Cheat sheet

City & Guilds 2391-52 Cheat Sheet

Quick Facts

Qualification
City & Guilds Level 3
Award reference
603/1275/0
Theory test
2391-052
Theory format
60 MCQs · 120 minutes
Theory conditions
Open book and invigilated
Theory pass
About 75%, subject to adjustment
Practical assignment
2391-502
Award requirement
Pass theory and practical
Guided learning
50 hours
Total qualification time
67 hours
Sitting edition
Confirm with your centre

Statutory Duties vs Technical Standard

EAWR

  • Legal duties in Great Britain
  • Controls work and electrical danger

BS 7671

  • UK installation technical standard
  • Part 6 covers verification

Apply applicable law and technical standard

Document Picker

  1. New installation→EIC with inspection and test schedules
  2. New circuit in existing installation→EIC(Apply initial verification to new work)
  3. Minor work, existing circuit only→MEIWC where suitable(Record the agreed work)
  4. Replacement consumer unit→EIC(Verify affected circuits)
  5. Condition of existing installation→EICR with schedules(Agree scope and limitations first)

Test Blueprint

LO1 requirements
13 online questions
LO2 safety
3 online questions
LO3 inspection
11 online questions
LO4 testing
33 online questions
LO5 performance
Practical assessment only
Online test weights
Published City & Guilds percentages

Book Rules

2391-052 references
BS 7671, On-Site Guide, GN3
GN3
Guidance Note 3, Inspection & Testing
Externally marked tests
Paper copies only
Page markers and highlighting
Permitted within book rules
Added formulas or procedures
Prohibited additions
Reference edition
Current unless City & Guilds specifies
Current UK wiring standard
BS 7671:2018+A4:2026
A4 assessment alignment
Check live centre instructions
Current IET Guidance Note 3
10th edition covers Amendment 4

Certificates and Reports

EIC
Electrical Installation Certificate
EIC trigger
New installation or new circuit
MEIWC
Minor Electrical Installation Works Certificate
MEIWC scope
Minor work on existing circuits
Consumer unit replacement
Use Electrical Installation Certificate
EICR
Electrical Installation Condition Report
EICR purpose
Suitability for continued service
Part 6 road map
Chapters 64 initial, 65 periodic
Appendix 6
Model certificates, reports and schedules

Periodic Scope

Extent
Parts included in the inspection
Agreed limitations
Record exclusions and reasons
Operational limitations
Record access constraints and reasons
Previous records
Identify changes and compare results
Sampling
Agree and record its extent
Next inspection
Recommend interval with reasons
EICR schedules
Inspections, circuit details, test results

Prove, Test, Prove

Prove the indicator, test dead, prove again

Secure isolation firstUse two-pole indicatorRepeat indicator check

Dead Work vs Live Testing

Dead working

  • Isolate and secure all supplies
  • Prove dead at work point

Live testing

  • Dead working must be unreasonable
  • Live working must be reasonable
  • Take precautions to prevent injury

Meet all Regulation 14 conditions

Safe Isolation Checks

  1. Supply source uncertain→Identify and isolate all sources(Include backfeeds)
  2. Isolation could be reversed→Lock off and retain key(Attach warning notice)
  3. Before testing for voltage→Prove two-pole indicator(Use suitable proving source)
  4. Testing for dead→Check relevant conductor pairs(At point of work)
  5. Voltage detected→Stop and resolve source
  6. Dead checks complete→Re-prove voltage indicator
  7. Live work considered→Apply EAWR Regulation 14(All three conditions must hold)

Electrical Safety Duties

Electricity at Work Regulations
Statutory duties in Great Britain
BS 7671
Technical standard for electrical installations
EAWR Regulation 12
Isolation and cutting off supply
EAWR Regulation 13
Prevent accidental re-energisation during work
EAWR Regulation 14
Three conditions for live work
EAWR Regulation 16
Competence or appropriate supervision
GS38
Low-voltage test equipment guidance
Before testing
Assess risks and plan controls
Electrical safety law in NI
Electricity at Work Regulations 1991

Safe Isolation

Isolation point
Identify equipment and every supply
Lockout
Secure isolation and retain key
Warning notice
Identify isolated equipment
Prove dead
Suitable two-pole voltage indicator
Before and after proving dead
Check indicator on proving unit
Voltage present
Stop and resolve supply source
Alternative supplies
Check PV, batteries, UPS, generators
Non-contact voltage pen
Preliminary indication only

EICR Code Memory

Danger, potential danger, improvement, investigate

C1 immediateC2 urgentC3 recommendedFI advised under A4

Initial vs Periodic

Initial verification

  • New work before service
  • Correct and retest defects
  • Issue EIC or appropriate MEIWC

Periodic inspection

  • Assess continued suitability
  • Report within extent and limitations
  • Code observations on EICR

Purpose determines certificate or report

EICR Code Picker

  1. Immediate danger present→C1(Make safe where practicable)
  2. Potentially dangerous defect→C2(Urgent remedial action)
  3. Safety improvement advisable→C3(Advisory under A4)
  4. Potential issue cannot be verified→FI when further investigation justified(Advisory under A4)
  5. Area excluded by agreed scope→Record limitation and reason(FI needs an identified issue)
  6. One or more C1/C2 codes→Report unsatisfactory

Visual Inspection

Initial inspection
Before energising the installation
Equipment selection
Check suitability for external influences
Equipment condition
Look for damage or deterioration
Basic protection
Check barriers and enclosures
Fault protection
Check earthing and protective bonding
Circuit protection
Check protective device type and rating
Conductor identification
Check line, neutral and earth
Isolation and switching
Check provision, access and labels
IP first numeral
Access and solid-object protection
IP second numeral
Water ingress protection
Sensory evidence
Use sight, sound, smell safely

C2 vs FI Under A4

C2

  • Potential danger can be identified
  • Urgent remedial action
  • Overall outcome unsatisfactory

FI

  • Issue cannot be fully verified
  • Further investigation advised
  • Outcome unchanged by FI alone

Classify established risk when possible

EICR Observations

C1
Danger present, act immediately
C2
Potentially dangerous, urgent remedial action
C3
Safety improvement recommended
FI under Amendment 4
Further investigation is advised
A4 unsatisfactory outcome
Any C1 or C2
A4 C3 or FI alone
Advisory, outcome unaffected
Known safety defect
Classify the observed risk
A4 recipient guidance
Include guidance based on Appendix 6
N/A on inspection schedule
Item does not apply
LIM on inspection schedule
Documented inspection limitation
FI wording in A2:2022
Further investigation without delay

Ring Test Trio

Ends first, then line-neutral, then line-earth

r1 is linern is neutralr2 is CPCCross-connect opposite ends

Ze vs Zs

Ze

  • External loop impedance
  • Supply-side contribution

Zs

  • Whole earth fault loop
  • Includes circuit contribution

Use Zs for circuit disconnection

Test Selection

  1. Verify CPC path→Low-resistance continuity test
  2. Verify ring connections→Three-stage ring test
  3. Find insulation weakness→Insulation resistance test(Choose voltage from Table 64)
  4. SPD cannot reasonably be disconnected→250 V DC insulation test(Minimum 1 MΩ)
  5. Confirm correct switching conductor→Polarity test
  6. Check electrode resistance→Earth electrode resistance test(Use method suited to site)
  7. Verify overcurrent fault disconnection→Determine Zs(Compare applicable device limit)
  8. Check device breaking capacity→Determine prospective fault current
  9. Verify RCD operation→AC trip test at IΔn(Compare device time criterion)
  10. Verify multiphase conductor order→Check phase sequence
  11. Check voltage at load→Assess voltage drop(Use measured conductor resistance)

Test Order

Initial verification
Follow applicable test sequence
Dead tests
Before tests requiring energisation
Early dead tests
Continuity, insulation resistance, polarity
Earth electrode where present
Measure before initial energisation
Initial test failure
Correct defect, repeat affected tests
Periodic testing
Adapt tests to condition and scope
Continuity instrument
Low-resistance ohmmeter
Instrument accuracy
Calibration plus ongoing accuracy checks
GS38 leads and probes
Check condition and suitability

Ring vs Radial Continuity

Ring final

  • Three end-to-end readings first
  • Then two cross-connected stages

Radial

  • Verify CPC continuity to points
  • Use R1 + R2 or R2

Match continuity method to topology

Protective and Ring Continuity

CPC
Circuit protective conductor
R1 + R2
Line plus CPC path resistance
R2 continuity method
CPC resistance using wander lead
Protective bonding continuity
Measure and record resistance
Ring step 1
End-to-end r1, rn and r2
Ring step 2
Cross-connect opposite line and neutral
Ring step 3
Cross-connect opposite line and CPC
Ring step 3 midpoint
Approx. (r1 + r2) ÷ 4
Ring schedule value
Highest measured step 3 result
Unequal line and CPC sizes
Step 3 readings may vary
Parallel paths
Can mask discontinuity
Test lead resistance
Null or subtract before interpreting

Loop Impedance vs RCD Operation

Zs check

  • Verifies earth fault loop impedance
  • Compare applicable device criterion

RCD trip test

  • Inject rated residual test current
  • Time device operation

Select checks for protective measure

Insulation Resistance

Insulation resistance result
Record resistance in MΩ
230 V circuit standard test
500 V DC, minimum 1 MΩ
SELV or PELV
250 V DC, minimum 0.5 MΩ
Sensitive equipment or SPD
Disconnect to prevent damage/interference
Disconnecting SPD impracticable
250 V DC, minimum 1 MΩ
Electrical separation
Verify isolation from other circuits
SELV separation
Verify separation from Earth too
Low reading
Investigate affected circuit or equipment
SPD
Surge protective device

Earthing and Fault Current

Ze
External earth fault loop impedance
Zs
Total earth fault loop impedance
Calculated Zs
Ze + (R1 + R2)
Measured Zs screening
0.8 × tabulated maximum
Close to screening limit
Check detailed temperature correction
TT with RCD fault protection
RA × IΔn ≤ 50 V
RA in TT calculation
Electrode and protective conductor resistance
PSCC
Prospective short-circuit current
PEFC
Prospective earth fault current
PFC
Maximum prospective current at point
Breaking capacity
Check against prospective fault current
Earth electrode resistance
Fall-of-potential test where suitable

RCDs and Functional Checks

RCD verification
AC test at rated IΔn
General non-delay RCD
Up to 300 ms
Type S time-delayed RCD
130–500 ms
Type S time delay
Fault protection, where appropriate
Half-current or five-times tests
Optional diagnostic tests
Dead polarity
Verify switching in line conductor
Supply polarity
Confirm at the origin
Phase sequence
Check order is maintained
Functional testing
Confirm equipment operates as intended
Voltage drop
Use measured conductor resistance method
Resistive single-phase estimate
Design current × line-neutral resistance
IΔn
Rated residual operating current

Practical Handover

Inspect, test, interpret, document

Verify complianceClassify periodic observationsComplete schedulesSign relevant declaration

Task A vs Task B

Task A

  • 30-minute visual inspection
  • Books closed

Task B

  • 150-minute practical
  • Books for confirming results only

Task C is separately timed

Practical Tasks

502 Task A
Visual inspection, 30 minutes
Task A references
Closed book
502 Task B
Practical, 150 minutes
Task B references
Only for confirming test results
502 Task C
Short-answer paper, 80 minutes
Task C references
BS 7671, On-Site Guide, GN3
Task B permitted books
BS 7671, On-Site Guide, GN3

Practical Records

Initial work
Verify compliance and certify
Periodic work
Classify observations and report
Schedule entries
Record results against matching circuits
Sign-off
Use appropriate declarations and signatures
EICR handover
Include schedules and recipient guidance
Instrument records
Identify instruments used
Practical test evidence
Compare readings with applicable criteria

Common Traps

Combined Award

2391-052 theory test ≠ 2391-502 practical assignment

Reference Books

Books for confirming Task B results ≠ Permission to consult testing procedures

Proving Dead

Voltage pen indicates possible voltage ≠ Two-pole test proves dead

Initial Certification

Adding a new circuit ≠ Minor works certificate

Periodic Limitations

Agreed inaccessible area ≠ Automatic FI observation

Amendment 4 Outcome

FI alone ≠ Unsatisfactory EICR outcome

Insulation Test Voltage

250 V for connected SPD exception ≠ 0.5 MΩ SELV/PELV minimum

Ring Readings

Lowercase ring end-to-end readings ≠ Recorded uppercase R1 + R2

Loop Impedance

80% ambient screening figure ≠ Universal maximum permitted Zs

RCD Verification

Built-in RCD test button ≠ Instrumented RCD trip-time test

Protective Device Checks

Maximum earth fault loop impedance ≠ Minimum adequate device breaking capacity

Last Minute

  1. 1.Confirm assessment edition with your centre
  2. 2.Pass both 2391-052 and 2391-502
  3. 3.Testing has 33 online questions
  4. 4.Lock off every supply source
  5. 5.Prove voltage indicator before and after
  6. 6.Complete relevant dead tests before energising
  7. 7.Record three ring end-to-end values
  8. 8.Select insulation voltage from Table 64
  9. 9.Compare Zs with device-specific limit
  10. 10.Test RCD trip time at IΔn
  11. 11.Use EIC for new circuits
  12. 12.Agree and record EICR limitations
  13. 13.A4 C1/C2 make EICRs unsatisfactory
  14. 14.A4 C3/FI are advisory
  15. 15.Attach inspection and test schedules
Same family resources

Explore More City & Guilds UK Trade Qualifications

Continue into nearby exams from the same family. Each card keeps practice questions, study guides, flashcards, videos, and articles in one place.

More From This Family

Videos and articles for deeper review.