16.3 Secondary Roof Drains, Scuppers, and Controlled Flow Systems

Key Takeaways

  • IPC 1108.1 requires secondary emergency overflow roof drains or scuppers where the roof perimeter construction extends above the roof so that water would be entrapped if the primary drains allow buildup.
  • IPC 1108.2 requires secondary roof drain systems to have an end point of discharge separate from the primary system, above grade, in a location normally observed by building occupants or maintenance personnel.
  • IPC 1108.3 sizes secondary roof drain systems for the same rainfall rate as the primary system, and states the flow through the primary system shall not be considered.
  • IPC 1106.5 and 1108.3 require scupper openings to be not less than 4 inches in height with a width equal to or greater than the circumference of a roof drain sized for the same area.
  • IPC 1110.4 requires not less than two roof drains in controlled flow roof areas of 10,000 square feet or less, and not less than four in roofs over 10,000 square feet.
Last updated: September 2026

Why secondary drainage exists

A flat roof with a parapet is a basin. If the primary drains block — with ice, leaves, a construction tarp, a roofing bucket — the roof fills. Water weighs about 5.2 pounds per square foot per inch of depth. A few inches of ponding across a large roof is tens of thousands of pounds the structure may not have been designed to carry, and roof collapses from ponding are a recognized failure mode.

IPC 1101.7 encodes the design assumption: in determining the maximum possible depth of ponded water, all primary roof drainage means shall be assumed to be blocked.

When secondary drainage is required — IPC 1108.1

Where roof drains are required, secondary (emergency overflow) roof drains or scuppers shall be provided where the roof perimeter construction extends above the roof in such a manner that water will be entrapped if the primary drains allow buildup for any reason. Where primary and secondary roof drains are manufactured as a single assembly, the inlet and outlet for each drain shall be independent.

Two triggers, both required:

  1. Roof drains are required on the roof, and
  2. the perimeter construction extends above the roof so water would be entrapped.

A roof that sheds freely over an unrestricted edge does not need secondary drainage, because the edge itself is the overflow.

The single-assembly rule prevents a manufacturer from sharing a throat or an outlet between the primary and secondary path — which would let a single blockage defeat both.

Separate discharge — IPC 1108.2

Secondary roof drain systems shall have the end point of discharge separate from the primary system. Discharge shall be above grade, in a location that would normally be observed by the building occupants or maintenance personnel.

Three requirements, each with a purpose:

  • Separate end point — a shared discharge means a blocked primary line blocks the secondary line too.
  • Above grade — a below-grade tie-in can surcharge.
  • Normally observed — the secondary system running is the building's alarm that the primary system has failed. Discharging it into a hidden courtyard defeats the warning.

Sizing the secondary system — IPC 1108.3

Secondary (emergency) roof drain systems shall be sized in accordance with Section 1106 based on the rainfall rate for which the primary system is sized. Scuppers shall be sized to prevent the depth of ponding water from exceeding that for which the roof was designed as determined by Section 1101.7. Scuppers shall have an opening dimension of not less than 4 inches in height and have an opening width equal to the circumference of the roof drain required for the area served. The flow through the primary system shall not be considered when sizing the secondary roof drain system.

The last sentence is the one exam items test. You do not credit the primary system with any capacity. The secondary system carries the entire design rainfall on its own, because the design case is that the primary system is blocked.

Scupper dimensions

DimensionRequirement
Height of the openingNot less than 4 inches
Width of the openingEqual to or greater than the circumference of a roof drain sized for the same roof area

IPC 1106.5 Parapet wall scuppers states the parallel rule for scuppers used as primary roof drainage:

Where scuppers are used for primary roof drainage or for secondary (emergency overflow) roof drainage or both, the quantity, size, location and inlet elevation of the scuppers shall be chosen to prevent the depth of ponding water on the roof from exceeding the maximum water depth the roof was designed for, as determined by Section 1611.1 of the International Building Code. Scupper openings shall be not less than 4 inches in height and have a width equal to or greater than the circumference of a roof drain sized for the same roof area. The flow through the primary system shall not be considered when locating and sizing secondary scuppers.

Worked scupper width

A roof area requires a 6-inch roof drain. What width must a secondary scupper be?

  • Circumference of a 6-inch circle = pi x diameter = 3.1416 x 6 = 18.85 inches.
  • Required scupper opening: not less than 4 inches high and not less than approximately 18.9 inches wide.

For an 8-inch drain: 3.1416 x 8 = 25.1 inches wide.

Siphonic roof drainage — IPC 1107

Siphonic roof drains and drainage systems shall be designed in accordance with ASME A112.6.9 and ASPE 45.

A siphonic system runs full bore by design, using an air baffle at the drain to exclude air and create a siphon in the horizontal collector. Because it runs full, the collector can be nearly level and much smaller than a conventional gravity system. It is an engineered design; the IPC delegates it entirely to the two referenced standards.

Note that 1102.6 excludes siphonic roof drains from the ASME A112.6.4 / ASPE-IAPMO Z1034 flow-rating requirement, because a siphonic drain's performance is a property of the whole system, not the drain alone.

Controlled flow roof drain systems — IPC 1110

The opposite approach: deliberately store water on the roof and release it slowly, reducing peak load on the storm sewer.

RuleRequirement
1110.1 GeneralThe roof shall be designed for the storage of water. The system shall be an engineered system meeting the design, submittal, approval, inspection and testing requirements of Section 316.1, designed on the required rainfall rate per 1106.1
1110.2 Control devicesInstalled so the rate of discharge per minute does not exceed the values for continuous flow indicated in 1110.1
1110.3 InstallationRunoff control by control devices, which shall be protected by strainers
1110.4 Minimum number of roof drainsNot less than two roof drains in roof areas 10,000 square feet or less; not less than four roof drains in roofs over 10,000 square feet

1110.4 is the most testable line in the section: two drains up to 10,000 square feet, four drains above it. A controlled-flow roof depends on standing water, so a single blocked drain is an unacceptable risk — redundancy is mandatory.

1110.1's cross-reference to Section 316.1 is the alternative engineered design section from Chapter 2 of this guide: a registered design professional, technical data, two sets of signed and sealed construction documents including a riser diagram, and code official approval recorded on the permit.

Putting the primary and secondary systems together

A warehouse has a 12,000 square foot roof surrounded by a 3-foot parapet, in Denver.

StepResultBasis
Is secondary drainage required?Yes — the parapet entraps water1108.1
Design rainfall rate2.4 inches per hour for DenverAppendix B / Figure 1106.1(1)
Total design flow0.0104 x 12,000 x 2.4 = 299.5 gpmEquation 11-1
Primary system sizingSize conductors and horizontal drains for 299.5 gpm across the drains provided1106.2, 1106.3
Secondary system sizingSize for the same 299.5 gpm, with no credit for the primary system1108.3
Secondary dischargeSeparate end point, above grade, normally observed1108.2
If scuppers are used4 inches minimum height, width at least the circumference of a roof drain sized for the same area1106.5, 1108.3
If a single primary/secondary assembly is usedIndependent inlet and outlet for each drain1108.1
If a controlled flow system is usedEngineered per 316.1; four roof drains minimum, since the roof exceeds 10,000 square feet1110.1, 1110.4
Loading diagram...
Primary and secondary roof drainage
Test Your Knowledge

When sizing a secondary (emergency overflow) roof drain system, how much credit is given to the primary system?

A
B
C
D
Test Your Knowledge

What is the minimum height of a scupper opening under IPC 1106.5 and 1108.3?

A
B
C
D
Test Your Knowledge

A controlled flow roof drain system serves a roof area of 14,000 square feet. How many roof drains are required at a minimum?

A
B
C
D
Test Your Knowledge

Where must a secondary roof drain system discharge under IPC 1108.2?

A
B
C
D