13.3 Neutral Load and Service Sizing

Key Takeaways

  • NEC 120.61 defines the feeder or service neutral load as the maximum unbalanced load — the load between the neutral and one ungrounded conductor.

  • NEC 120.61(B)(1) permits a 70% demand factor on the household range and dryer portion of the neutral load; 120.61(B)(2) permits a 70% demand factor on the portion of the unbalanced load exceeding 200 A.

  • The total computed service load combines the 120.45 demand-factored lighting load, the 120.53 appliance load, the 120.54 dryer load, the 120.55 range load, and the larger of heating or cooling per 120.60.

  • Table 310.12(A) sizes service-entrance conductors for single-family dwellings at 83% of the service rating: 175 A service requires 1/0 AWG copper or 3/0 AWG aluminum.

  • The service rating is selected from the 240.6(A) standard ampere ratings at or above the computed load current — a 154.9 A computed load requires a 175 A service.

Last updated: October 2026

Why This Matters for the TX Journeyman Exam

The final step of a dwelling service calculation ties together every load category from Sections 13.1 and 13.2, adds the neutral-load rules from NEC 120.61, and lands on a service-entrance conductor size from Table 310.12(A). The exam typically asks you to carry a full calculation through to the conductor size, so every arithmetic step must be right. This section references Chapter 4 for the service-disconnect rules (230.70–230.79) and Chapter 7 for OCPD selection (240.6(A)) — it does not re-teach them.

NEC 120.61 — Feeder or Service Neutral Load

NEC 120.61 defines the neutral load as the maximum unbalanced load: the greatest load between the neutral conductor and any one ungrounded conductor. On a 120/240 V single-phase, 3-wire service, 240 V loads (line-to-line) do not contribute to the neutral; only 120 V loads (line-to-neutral) do.

120.61(B) — Permitted Neutral Demand Factors

There is no separate "Table 120.61" in the 2026 NEC — the reductions are in 120.61(B) as text:

ProvisionReduction permitted
120.61(B)(1)A 70% demand factor on the household electric range, wall oven, cooktop, and electric dryer portion of the neutral load (where calculated per Tables 120.55 and 120.54)
120.61(B)(2)A 70% demand factor on that portion of the unbalanced load exceeding 200 A, for 3-wire DC or single-phase AC, 4-wire 3-phase, 3-wire 2-phase, or 5-wire 2-phase systems

The practical result for a single-family dwelling: the first 200 A of unbalanced neutral load is taken at 100%, and the portion above 200 A is taken at 70%.

120.61(C) — Prohibited Reductions

No neutral reduction is permitted for:

  • Any portion of a 3-wire circuit consisting of 2 ungrounded conductors and the neutral of a 4-wire, 3-phase wye-connected system
  • That portion consisting of nonlinear loads on a 4-wire, wye-connected, 3-phase system (harmonic current concerns)

NEC 120.60 — Net Computed Load (Recap)

As covered in Section 13.2, where noncoincident loads (heating vs. air-conditioning) will not run simultaneously, 120.60 permits only the larger load to be included in the total. This applies to the total ungrounded-conductor load and indirectly to the neutral (since the 240 V heating or cooling load contributes little or nothing to the neutral).

Table 310.12(A) — Single-Phase Dwelling Service Conductors

Table 310.12(A) applies to service conductors supplying the entire load of a one-family dwelling on a single-phase, 120/240 V system rated 100–400 A. Conductors sized per this table must have an ampacity not less than 83% of the service or feeder rating, and the table may only be used where no adjustment or correction factors (310.15) apply.

Table 310.12(A) — Excerpt (Service-Entrance Conductors)

Service Rating (A)Copper (AWG/kcmil)Aluminum or Copper-Clad Al
1004 AWG2 AWG
1252 AWG1/0 AWG
1501 AWG2/0 AWG
1751/0 AWG3/0 AWG
2002/0 AWG4/0 AWG

Per 310.12(D), the neutral conductor may be smaller than the ungrounded conductors if the requirements of 120.61 (and 230.42(C) for services) are met.

Complete Worked Example — Single-Family Dwelling Service Load

Given: A 2000 sq ft single-family dwelling, 120/240 V single-phase service, with:

  • 2 small-appliance branch circuits, 1 laundry branch circuit
  • 10 kW electric range
  • 5500 VA electric clothes dryer
  • 4 fastened-in-place appliances with a combined nameplate of 9000 VA
  • 12 kW electric furnace (no air-conditioning)
  • No appliance neutral components or line-to-neutral distribution specified; neutral sizing is a separate exercise

Step 1 — General-Lighting Demand Load (from 13.1)

ComponentCalculationLoad
General lighting2000 ft² × 2 VA/ft²4000 VA
Small-appliance (120.52(A))2 × 1500 VA3000 VA
Laundry (120.52(B))1 × 1500 VA1500 VA
Combined subtotal8500 VA

Apply Table 120.45:

  • First 3000 VA × 100% = 3000 VA
  • Remaining 5500 VA × 35% = 1925 VA
  • General-lighting demand load = 4925 VA

Step 2 — Range Load (120.55, Table 120.55 Column C)

10 kW ≤ 12 kW → Column C direct = 8000 VA

Step 3 — Dryer Load (120.54)

max(5000 VA, 5500 VA) = 5500 VA

Step 4 — Fastened-in-Place Appliances (120.53)

4 or more qualifying appliances → 75% demand factor:

9000 VA × 0.75 = 6750 VA

Step 5 — HVAC (120.51, 120.60)

Electric furnace: 12 kW × 100% = 12000 VA (120.51) Air-conditioning: none → 0 VA Per 120.60, use the larger: 12000 VA

Step 6 — Total Computed Load (Ungrounded Conductors)

Load categoryVA
General-lighting demand4925
Range (120.55)8000
Dryer (120.54)5500
Fastened-in-place appliances (120.53)6750
Electric furnace (120.51/120.60)12000
Total computed load37175 VA

Step 7 — Service Current

Formula: I = Total VA / V

Substitution: 37175 VA / 240 V = 154.9 A

Step 8 — Select the Service Rating

The computed load is 154.9 A. The service-disconnect rating must be selected from the 240.6(A) standard ampere ratings at or above this value. Standard ratings include 150 A and 175 A — 150 A is below 154.9 A, so the minimum standard service rating is 175 A.

Step 9 — Select Service-Entrance Conductors (Table 310.12(A))

For a 175 A single-family dwelling service, Table 310.12(A) gives:

  • Copper: 1/0 AWG
  • Aluminum or copper-clad aluminum: 3/0 AWG

Step 10 — Neutral Load Requires a Separate Calculation

The total 37,175 VA includes line-to-line appliances and does not identify their neutral components or the maximum line-to-neutral loading. You cannot derive the neutral current by dividing the lighting subtotal by 240 V and ignoring every other 120 V load. Determine the maximum unbalanced load under 120.61, apply only permitted reductions, and check the service grounded-conductor minimum under 250.24(D) and Table 250.102(C)(1).

For a separate neutral-sizing exercise, suppose a completed load schedule gives 80 A of maximum unbalanced neutral load after permitted reductions. At 75°C, 4 AWG copper has an ampacity of 85 A in Table 310.16, so it meets that 80 A load before any adjustment/correction and minimum-size checks. The 100 A service allowance in Table 310.12(A) is not a general-purpose 100 A ampacity rating for 4 AWG copper.

Summary of Results

ResultValue
Total computed load37175 VA
Service current154.9 A
Minimum service rating (240.6(A))175 A
Cu service-entrance conductor1/0 AWG
Al service-entrance conductor3/0 AWG
Neutral currentRequires a line-to-neutral load schedule; not established by the total service VA

This is the natural endpoint of the load calculation. The service-disconnect rules (230.70–230.79), conductor ampacity adjustments, and OCPD selection are covered in Chapters 4 and 7.

Test Your Knowledge

Per NEC 120.61(B)(2), what demand factor may be applied to the portion of the unbalanced neutral load that exceeds 200 A on a single-family dwelling service?

A

100%

B

70%

C

35%

D

25%

Test Your Knowledge

A single-family dwelling has a total computed service load of 37175 VA on a 120/240 V single-phase system. What is the computed service current?

A

189.4 A

B

94.7 A

C

309.8 A

D

154.9 A

Test Your Knowledge

Per Table 310.12(A), what is the minimum copper service-entrance conductor size for a 175 A single-family dwelling service?

A

1/0 AWG

B

2 AWG

C

1 AWG

D

2/0 AWG