14.4 Commercial Building Load Capstone

Key Takeaways

  • A commercial service calculation runs in order: general lighting, receptacles, continuous non-table loads, the larger of heating or cooling, kitchen equipment, then total and convert to amperes.
  • NEC 220.14(K) makes an office building take the LARGER of the 220.14(I) receptacle load or 1 VA per square foot — a 10,000 ft² office with only 40 straps uses the 10,000 VA floor, not 7,200 VA.
  • NEC 220.60 counts only the larger of two noncoincident loads, so 14,000 VA of heating displaces 11,000 VA of air conditioning entirely.
  • Three-phase current is I = VA ÷ (V × √3), so 46,500 VA at 208 V is 46,500 ÷ 360.26 = 129.1 A.
  • Per 110.14(C)(1)(b) equipment rated over 100 A is sized from the 75°C column, and 240.4(B) permits the next standard OCPD above a conductor ampacity that is not itself a standard rating.
Last updated: August 2026

Capstone Problem: 10,000 sq ft Office Building

This capstone integrates every rule from Sections 14.1 through 14.3 into a single end-to-end calculation.

Given:

  • 10,000 sq ft office building
  • 40 receptacle outlets (one per strap/yoke)
  • Occupancy classification: office building, which triggers the 220.14(K) receptacle comparison
  • Continuous display lighting: 2,000 VA (separate from Table 220.42(A) general lighting)
  • Electric heating: 14,000 VA
  • Air conditioning: 11,000 VA
  • Commercial kitchen: range 4,000 VA + oven 3,000 VA (2 units)
  • System: 208 V, three-phase

Step 1 — General Lighting (Table 220.42(A))

ItemCalculationResult
Floor area10,000 ft²
Unit load (office)Table 220.42(A)1.3 VA/ft²
General lighting10,000 × 1.313,000 VA
Demand factorTable 220.45, All Others100%
Lighting demand13,000 × 100%13,000 VA

The 125% continuous load factor is already included in the Table 220.42(A) unit value — do not apply it again.

Step 2 — Receptacles (220.14(I), Table 220.47, and the 220.14(K) floor)

ItemCalculationResult
Receptacle load40 straps × 180 VA7,200 VA
Demand factorTable 220.47First 10 kVA @ 100%
(K)(1) result7,200 ≤ 10,000 → 100%7,200 VA
(K)(2) floor10,000 ft² × 1 VA/ft²10,000 VA
Receptacle load usedLarger of (K)(1) and (K)(2)10,000 VA

Two things are happening here. First, 7,200 VA is under the 10 kVA threshold, so no 50% reduction applies under Table 220.47. Second — and this is the step most candidates drop — 220.14(K) requires banks and office buildings to use the larger of the 220.14(I) result or 1 VA per square foot. At 10,000 ft² the floor is 10,000 VA, which beats the 7,200 VA strap count, so 10,000 VA is what moves forward. The two figures are never added.

Step 3 — Continuous Display Lighting (215.2(A)(1))

ItemCalculationResult
Connected loadDisplay lighting (not from Table 220.42(A))2,000 VA
Continuous factor215.2(A)(1): 125%× 1.25
Calculated load2,000 × 1.252,500 VA

This display lighting is a separate continuous load — it is not part of the Table 220.42(A) general lighting, so the 125% factor must be applied explicitly.

Step 4 — Noncoincident Loads (220.60)

LoadVAIncluded?
Electric heating14,000Yes (larger)
Air conditioning11,000No (smaller)

Per 220.60, only the larger load is used. Per 220.51, fixed heating is calculated at 100% of connected load.

  • Heating demand = 14,000 VA

Step 5 — Commercial Kitchen (Table 220.56)

ItemCalculationResult
Connected load4,000 + 3,0007,000 VA
Number of units2
Demand factorTable 220.56, 2 units100%
Kitchen demand7,000 × 100%7,000 VA
Floor check4,000 + 3,000 = 7,0007,000 ≤ 7,000 ✓

Step 6 — Total Computed Load

ComponentVA
General lighting (Step 1)13,000
Receptacles (Step 2, per 220.14(K))10,000
Continuous display lighting (Step 3)2,500
Electric heating (Step 4)14,000
Kitchen (Step 5)7,000
Total46,500 VA

Step 7 — Service Current (208 V Three-Phase)

Three-phase current formula:

I = VA ÷ (V × √3)

Substitution:

  • I = 46,500 ÷ (208 × 1.732)
  • I = 46,500 ÷ 360.26
  • I = 129.1 A

Step 8 — Service Conductor Selection

Per 110.14(C)(1)(b), equipment rated over 100 A uses the 75°C column of Table 310.16.

Conductor (Cu)75°C AmpacityAdequate?
#2 AWG115 ANo — 115 < 129.1
#1 AWG130 AYes — 130 ≥ 129.1

Select: 1 AWG Cu THWN-2 (130 A at 75°C)

Step 9 — OCPD Selection (240.6(A) and 240.4(B))

  • Load current = 129.1 A
  • 130 A is not a standard rating, so the next standard rating from 240.6(A) at or above the load is 150 A
  • 240.4(B) permits the next higher standard rating above the conductor ampacity where the ampacity does not correspond to a standard rating, the conductors do not supply cord-and-plug-connected portable loads on a multioutlet branch circuit, and the rating is 800 A or less. 230.90(A), Exception No. 2 carries that allowance to service conductors.
  • Verify: load 129.1 A ≤ conductor 130 A ✓, and 150 A is the next standard rating above 130 A ✓

Select: 150 A device on 1 AWG Cu. Upsizing to 1/0 Cu (150 A at 75°C) is the conservative alternative and removes the need to invoke 240.4(B) at all.

Verification Summary

CheckResult
Receptacle load compared per 220.14(K)?10,000 VA floor > 7,200 VA strap count ✓
Conductor ampacity ≥ load?130 A ≥ 129.1 A ✓
OCPD ≥ load?150 A ≥ 129.1 A ✓
OCPD permitted on this conductor?150 A is the next standard rating above 130 A, per 240.4(B) ✓
OCPD is standard per 240.6(A)?150 A is listed ✓
Termination temp per 110.14(C)?75°C column (equipment > 100 A) ✓

Cross-Reference

Chapter 4 covers the service-disconnect requirements (230.70–230.79) and service-entrance conductor rules (230.42) that complete the service design. Chapter 5 covers multi-family demand calculations (Table 220.84) and separately derived systems, which are distinct from this single-tenant commercial building calculation.

What Could Change the Answer?

  • If the building were 240 V single-phase instead of 208 V three-phase: I = 46,500 ÷ 240 = 193.8 A. In the 75°C column, 2/0 Cu is only 175 A, so the conductor moves to 3/0 Cu at 200 A, protected by a 200 A device — 240.4(B) is not needed here because 200 A is both a standard rating and the exact conductor ampacity.
  • If the building included a hospital wing: the lighting demand factor from Table 220.45 would change from 100% (All Others) to 40%/20% (hospitals), potentially reducing the total load.
  • If a voltage-drop check were required for a long service run: the conductor might need to be upsized beyond the ampacity-based selection, as demonstrated in Section 14.3.
Test Your Knowledge

In a three-phase system, what is the formula for line current when the total load is 46,500 VA at 208 V?

A
B
C
D
Test Your Knowledge

Per 110.14(C), equipment rated over 100 A must use which column of Table 310.16 for conductor sizing?

A
B
C
D
Test Your Knowledge

Which of the following is a standard ampere rating per NEC 240.6(A)?

A
B
C
D
Test Your Knowledge

A 10,000 sq ft office building has 40 receptacle outlets, each on its own strap. What receptacle load is carried into the service calculation?

A
B
C
D