14.4 Commercial Building Load Capstone
Key Takeaways
- A commercial service calculation runs in order: general lighting, receptacles, continuous non-table loads, the larger of heating or cooling, kitchen equipment, then total and convert to amperes.
- NEC 220.14(K) makes an office building take the LARGER of the 220.14(I) receptacle load or 1 VA per square foot — a 10,000 ft² office with only 40 straps uses the 10,000 VA floor, not 7,200 VA.
- NEC 220.60 counts only the larger of two noncoincident loads, so 14,000 VA of heating displaces 11,000 VA of air conditioning entirely.
- Three-phase current is I = VA ÷ (V × √3), so 46,500 VA at 208 V is 46,500 ÷ 360.26 = 129.1 A.
- Per 110.14(C)(1)(b) equipment rated over 100 A is sized from the 75°C column, and 240.4(B) permits the next standard OCPD above a conductor ampacity that is not itself a standard rating.
Capstone Problem: 10,000 sq ft Office Building
This capstone integrates every rule from Sections 14.1 through 14.3 into a single end-to-end calculation.
Given:
- 10,000 sq ft office building
- 40 receptacle outlets (one per strap/yoke)
- Occupancy classification: office building, which triggers the 220.14(K) receptacle comparison
- Continuous display lighting: 2,000 VA (separate from Table 220.42(A) general lighting)
- Electric heating: 14,000 VA
- Air conditioning: 11,000 VA
- Commercial kitchen: range 4,000 VA + oven 3,000 VA (2 units)
- System: 208 V, three-phase
Step 1 — General Lighting (Table 220.42(A))
| Item | Calculation | Result |
|---|---|---|
| Floor area | 10,000 ft² | — |
| Unit load (office) | Table 220.42(A) | 1.3 VA/ft² |
| General lighting | 10,000 × 1.3 | 13,000 VA |
| Demand factor | Table 220.45, All Others | 100% |
| Lighting demand | 13,000 × 100% | 13,000 VA |
The 125% continuous load factor is already included in the Table 220.42(A) unit value — do not apply it again.
Step 2 — Receptacles (220.14(I), Table 220.47, and the 220.14(K) floor)
| Item | Calculation | Result |
|---|---|---|
| Receptacle load | 40 straps × 180 VA | 7,200 VA |
| Demand factor | Table 220.47 | First 10 kVA @ 100% |
| (K)(1) result | 7,200 ≤ 10,000 → 100% | 7,200 VA |
| (K)(2) floor | 10,000 ft² × 1 VA/ft² | 10,000 VA |
| Receptacle load used | Larger of (K)(1) and (K)(2) | 10,000 VA |
Two things are happening here. First, 7,200 VA is under the 10 kVA threshold, so no 50% reduction applies under Table 220.47. Second — and this is the step most candidates drop — 220.14(K) requires banks and office buildings to use the larger of the 220.14(I) result or 1 VA per square foot. At 10,000 ft² the floor is 10,000 VA, which beats the 7,200 VA strap count, so 10,000 VA is what moves forward. The two figures are never added.
Step 3 — Continuous Display Lighting (215.2(A)(1))
| Item | Calculation | Result |
|---|---|---|
| Connected load | Display lighting (not from Table 220.42(A)) | 2,000 VA |
| Continuous factor | 215.2(A)(1): 125% | × 1.25 |
| Calculated load | 2,000 × 1.25 | 2,500 VA |
This display lighting is a separate continuous load — it is not part of the Table 220.42(A) general lighting, so the 125% factor must be applied explicitly.
Step 4 — Noncoincident Loads (220.60)
| Load | VA | Included? |
|---|---|---|
| Electric heating | 14,000 | Yes (larger) |
| Air conditioning | 11,000 | No (smaller) |
Per 220.60, only the larger load is used. Per 220.51, fixed heating is calculated at 100% of connected load.
- Heating demand = 14,000 VA
Step 5 — Commercial Kitchen (Table 220.56)
| Item | Calculation | Result |
|---|---|---|
| Connected load | 4,000 + 3,000 | 7,000 VA |
| Number of units | 2 | — |
| Demand factor | Table 220.56, 2 units | 100% |
| Kitchen demand | 7,000 × 100% | 7,000 VA |
| Floor check | 4,000 + 3,000 = 7,000 | 7,000 ≤ 7,000 ✓ |
Step 6 — Total Computed Load
| Component | VA |
|---|---|
| General lighting (Step 1) | 13,000 |
| Receptacles (Step 2, per 220.14(K)) | 10,000 |
| Continuous display lighting (Step 3) | 2,500 |
| Electric heating (Step 4) | 14,000 |
| Kitchen (Step 5) | 7,000 |
| Total | 46,500 VA |
Step 7 — Service Current (208 V Three-Phase)
Three-phase current formula:
I = VA ÷ (V × √3)
Substitution:
- I = 46,500 ÷ (208 × 1.732)
- I = 46,500 ÷ 360.26
- I = 129.1 A
Step 8 — Service Conductor Selection
Per 110.14(C)(1)(b), equipment rated over 100 A uses the 75°C column of Table 310.16.
| Conductor (Cu) | 75°C Ampacity | Adequate? |
|---|---|---|
| #2 AWG | 115 A | No — 115 < 129.1 |
| #1 AWG | 130 A | Yes — 130 ≥ 129.1 |
Select: 1 AWG Cu THWN-2 (130 A at 75°C)
Step 9 — OCPD Selection (240.6(A) and 240.4(B))
- Load current = 129.1 A
- 130 A is not a standard rating, so the next standard rating from 240.6(A) at or above the load is 150 A
- 240.4(B) permits the next higher standard rating above the conductor ampacity where the ampacity does not correspond to a standard rating, the conductors do not supply cord-and-plug-connected portable loads on a multioutlet branch circuit, and the rating is 800 A or less. 230.90(A), Exception No. 2 carries that allowance to service conductors.
- Verify: load 129.1 A ≤ conductor 130 A ✓, and 150 A is the next standard rating above 130 A ✓
Select: 150 A device on 1 AWG Cu. Upsizing to 1/0 Cu (150 A at 75°C) is the conservative alternative and removes the need to invoke 240.4(B) at all.
Verification Summary
| Check | Result |
|---|---|
| Receptacle load compared per 220.14(K)? | 10,000 VA floor > 7,200 VA strap count ✓ |
| Conductor ampacity ≥ load? | 130 A ≥ 129.1 A ✓ |
| OCPD ≥ load? | 150 A ≥ 129.1 A ✓ |
| OCPD permitted on this conductor? | 150 A is the next standard rating above 130 A, per 240.4(B) ✓ |
| OCPD is standard per 240.6(A)? | 150 A is listed ✓ |
| Termination temp per 110.14(C)? | 75°C column (equipment > 100 A) ✓ |
Cross-Reference
Chapter 4 covers the service-disconnect requirements (230.70–230.79) and service-entrance conductor rules (230.42) that complete the service design. Chapter 5 covers multi-family demand calculations (Table 220.84) and separately derived systems, which are distinct from this single-tenant commercial building calculation.
What Could Change the Answer?
- If the building were 240 V single-phase instead of 208 V three-phase: I = 46,500 ÷ 240 = 193.8 A. In the 75°C column, 2/0 Cu is only 175 A, so the conductor moves to 3/0 Cu at 200 A, protected by a 200 A device — 240.4(B) is not needed here because 200 A is both a standard rating and the exact conductor ampacity.
- If the building included a hospital wing: the lighting demand factor from Table 220.45 would change from 100% (All Others) to 40%/20% (hospitals), potentially reducing the total load.
- If a voltage-drop check were required for a long service run: the conductor might need to be upsized beyond the ampacity-based selection, as demonstrated in Section 14.3.
In a three-phase system, what is the formula for line current when the total load is 46,500 VA at 208 V?
Per 110.14(C), equipment rated over 100 A must use which column of Table 310.16 for conductor sizing?
Which of the following is a standard ampere rating per NEC 240.6(A)?
A 10,000 sq ft office building has 40 receptacle outlets, each on its own strap. What receptacle load is carried into the service calculation?