3.2 Conductors, Resistance, and Voltage Drop
Key Takeaways
- NEC Chapter 9, Table 8 lists the DC resistance (Ω per 1,000 ft at 75 °C) for copper and aluminum conductors by AWG and kcmil size.
- Three-phase voltage drop: VD = 1.732 × I × R × L ÷ 1,000; single-phase voltage drop: VD = 2 × I × R × L ÷ 1,000 (L is one-way length, R is from Table 8).
- NEC 210.19(A) Informational Note No. 4 and 215.2(A) Informational Note No. 2 recommend a maximum 3% drop on branch circuits or feeders and 5% total combined — these are best-practice notes, not mandatory Code.
- When voltage drop governs, upsize the conductor until its Table 8 resistance brings the calculated VD under the target percentage.
- Aluminum conductors of a given size have roughly 1.6 times the resistance of same-size copper, so aluminum runs need one size larger to match copper voltage drop.
Why This Matters for the Texas Journeyman Exam
Voltage-drop calculations appear directly on the Calculations part of the TDLR/PSI exam and indirectly on the Knowledge part when questions ask about conductor upsizing, feeder sizing, and the NEC Informational Notes that recommend voltage-drop limits. A candidate who can quickly pull a resistance value from NEC Chapter 9, Table 8, plug it into the correct formula, and compare the result to 3% or 5% will pick up several points that candidates who guess on conductor size will miss.
Conductor Resistance — NEC Chapter 9, Table 8
NEC Chapter 9, Table 8 ("Conductor Properties") lists the cross-sectional area, stranding, and DC resistance at 75 °C for copper (coated and uncoated) and aluminum conductors. The resistance column is given in ohms per 1,000 feet (Ω/kft) and is the value you plug into the voltage-drop formulas.
Selected copper resistances at 75 °C (Ω per 1,000 ft):
| Size | Area (kcmil) | Cu R (Ω/kft) | Al R (Ω/kft) |
|---|---|---|---|
| 14 AWG | 4.11 | 3.07 | 5.06 |
| 12 AWG | 6.53 | 1.93 | 3.18 |
| 10 AWG | 10.38 | 1.21 | 2.00 |
| 8 AWG | 16.51 | 0.764 | 1.26 |
| 6 AWG | 26.24 | 0.491 | 0.808 |
| 4 AWG | 41.74 | 0.308 | 0.508 |
| 2 AWG | 66.36 | 0.194 | 0.320 |
| 1/0 AWG | 105.6 | 0.122 | 0.201 |
| 2/0 AWG | 133.1 | 0.0967 | 0.159 |
| 3/0 AWG | 167.8 | 0.0766 | 0.126 |
| 4/0 AWG | 211.6 | 0.0607 | 0.100 |
| 250 kcmil | 250 | 0.0515 | 0.0847 |
| 300 kcmil | 300 | 0.0429 | 0.0707 |
| 350 kcmil | 350 | 0.0367 | 0.0605 |
| 500 kcmil | 500 | 0.0258 | 0.0424 |
Two patterns to remember:
- Larger conductors have lower resistance. Resistance is inversely proportional to cross-sectional area; doubling the kcmil halves the resistance.
- Aluminum has ~1.6× the resistance of copper at the same size. To match copper voltage drop, aluminum usually needs to be one AWG size larger.
Voltage-Drop Formulas
The exam uses two formulas, depending on the phase configuration. L is the one-way length of the circuit (in feet), I is the load current (in amperes), and R is the Table 8 resistance (in Ω per 1,000 ft).
| Circuit Type | Formula |
|---|---|
| Three-phase | VD = 1.732 × I × R × L ÷ 1,000 |
| Single-phase | VD = 2 × I × R × L ÷ 1,000 |
The 1.732 factor (√3) reflects that in a balanced three-phase load, current flows through two conductors at any instant — the vector sum of the two phase currents is √3 times one phase current. The 2 in the single-phase formula is the round-trip factor: current travels out on one conductor and returns on the other, so the total conductor length is twice the one-way run.
Formula Derivation (Intuition)
Ohm's Law says the voltage dropped on one conductor is I × R_conductor. For a single-phase circuit the current uses two conductors (hot and neutral, or hot and hot), so the total loop drop is 2 × I × R. For three-phase, the vector combination of two energized conductors yields √3 ≈ 1.732 times the single-conductor drop. The ÷ 1,000 converts the per-1,000-ft Table 8 value to per-foot resistance.
NEC Voltage-Drop Limits — Informational Notes
The NEC states voltage-drop guidance in Informational Notes, which are not mandatory Code but describe best practice and are routinely tested:
- NEC 210.19(A) Informational Note No. 4 — Branch-circuit conductors should be sized so that the voltage drop does not exceed 3%, and the combined voltage drop of feeder plus branch circuit should not exceed 5%.
- NEC 215.2(A) Informational Note No. 2 — Feeder conductors should be sized so that the voltage drop does not exceed 3%, with the same 5% combined recommendation.
Reasonable design practice (and exam convention) is to treat 3% as the target for an individual feeder or branch circuit and 5% as the maximum for the total run from service to load.
Worked Example — Size Conductor for 250 A at 200 ft (Three-Phase, 480 V, Copper)
Problem: A 250 A continuous load is supplied by a 480 V three-phase feeder, 200 ft one-way, copper conductors. Size the conductor so voltage drop stays within 3%.
Step 1 — Find the maximum allowable voltage drop
Max VD = 480 V × 0.03 = 14.4 V
Step 2 — Solve for the maximum allowable resistance
Rearrange the three-phase formula:
R = VD × 1,000 ÷ (1.732 × I × L)
R = 14.4 × 1,000 ÷ (1.732 × 250 × 200)
R = 14,400 ÷ 86,600 = 0.1663 Ω/kft
Any copper conductor with Table 8 resistance ≤ 0.1663 Ω/kft satisfies the voltage-drop limit.
Step 3 — Check ampacity (NEC Table 310.16)
Before accepting a conductor based on voltage drop alone, verify it can carry the load. From NEC Table 310.16 (75 °C column, copper):
- 4/0 AWG Cu = 230 A — not enough for a 250 A load.
- 250 kcmil Cu = 255 A — meets 250 A.
Step 4 — Verify voltage drop with 250 kcmil
From Chapter 9 Table 8, 250 kcmil Cu R = 0.0515 Ω/kft.
VD = 1.732 × 250 × 0.0515 × 200 ÷ 1,000
VD = 1.732 × 250 × 0.0103 = 4.46 V
%VD = 4.46 ÷ 480 = 0.93% — well within 3%.
Step 5 — Conclusion
250 kcmil copper satisfies both the ampacity requirement (255 A ≥ 250 A) and the voltage-drop recommendation (0.93% < 3%). At 200 ft, ampacity governs; voltage drop is not the limiting factor.
What Happens at Longer Distances?
At 500 ft with 250 kcmil: VD = 1.732 × 250 × 0.0515 × 0.5 = 11.15 V → 2.32% (still under 3%).
At 700 ft with 250 kcmil: VD = 1.732 × 250 × 0.0515 × 0.7 = 15.6 V → 3.25% (exceeds 3%). Upsize to 300 kcmil (R = 0.0429): VD = 1.732 × 250 × 0.0429 × 0.7 = 13.0 V → 2.71% (within 3%).
This is the pattern the exam tests: compute the drop, compare to 3% (or 5%), and upsize if needed.
Worked Example — Single-Phase Voltage Drop
A 120 V, 15 A branch circuit runs 100 ft one-way using #12 copper (R = 1.93 Ω/kft). Find the voltage drop and percentage.
VD = 2 × 15 × 1.93 × 100 ÷ 1,000 = 5.79 V
%VD = 5.79 ÷ 120 = 4.83% — exceeds the 3% branch-circuit recommendation.
To bring it under 3% (max 3.6 V), solve for R: R = 3.6 × 1,000 ÷ (2 × 15 × 100) = 1.2 Ω/kft. #10 Cu (R = 1.21) is just over; #8 Cu (R = 0.764) gives VD = 2 × 15 × 0.764 × 0.1 = 2.29 V → 1.91%. So upsizing from #12 to #8 brings a 100 ft, 15 A circuit into compliance.
Exam Tips for Voltage-Drop Questions
- Identify the phase configuration first. Three-phase → 1.732; single-phase → 2. Mixing these up is the most common calculation error.
- Use the one-way length, not round-trip. The formula factor already accounts for return path.
- Pull R from Chapter 9 Table 8, not Table 310.16. Table 310.16 gives ampacity, not resistance.
- Check ampacity first, then voltage drop. If a conductor is too small for the load, voltage drop doesn't matter.
- Remember the limits are Informational Notes. A 3.2% drop is not a Code violation — but the exam treats 3% as the design threshold.
- Aluminum runs need ~1.6× the copper area, so go one size up to match.
A single-phase 120 V branch circuit carries 15 A for 100 ft one-way using #12 copper (R = 1.93 Ω/kft from NEC Chapter 9 Table 8). What is the voltage drop as a percentage of the supply?
Which NEC table lists the DC resistance of copper and aluminum conductors by AWG and kcmil size?
On a 480 V three-phase circuit, what is the maximum voltage drop allowed by the 3% recommendation?