13.2 Motor Branch-Circuit Conductors
Key Takeaways
NEC 430.22(A) requires branch-circuit conductors supplying a single continuous-duty motor to have ampacity not less than 125% of the motor’s Table FLC
Select conductor size from Table 310.16 (or other applicable ampacity tables) after 110.14(C) termination limits and any 310.15 adjustment/correction — 125% of FLC is the motor-circuit minimum, not a free pass to the 90°C column
Several motors on one circuit / feeder follow 430.24: 125% of the highest-rated motor FLC plus the sum of the other motor FLCs (plus other loads as applicable)
Do not size motor branch conductors from nameplate FLA or from the overload heater rating
Motor circuit EGCs still follow 250.122 based on the branch-circuit SC/GF device rating — Article 430 does not replace the EGC table
Conductor Sizing After You Have the Right FLC
Section 13.1 locked the current source: Table FLC. This section applies Article 430 Part II conductor rules that produce the wire size Prov expects on Motors and Controls items.
On Arkansas’s open-book form, the arithmetic is simple — FLC × 1.25 — but candidates lose points by (1) using nameplate, (2) forgetting 125%, or (3) picking a Table 310.16 size from the wrong temperature column.
Tab 430.22, 430.24, Table 430.250, Table 310.16, and 110.14(C).
Single Continuous-Duty Motor — 430.22(A)
430.22(A) general rule: conductors that supply a single motor used in a continuous-duty application shall have an ampacity of not less than 125% of the motor’s full-load current as determined by 430.6(A) — meaning Table FLC for ordinary motors.
Worked example A — 10 hp, 460 V, 3φ
- Table 430.250 FLC for 10 hp @ 460 V ≈ 14 A (verify).
- Minimum conductor ampacity = 14 × 1.25 = 17.5 A.
- From Table 310.16, 12 AWG copper in the 75°C column is typically 25 A — adequate for 17.5 A after termination rules are respected.
- Do not stop at “14 A needs 14 AWG.” The motor rule is 125%, so 17.5 A is the floor before ampacity table selection.
Worked example B — 25 hp, 230 V, 3φ
- Table 430.250 FLC for 25 hp @ 230 V ≈ 68 A (verify).
- Minimum ampacity = 68 × 1.25 = 85 A.
- Select copper (or aluminum if the stem says so) with allowable ampacity ≥ 85 A at the permitted termination temperature — often 4 AWG Cu or 3 AWG Cu depending on column and conditions (open Table 310.16; do not memorize from a blog).
Worked example C — single-phase shop motor
A 5 hp, 230 V, single-phase motor uses Table 430.248 FLC (commonly 28 A — verify), then 28 × 1.25 = 35 A minimum ampacity. Mixing in the three-phase 15.2 A value is a classic wrong path.
What “Continuous Duty” Means Here
Most general-purpose motors on Prov stems are treated as continuous duty unless the question specifies intermittent, periodic, or varying duty and points you to other rows in 430.22 / duty-cycle tables. If the stem is silent, apply 430.22(A) 125%.
Other duty types can require different percentages of FLC for conductors — open the specific subsection only when the stem names the duty cycle. Do not invent a reduced percentage for a silent continuous-duty motor just because the machine “only runs eight hours.”
Multi-Motor and Combination Loads — 430.24
430.24 covers conductors supplying several motors, or motors plus other loads. The core pattern for several motors:
- Ampacity ≥ 125% of the highest-rated motor FLC + sum of the FLC of all other motors + other load currents as required.
Worked example D — three motors on one feeder/circuit conductor set
Motors (all 460 V, 3φ; FLCs from Table 430.250 — verify):
| Motor | FLC |
|---|---|
| 10 hp | 14 A |
| 5 hp | 7.6 A |
| 3 hp | 4.8 A |
Highest-rated motor FLC = 14 A.
Minimum conductor ampacity = (14 × 1.25) + 7.6 + 4.8 = 17.5 + 12.4 = 29.9 A.
Then select conductors ≥ 29.9 A from Table 310.16 under the correct temperature column.
Trap: Applying 125% to every motor (14×1.25 + 7.6×1.25 + 4.8×1.25) oversizes relative to 430.24 and will not match the keyed answer. Only the largest motor gets the 125% factor in this combination rule.
Termination Temperature Still Applies
Motor circuits do not escape 110.14(C). If the breaker and starter lugs are 75°C-rated, you generally select ampacity from the 75°C column of Table 310.16 even when the insulation is THHN 90°C. You may still use 90°C ampacity as a starting point for adjustment/correction where the Code allows, but the equipment termination limit controls final sizing to the terminations.
Also apply 310.15 ambient correction and more-than-three current-carrying-conductor adjustment when the stem gives those facts. Compute:
- Motor minimum from 430.22 / 430.24.
- Adjusted/corrected ampacity of the chosen size.
- Confirm adjusted ampacity still ≥ the motor minimum.
Motor Circuit Equipment Grounding Conductors
The branch-circuit EGC is sized from Table 250.122 based on the rating of the branch-circuit short-circuit and ground-fault protective device, not from 125% of FLC and not from 250.66. Article 430 tells you how to pick the SC/GF device (§13.4); Article 250 tells you the EGC once that device rating is known.
If a stem asks for the EGC of a motor branch circuit protected by a 70 A breaker, open 250.122 for 70 A — do not open Table 430.250 again looking for a grounding column that is not there.
Conductors on the Load Side of a Drive or Soft Starter
When an adjustable-speed drive or similar equipment is involved, manufacturer markings and Article 430 drive-related sections can change which current is used for load-side conductors. On Prov JW items, if the stem is a plain across-the-line motor starter, stay with 430.22 and Table FLC. If the stem explicitly names a VFD and input/output currents, read the applicable drive conductor rules rather than blindly multiplying motor FLC.
Exam Workflow — Branch Conductor Stems
- Identify single motor vs several motors / other loads.
- Pull Table FLC (correct table and voltage).
- Apply 430.22(A) (×1.25) or 430.24 (1.25× largest + others).
- Select from Table 310.16 with 110.14(C).
- Adjust for ambient/bundling if given.
- Only then move to overload (§13.3) or SC/GF (§13.4) — those are different percentages and sometimes different currents.
Timed Open-Book Tips for §13.2
- Scratch-paper line:
FLC = ____; ×1.25 = ____ A min. - Multi-motor: star the largest FLC before multiplying.
- Wire size ≠ breaker size; finish conductors before Table 430.52.
- Nameplate FLA on the page is usually a distractor for this section.
- If ampacity after adjustment falls below 17.5 A (or whatever minimum you calculated), upsize — do not ignore 310.15 facts the stem handed you.
Under NEC 430.22(A), what is the general minimum ampacity of branch-circuit conductors supplying a single continuous-duty motor?
100% of the motor nameplate FLA
115% of the Table FLC
125% of the motor full-load current as determined under 430.6(A) (Table FLC for ordinary motors)
250% of the Table FLC
A 10 hp, 460 V, three-phase continuous-duty motor has a Table 430.250 FLC of 14 A. Ignoring adjustment/correction, what minimum conductor ampacity does 430.22(A) require?
17.5 A
14 A
28 A
35 A
Three 460 V, three-phase motors with Table FLCs of 14 A, 7.6 A, and 4.8 A are supplied by the same conductors. Per 430.24, what minimum ampacity is required for those conductors (motors only, no other loads)?
26.4 A
33.0 A
14 × 1.25 + 7.6 × 1.25 + 4.8 × 1.25 = 33.0 A
14 × 1.25 + 7.6 + 4.8 = 29.9 A
After calculating a motor branch-circuit minimum ampacity of 17.5 A, which limitation still commonly controls the Table 310.16 column you may use for termination-limited sizing?
Always the 90°C column because motor circuits are exempt from 110.14(C)
110.14(C) termination temperature limits (often the 75°C column on standard equipment)
Table 430.52 percentages instead of Table 310.16
Only the motor service factor
Sections you finish are checked off in the contents.