8.1 Wiring Methods and Raceways

Key Takeaways

  • NEC Article 300 is the umbrella for all wiring methods: 300.3(A) requires all conductors of the same circuit in the same raceway, 300.4 mandates a 1-1/4 in. edge distance or steel plate, 300.17 makes the lowest insulation temperature govern, and 300.22 restricts plenum installations
  • Raceway article numbers to memorize: RMC=342, IMC=344, EMT=358, FMC=350, ENT=362, RTRC=353, PVC=352, LFNC=356
  • Rigid PVC (Article 352) is prohibited in hazardous classified locations (352.12), cannot support luminaires, and requires Schedule 80 where subject to physical damage
  • FMC (Article 350) may serve as an equipment grounding conductor only for runs not exceeding 6 ft (350.60)
  • Trade sizes pair with metric designators: 1/2 in.=16, 3/4 in.=21, 1 in.=27, 1-1/4 in.=35, 1-1/2 in.=41, 2 in.=53; minimum raceway trade size is 1/2 in. (metric 16)
Last updated: August 2026

Why Wiring Methods Matter on the TX Journeyman Exam

Wiring methods and materials make up one of the heaviest content areas on the NEC Knowledge portion of the Texas Journeyman exam — roughly 15 to 20 percent of the 59 knowledge questions. Article 300 sets the universal rules for how conductors are installed and protected; Articles 342 through 362 define each raceway type and where it may and may not be used. Expect code-knowledge questions such as "Which raceway is prohibited in a Class I, Division 1 location?" and scenario questions that require you to identify the correct installation method or minimum clearance.

Article 300 — General Requirements for Wiring Methods

NEC Article 300 applies to all wiring installations unless a specific article modifies it. The most-tested subsections on the Journeyman exam are below.

300.3(A) — All Conductors of the Same Circuit in the Same Raceway

All conductors of the same circuit — including the grounded (neutral) conductor and the equipment grounding conductor (EGC) — must be run in the same raceway, trench, cable, or cord. Running the hot and neutral in separate conduits creates magnetic imbalance, inductive heating, and elevated conductor temperature. This is one of the most frequently tested rules.

Exception: Conductors for spark igniters, certain remote-control and signaling conductors under 50 V, and specific parallel conductor installations per 310.10(G) have defined allowances.

300.4 — Protection Against Physical Damage

When raceways or cables pass through structural members, the NEC requires minimum edge clearances or steel plate protection:

SituationRequirement
300.4(A) — Bored holes in wood membersAt least 1-1/4 in. from the nearest edge of the stud or joist, or protected by a 1/16 in. steel plate
300.4(B) — Notches in wood members1-1/4 in. from edge or steel plate
300.4(C) — Metal framing membersListed bushings or grommets to prevent abrasion
300.4(D) — Cables through studs1-1/4 in. edge distance or steel plate
300.4(G) — Insulated fittings at terminationsConductors #4 AWG and larger require a bushing at conduit terminations

The 1-1/4 in. rule is one of the most frequently tested single numbers on the exam — memorize it.

300.17 — Conductors of Different Insulation Ratings

When conductors with different temperature ratings are installed in the same raceway or cable, the lowest temperature rating governs the allowable ampacity of every conductor in the group. If THHN (90 °C) and THW (75 °C) are pulled together, both are limited to the 75 °C column ampacity — even the THHN.

300.22 — Wiring in Ducts, Plenums, and Other Air-Handling Spaces

Article 300.22 restricts what may be installed in spaces that carry environmental air:

  • 300.22(B) — Plenums and ducts specifically fabricated for environmental air: Only listed plenum-rated cable (CMP, CL2P, and similar) or metal raceways (RMC, IMC, EMT, FMC up to 4 ft) and mineral-insulated cable are permitted. Nonmetallic conduit is not allowed.
  • 300.22(C) — Other spaces used for environmental air (for example, the area above a suspended ceiling used as a return-air plenum): Wider allowances — MC cable, AC cable, NM cable, and most raceways are permitted when installed per their respective articles.

Exam tip: plenums under 300.22(B) are far more restrictive than other spaces used for environmental air under 300.22(C). Know the difference.

Raceway Types — Comparison

The NEC organizes each raceway in its own article (342 through 362). Every article has a "Uses Permitted" and a "Uses Not Permitted" section — these are the exact subsections the exam references.

RacewayNEC ArticleTypeKey Uses PermittedKey Prohibitions
RMC (Rigid Metal Conduit)342Rigid metalAll atmospheric conditions; hazardous locations; direct burialSubject to severe physical damage unless protected
IMC (Intermediate Metal Conduit)344Rigid metalSame as RMC; thinner wall, lighter weightSame general restrictions as RMC
EMT (Electrical Metallic Tubing)358Thin-wall metalWhere not subject to severe physical damage; concealed or exposedNot where subject to severe physical damage (358.12(B)); not in hazardous locations unless Chapter 5 permits
FMC (Flexible Metal Conduit)350Flexible metalWhere flexibility is required; motor connections; luminairesNot in hoistways; not where subject to physical damage; as EGC limited to 6 ft (350.60)
ENT (Electrical Nonmetallic Tubing)362Flexible nonmetallicConcealed in walls and floors; wet or damp where listedNot in hazardous locations; not where subject to physical damage; not above 50 °C ambient
RTRC (Reinforced Thermosetting Resin Conduit)353Rigid nonmetallicUnderground; corrosive and wet locations; exposed where listedNot in hazardous locations unless Chapter 5 permits
Rigid PVC (Schedule 40 and 80)352Rigid nonmetallicUnderground; wet and corrosive locations; Schedule 80 where subject to physical damageNot in hazardous locations (352.12); not for luminaire support; ambient temperature limits
LFNC (Liquidtight Flexible Nonmetallic Conduit)356Flexible nonmetallicWet locations; outdoors; direct burial where listed; flexibilityNot in hazardous locations unless Chapter 5 permits; length restrictions per 356.12

Trade Size vs. Metric Designator

The NEC uses trade sizes (inches) alongside metric designators. You will see both on the exam. Memorize the common pairings:

Trade SizeMetric Designator
1/2 in.16
3/4 in.21
1 in.27
1-1/4 in.35
1-1/2 in.41
2 in.53

The metric number is the nominal outside diameter in millimeters, rounded. Trade sizes smaller than 1/2 in. (metric 16) are not permitted for most raceway wiring methods — each raceway article sets a minimum trade size of 1/2 in.

Where Each Raceway Is Prohibited — Exam Favorites

  • PVC (Article 352): Not permitted in hazardous (classified) locations (352.12) except as Chapter 5 allows. Not used to support luminaires. Schedule 80 may be used where subject to physical damage; Schedule 40 may not.
  • EMT (Article 358): Not permitted where subject to severe physical damage (358.12(B)). Minimum trade size is 1/2 in.
  • FMC (Article 350): Not permitted as the sole equipment grounding conductor for runs exceeding 6 ft (350.60). Not in hoistways or where subject to physical damage.
  • ENT (Article 362): Not permitted in plenums (300.22(B)), not in hazardous locations, not where subject to physical damage, and not in ambient temperatures above 50 °C.
  • LFNC (Article 356): Total length must not exceed 6 ft in a single run unless specifically permitted; not in hazardous locations unless Chapter 5 allows.
Test Your Knowledge

Which NEC article governs Rigid Metal Conduit (RMC)?

A
B
C
D