7.4 Continuous Loads & OCPD Sizing
Key Takeaways
- A continuous load is expected to continue for 3 hours or more (Art. 100) — lighting and process loads are frequent continuous-load flags on Prov stems
- Branch-circuit and feeder OCPDs are generally sized at not less than 125% of continuous load plus 100% of noncontinuous load (210.19/210.20 and 215.2/215.3 parallel logic)
- NEC 215.3 requires feeder overcurrent devices to have a rating not less than the noncontinuous load plus 125% of the continuous load unless listed for 100% operation
- Conductor ampacity (215.2) and OCPD rating (215.3 / 210.20) both carry 125% continuous-load logic — calculate each, then apply 240.4 pairing
- Next-size-up under 240.4(B) does not erase the continuous-load 125% calculation; compute the minimum rating first, then select a standard device
Continuous Loads Tie Feeder Ampacity to Breaker Size
Sections 7.1–7.3 taught feeder ampacity, Article 240 device selection, and taps. This section welds them together with the continuous-load 125% rules that appear repeatedly on the Arkansas Journeyman (Prov) exam. If you remember only one sizing slogan for this chapter, make it: size for continuous load at 125%, then pick a standard OCPD that protects the conductors under 240.4.
Tab Article 100 (Continuous Load), 210.19, 210.20, 215.2, 215.3, 230.42 (for service comparisons), 240.4, and 240.6.
Definition — Continuous Load
Continuous load (Art. 100): A load where the maximum current is expected to continue for 3 hours or more.
Exam recognition cues:
- Store or warehouse lighting left on for business hours.
- Office lighting and certain receptacle loads treated as continuous in design notes.
- Industrial process heaters or equipment specified as continuous.
- Stems that explicitly say “continuous load” or “operates for 3 hours or more.”
If the stem does not establish continuity, do not invent a 125% adder for the entire load. Conversely, when the stem says continuous, missing the 125% factor is an instant miss.
Why 125% Exists
Continuous current heats conductors and OCPDs for extended periods. The Code’s 125% factor builds margin into:
- Conductor ampacity requirements for feeders and branch circuits.
- OCPD ratings that supply those circuits (unless equipment is listed for operation at 100% of its rating under the applicable section).
Think of 125% as applying to the continuous portion, then adding noncontinuous load at 100%, unless a specific rule says otherwise.
Branch-Circuit Continuous-Load Rules — 210.19 / 210.20
For branch circuits (needed because feeder stems sometimes mix in branch math, and the same 125% logic appears in both places):
- 210.19(A) — branch-circuit conductors shall have ampacity not less than the maximum load to be served; for continuous loads, ampacity not less than noncontinuous + 125% continuous (parallel structure to feeders).
- 210.20(A) — branch-circuit OCPDs shall have a rating not less than the noncontinuous load plus 125% of the continuous load, with the listed 100%-rated assembly exception path.
These branch rules mirror feeder rules so you do not learn two contradictory formulas.
Feeder Continuous-Load Rules — 215.2 / 215.3
Conductors — 215.2(A)(1)
Feeder conductor ampacity ≥ noncontinuous load + 125% continuous load (absent the listed-assembly exception).
Overcurrent devices — 215.3
215.3 requires the feeder overcurrent device rating / setting to be not less than the noncontinuous load plus 125% of the continuous load. Exception: where the assembly — including the OCPD — is listed for operation at 100% of its rating, the continuous load may be permitted up to the device’s rating under the exception’s conditions.
Prov paired question pattern:
- Compute minimum feeder ampacity (215.2).
- Compute minimum OCPD rating (215.3).
- Choose conductors from Table 310.16 that meet ampacity.
- Choose a standard OCPD from 240.6(A) that is ≥ the 215.3 minimum.
- Verify 240.4 still protects those conductors (including 240.4(B)/(C)/(D) as applicable).
Often the conductor ampacity minimum and the OCPD minimum calculate to the same 125% number before standard-size rounding — then 240.4(B) may allow the next standard size above conductor ampacity when conditions are met.
Worked Example (Open-Book Style)
Feeder load: 80 A continuous + 30 A noncontinuous.
- Minimum ampacity / minimum OCPD basis = 30 + (80 × 1.25) = 30 + 100 = 130 A.
- Conductors: select a copper size from Table 310.16 (correct temperature column) with ampacity ≥ 130 A after adjustment/correction.
- OCPD: 130 A is not a standard 240.6(A) rating. Nearby standards include 125 A and 150 A. Because 125 A is below the 130 A continuous-load minimum, 125 A is too small. Select 150 A if that rating also satisfies conductor protection rules.
- Confirm the chosen conductors’ ampacity can be protected by 150 A under 240.4 (next-size-up / ampacity relationship).
Trap: Calculating 80 + 30 = 110 A and picking a 110 A or 125 A breaker without the continuous 125% adder.
100%-Rated Assemblies — Use Only When the Stem Gives Them
The exception path for equipment listed for 100% continuous operation is real, but Prov distractors love it. Apply it only when:
- The stem states the breaker/assembly is listed/rated for 100% operation, and
- You verify the exception language in 215.3 / 210.20 (and related equipment standards).
Otherwise, default to 125% of continuous + 100% noncontinuous.
Interaction with Services (Do Not Cross-Wire Articles)
230.42 uses the same continuous-load philosophy for service-entrance conductors. That does not mean you cite 230.42 on a feeder stem. Identity check:
| System part | Continuous-load conductor rule | Continuous-load OCPD rule |
|---|---|---|
| Service-entrance | 230.42 | Service OCPD rules in Art. 230 + 240 as applicable |
| Feeder | 215.2 | 215.3 |
| Branch circuit | 210.19 | 210.20 |
Same math family, different section numbers — answers are often wrong solely because of the wrong article citation in a “which section requires…” stem.
Continuous Loads on Taps
If a feeder tap terminates in an OCPD that supplies continuous load, the terminating device still needs the 215.3 / 210.20 continuous-load rating logic for what it supplies. The upstream feeder OCPD protecting the large feeder is sized for the feeder’s load; the tap rule only allows unprotected (or differently protected) conductor length under 240.21 — it does not erase continuous-load sizing at the load-end device.
Multioutlet and Receptacle Nuances
For branch circuits supplying cord-and-plug connected equipment, continuous-load and receptacle rules interact with Article 210 ratings. Also remember 240.4(B) denies next-size-up for certain multi-receptacle portable-load branch circuits. Continuous-load math and next-size-up permission are independent checks — both must pass.
Practical Exam Checklist — Continuous Load Stems
- Does the stem establish a continuous load (definition or explicit label)?
- Split continuous vs noncontinuous amperes.
- Compute I_req = noncontinuous + 1.25 × continuous.
- Apply I_req to conductors (215.2 / 210.19) and to OCPDs (215.3 / 210.20).
- Select standard OCPD ≥ I_req from 240.6(A).
- Confirm 240.4 conductor protection (small-conductor caps, ≤800 A next size, >800 A no round-up).
- Only if listed 100%-rated assembly is in the stem, reopen the exception.
Timed Tips for the Whole Chapter 7 Cluster
- Feeder identity first (Art. 100 / 215 vs 230 vs 210).
- Continuous 125% next (215.2 / 215.3).
- Table 310.16 + 110.14(C) for conductors.
- 240.6 + 240.4 for device pairing.
- 240.21 only when length-from-supply / tap language appears.
Mastering that order turns the 8-item Services/Feeders/OCP block into a lookup sequence instead of a memory contest on a 3-hour, 60-question, 70% Prov Arkansas JW exam using NEC 2023.
Per the NEC definition, a continuous load is one where the maximum current is expected to continue for at least how long?
Under NEC 215.3, what is the general minimum rating basis for a feeder overcurrent device supplying continuous and noncontinuous loads (absent a listed 100%-rated assembly exception)?
A feeder supplies 60 A continuous and 20 A noncontinuous. What minimum overcurrent-device rating basis does 215.3 require before selecting a standard 240.6(A) size (no 100%-rated exception)?
After computing a 215.3 continuous-load minimum of 130 A for a feeder OCPD, which standard rating from 240.6(A) is the smallest that generally satisfies that minimum?