7.2 Air Gaps and the Backflow Preventer Family
Key Takeaways
- IPC 608.14.1 measures the air gap vertically from the lowest end of the potable water outlet to the flood level rim of the fixture or receptacle it discharges into.
- IPC Table 608.16.1 requires a 1-inch air gap away from a wall for fixtures with effective openings not greater than 1/2 inch, and two times the effective opening diameter for openings greater than 1 inch.
- IPC 608.14.5 requires pressure vacuum breaker assemblies to be installed with the critical level not less than 12 inches above all downstream piping and outlets.
- IPC 608.16.4 requires the critical level of atmospheric-type or pressure-type vacuum breakers to be set not less than 6 inches above the flood level rim of the fixture or device.
- IPC 608.14.2 requires the relief opening of a reduced pressure principle assembly to discharge by air gap and be prevented from being submerged.
The air gap
IPC 608.14.1: the minimum required air gap shall be measured vertically from the lowest end of a potable water outlet to the flood level rim of the fixture or receptacle into which the outlet discharges. Air gaps comply with ASME A112.1.2; air gap fittings comply with ASME A112.1.3.
An air gap is the only method that cannot fail mechanically. There is no seat to foul, no check to stick, no diaphragm to tear. It is rated for both backsiphonage and backpressure at both low and high hazard. Everything else in Table 608.1 is a compromise made because a physical gap is not practical at that location.
Table 608.16.1 — minimum required air gaps
| Fixture | Away from a wall | Close to a wall |
|---|---|---|
| Lavatories and other fixtures with effective openings not greater than 1/2 inch | 1 inch | 1-1/2 inches |
| Sinks, laundry trays, gooseneck back faucets and other fixtures with effective openings not greater than 3/4 inch | 1-1/2 inches | 2-1/2 inches |
| Over-rim bath fillers and other fixtures with effective openings not greater than 1 inch | 2 inches | 3 inches |
| Drinking water fountains, single orifice not greater than 7/16 inch, or multiple orifices totaling 0.150 square inch | 1 inch | 1-1/2 inches |
| Effective openings greater than 1 inch | 2 times the diameter of the effective opening | 3 times the diameter of the effective opening |
The close to a wall column exists because a nearby vertical surface lets water climb by capillary action and wall-following flow, defeating a gap that would otherwise work. Footnote a defines when the "away from a wall" column applies: walls or obstructions spaced from the nearest inside edge of the spout opening by more than three times the effective opening diameter for a single wall, or more than four times for two intersecting walls.
IPC 608.16.1 adds one limitation: openings and outlets equipped for hose connection shall be protected by means other than an air gap. A hose defeats a gap by definition — you can always lift the end.
Worked air gap
A 2-inch nonpotable fill line discharges into an open tank, with a wall 3 inches from the spout.
- Effective opening is greater than 1 inch, so the last row applies.
- Is it "close to a wall"? The wall is 3 inches away, and three times the effective opening (2 inches) is 6 inches. Since 3 inches is less than 6 inches, this is the close to a wall case.
- Required air gap: 3 times 2 inches = 6 inches, measured vertically from the lowest end of the outlet to the flood level rim.
The mechanical devices
Reduced pressure principle backflow prevention assembly (RPZ) — 608.14.2
Two independently acting check valves separated by a relief valve zone held at a pressure lower than the supply. If either check fouls, the relief valve dumps to atmosphere and the zone can never rise to supply pressure.
- Standards: ASSE 1013, AWWA C511, CSA B64.4, CSA B64.4.1. Detector version: ASSE 1047.
- Rated high or low hazard, backpressure or backsiphonage. Sizes 3/8 to 16 inches.
- Permitted under continuous pressure.
- The relief opening shall discharge by air gap and shall be prevented from being submerged.
IPC 608.15.2.1 Relief port piping: the termination of the piping from the relief port or air gap fitting must discharge to an approved indirect waste receptor or to the outdoors where it will not cause damage or create a nuisance, and the receptor and drainage piping must be sized to drain the maximum discharge flow rate from the relief port as published by the manufacturer. An RPZ dumping 40 gpm into a 2-inch floor drain rated for 20 gpm floods the room.
Double check backflow prevention assembly (DC) — 608.14.7
Two independently acting checks in series, with shutoffs and test cocks.
- Standards: ASSE 1015, CSA B64.5, CSA B64.5.1, AWWA C510. Detector fire protection version: ASSE 1048.
- Rated low hazard only, but handles both backpressure and backsiphonage. Sizes 3/8 to 16 inches.
- Capable of operating under continuous pressure.
Pressure vacuum breaker assembly (PVB) — 608.14.5
A spring-loaded air inlet plus a check valve, with shutoffs and test cocks.
- Standards: ASSE 1020 or CSA B64.1.2. Spill-resistant version (SVB): ASSE 1056 or CSA B64.1.3.
- Rated high or low hazard, backsiphonage only. Sizes 1/2 to 2 inches.
- Installed with the critical level not less than 12 inches above all downstream piping and outlets.
- Shall not be installed where spillage could cause damage to the structure.
Atmospheric vacuum breaker (AVB) — 608.14.6, 608.16.4
A simple float or poppet that opens to atmosphere when supply pressure drops.
- Pipe-applied: ASSE 1001 or CSA B64.1.1. Hose connection types: ASME A112.21.3, ASSE 1011, 1019, 1035, 1052, CSA B64.2 family.
- Rated high or low hazard, backsiphonage only.
- Critical level set not less than 6 inches above the flood level rim of the fixture or device (608.16.4). Pipe-applied vacuum breakers are installed not less than 6 inches above the flood level rim of the fixture, receptor or device served.
- No valve may be installed downstream of an AVB, and it may not be under continuous pressure — the poppet will stick. IPC 608.17.5 states the downstream valve prohibition explicitly for irrigation.
- Shall not be installed under exhaust hoods or similar locations containing toxic fumes or vapors (608.16.4).
Deck-mounted and integral vacuum breakers — 608.16.4.1
Approved deck-mounted or equipment-mounted vacuum breakers, and faucets with integral atmospheric vacuum breakers or spill-resistant assemblies, are installed per the manufacturer with the critical level not less than 1 inch above the flood level rim.
Other devices
| Device | Section | Hazard | Backflow type | Sizes |
|---|---|---|---|---|
| Backflow preventer with intermediate atmospheric vent (ASSE 1012, 1081, CSA B64.3) | 608.14.3 | Low | Backpressure or backsiphonage | 1/4 to 3/4 in |
| Dual check backflow preventer (ASSE 1024, CSA B64.6) | 608.14.9 | Low | Backpressure or backsiphonage | 1/4 to 1 in |
| Chemical dispenser backflow device (ASSE 1055 or air gap fitting) | 608.14.8 | — | — | — |
| Hose connection backflow preventer (ASSE 1052, ASME A112.21.3) | Table 608.1 | High or low | Low head backpressure, rated working pressure, backpressure or backsiphonage | 1/2 to 1 in |
| Hose connection vacuum breaker (ASSE 1011, CSA B64.2) | Table 608.1 | High or low | Low head backpressure or backsiphonage | 1/2, 3/4, 1 in |
| Laboratory faucet backflow preventer (ASSE 1035, CSA B64.7) | Table 608.1 | High or low | Low head backpressure and backsiphonage | — |
| Vacuum breaker wall hydrant, frost-resistant, automatic draining (ASSE 1019) | Table 608.1 | High or low | Low head backpressure or backsiphonage | 3/4, 1 in |
| Carbonated beverage machine preventer (ASSE 1022) | Table 608.1 | Low | Backpressure or backsiphonage | 1/4 to 3/8 in |
| Antisiphon fill valve (ASSE 1002) | Table 608.1 | High | Backsiphonage only | — |
The barometric loop — 608.14.4
Barometric loops shall precede the point of connection and shall extend vertically to a height of 35 feet. A barometric loop shall only be utilized as an atmospheric-type or pressure-type vacuum breaker.
Thirty-five feet is not arbitrary: it is just above the theoretical maximum height (33.9 feet) that atmospheric pressure can lift a column of water. Above that height, siphonage is physically impossible. It is backsiphonage protection only.
Location and protection of devices
- 608.15: access to backflow preventers as specified by the manufacturer's instructions.
- 608.15.1: outdoor enclosures for backflow prevention devices comply with ASSE 1060.
- 608.15.2: backflow preventers shall not be located in areas subject to freezing, except where they can be removed by means of unions or are protected from freezing by heat, insulation or both. In Colorado this is a working constraint, not a theoretical one.
A faucet with a 1/2-inch effective opening discharges into a lavatory, with a wall closer than three times the opening diameter. What minimum air gap does Table 608.16.1 require?
At what height above all downstream piping and outlets must the critical level of a pressure vacuum breaker assembly be installed?
Which single device is approved for high hazard applications subject to backpressure and may be installed under continuous pressure?
What is the required vertical height of a barometric loop, and what protection does it provide?