwashers and utility sinks.
Colorado field note (not exam-scored): Colorado rewrites both definitions. Board Rule 1.2(E)(1)(f) defines graywater as wastewater collected from bathroom and laundry room sinks, bathtubs, showers and laundry machines for beneficial use, excluding toilets, urinals, kitchen sinks, dishwashers and non-laundry utility sinks. Rule 1.2(E)(1)(g) defines reclaimed water as domestic wastewater that has received secondary treatment by a domestic wastewater treatment works plus additional treatment sufficient to meet the standards for approved uses.
Colorado also modifies the filtration exception (Rule 1.2(E)(1)(yy)): reclaimed water sources are not required to meet the 100-micron filtration requirement, and graywater treatment systems installed per Section 1302.6.1 do not need additional filtration. Rule 1.2(E)(1)(aaa) adds a required sign on the door of any room containing graywater treatment works: "CAUTION GRAYWATER TREATMENT WORKS, DO NOT DRINK, DO NOT CONNECT TO THE POTABLE DRINKING WATER SYSTEM. NOTICE: CONTACT BUILDING MANAGEMENT BEFORE PERFORMING ANY WORK ON THIS WATER SYSTEM."
Reuse rules — IPC 608.10 and 608.11
608.10 Reutilization prohibited: water used for cooling equipment or other processes shall not be returned to the potable water system. Such water may be reused for:
- flushing water closets and urinals, or
- irrigation,
provided that it is not sprayed onto areas open to public use — the spray restriction exists because aerosolized nonpotable water is an inhalation route.
608.11 Reuse of piping: piping that has conveyed nonpotable water or other contaminating substances shall not be reused for potable water service or distribution. Reusing an old irrigation main as a domestic water line is prohibited no matter how thoroughly it is flushed.
Putting the chapter together: an inspection walkthrough
A commercial building uses reclaimed water for water closet and urinal flushing and for site irrigation.
| Item to verify | Requirement |
|---|---|
| Distribution piping color | Purple (608.9.2, 608.9.2.1) |
| Pipe marking text | "CAUTION: NONPOTABLE WATER - DO NOT DRINK", with contents and flow arrow |
| Marking interval | Every 25 feet maximum and at every wall, floor and roof penetration |
| Letter size on a 4-inch line | 1.25 inch, on a 12-inch background field (Table 608.9.2.2) |
| Outlet signage | 0.5-inch letters minimum, contrasting colors, plus the do-not-drink pictograph |
| Flushing water filtration | 100-micron or finer filter (1301.2.2) |
| Potable makeup to the reclaimed storage tank | Air gap |
| Irrigation spray | Not sprayed onto areas open to public use (608.10) |
| Backflow protection at the irrigation connection | AVB, PVB or RPZ; RPZ if chemicals are injected (608.17.5) |
| Annual duties | Inspect all assemblies and air gaps; test assemblies (312.10.1, 312.10.2) |
At what maximum interval must nonpotable water pipe identification be repeated under IPC 608.9.2?
What color identifies reclaimed, rain and graywater distribution systems under IPC 608.9.2.1?
Nonpotable water is used to flush water closets and urinals. What filtration does IPC 1301.2.2 require?
Water used for cooling equipment may be reused for which purposes under IPC 608.10?