9.3 Sizing Building Drains, Building Sewers, and Horizontal Branches

Key Takeaways

  • IPC Table 710.1(1) sizes building sewers, building drains and branches of the building drain; Table 710.1(2) sizes horizontal fixture branches and vertical stacks.
  • IPC Table 710.1(1) footnote a requires the minimum size of any building drain serving a water closet to be 3 inches.
  • IPC Table 710.1(1) allows a 4-inch building drain 180 dfu at 1/8 inch per foot, 216 dfu at 1/4 inch per foot and 250 dfu at 1/2 inch per foot.
  • IPC Table 710.1(1) allows a 3-inch building drain 36 dfu at 1/8 inch per foot and 42 dfu at 1/4 inch per foot.
  • IPC Table 710.1(2) limits a 3-inch horizontal fixture branch to 20 dfu and a 4-inch horizontal branch to 160 dfu.
Last updated: September 2026

Two tables, two jobs

This is where candidates lose points. IPC 710.1 assigns each table a specific class of pipe:

Use this tableFor this pipe
Table 710.1(1) Building Drains and SewersBuilding sewer, building drain, and horizontal branches of the building drain
Table 710.1(2) Horizontal Fixture Branches and StacksHorizontal fixture branches and vertical soil or waste stacks

The phrase "branch of the building drain" means a horizontal branch that connects to the building drain itself — below the lowest floor, typically under the slab. A "horizontal fixture branch" is a horizontal drain above that, receiving fixtures and carrying them to a stack.

Table 710.1(1) is organized by slope because the pipe runs horizontally its entire length. Table 710.1(2) has no slope column for stacks because a stack is vertical.

Table 710.1(1) — building drains and sewers

Maximum dfu connected to any portion of the building drain or building sewer, including branches of the building drain:

Pipe size1/16 in/ft1/8 in/ft1/4 in/ft1/2 in/ft
1-1/411
1-1/233
22126
2-1/22431
3364250
4180216250
5390480575
67008401,000
81,4001,6001,9202,300
102,5002,9003,5004,200
123,9004,6005,6006,700
157,0008,30010,00012,000

Footnote a: the minimum size of any building drain serving a water closet shall be 3 inches. That floor overrides the dfu math. A single private water closet is 3 dfu, which a 2-inch line would carry numerically — but a water closet needs 3 inches.

Notice the enormous jump from 3 inches to 4 inches: 42 dfu to 216 dfu at 1/4 inch per foot, more than a fivefold increase for a one-size step. Flow capacity in a partially full gravity pipe scales roughly with diameter to the 8/3 power, which is why the 3-to-4 step is so dramatic and why dropping a 4-inch drain to 3 inches to clear an obstruction is almost never workable.

Notice also the blank cells. The 1/16 inch per foot column is empty below 8 inches because Table 704.1 does not allow that slope on smaller pipe.

Table 710.1(2) — horizontal fixture branches and stacks

Pipe sizeHorizontal branch totalStack: discharge into one branch intervalStack of 3 branch intervals or lessStack greater than 3 branch intervals
1-1/23248
2661024
2-1/21292042
320204872
416090240500
53602005401,100
66203509601,900
81,4006002,2003,600
102,5001,0003,8005,600
123,9001,5006,0008,400

Footnote a: the table does not include branches of the building drain — refer to Table 710.1(1).

Compare a 3-inch pipe across the two tables: 20 dfu as a horizontal fixture branch, but 36 to 50 dfu as a building drain depending on slope. The horizontal branch value is lower because a branch discharges into a stack, where surging matters, while a building drain runs to open sewer.

Worked sizing: a 24-unit apartment building

Each of 24 units has one bathroom group (1.6 gpf water closet), one kitchen sink and one residential clothes washer. There is also a common laundry with two commercial clothes washers and one service sink, and three floor drains in the mechanical room.

Step 1 — total dfu:

Fixturedfu eachCountSubtotal
Bathroom group, 1.6 gpf524120
Kitchen sink, domestic22448
Clothes washer, residential22448
Clothes washer, commercial326
Service sink212
Floor drain236
Total230 dfu

Step 2 — building drain. Enter Table 710.1(1) at 230 dfu:

  • At 1/8 inch per foot: 4-inch carries 180 (too small); 5-inch carries 390 — sufficient.
  • At 1/4 inch per foot: 4-inch carries 216 — still too small; 5-inch carries 480 — sufficient.
  • At 1/2 inch per foot: 4-inch carries 250 — sufficient, if that slope is achievable.

So a 5-inch building drain at 1/8 or 1/4 inch per foot, or a 4-inch drain at 1/2 inch per foot if the site has the fall. In practice the 5-inch at 1/4 inch per foot is the ordinary answer; 1/2 inch per foot over a long run demands a great deal of depth.

Step 3 — check the water closet floor. Footnote a requires at least 3 inches for any building drain serving a water closet. Satisfied.

Step 4 — the stack. If the building has three stacks each serving 8 units, each stack carries roughly (8 x 5) + (8 x 2) + (8 x 2) = 72 dfu and spans four stories, which is more than three branch intervals. From Table 710.1(2), "stack greater than 3 branch intervals": a 3-inch stack carries 72 dfu — exactly at the limit — and a 4-inch stack carries 500. Because there is no margin at 3 inches and every added fixture would bust it, 4 inches is the sound choice.

Step 5 — horizontal branches. A branch serving two bathroom groups plus two kitchen sinks is (2 x 5) + (2 x 2) = 14 dfu. Table 710.1(2) horizontal branch column: 2-1/2 inch carries 12 (too small), 3-inch carries 20 — a 3-inch branch works, and it also satisfies the requirement that a branch serving a water closet be at least 3 inches.

Offsets

  • IPC 710.1.1 Horizontal stack offsets: sized as required for building drains per Table 710.1(1), except as required by 711.3.
  • IPC 710.1.2 Vertical stack offsets: sized as required for straight stacks per Table 710.1(2), except where required to be sized as a building drain per 711.1.1.

The logic is physical: a horizontal offset behaves like a building drain — flow decelerates and runs partially full along a slope. A vertical offset is still a stack.

Section 711 adds special rules for buildings of five stories or more, covered in the next section of this guide.

Loading diagram...
Choosing the right drainage sizing table
Test Your Knowledge

A building drain serves a single private water closet, a lavatory and a bathtub. What is the minimum building drain size?

A
B
C
D
Test Your Knowledge

A building drain must carry 230 drainage fixture units at a slope of 1/4 inch per foot. What is the minimum size?

A
B
C
D
Test Your Knowledge

Which table sizes a horizontal branch of the building drain?

A
B
C
D
Test Your Knowledge

A 3-inch soil stack spans six branch intervals. What is its maximum drainage fixture unit load?

A
B
C
D