14.2 Protective Relaying Schemes (Differential 87, Distance 21, Undervoltage 27)
Key Takeaways
- Differential protection (ANSI 87) enforces Kirchhoff's Current Law across a strictly bounded zone: operating current $I_{diff} = |\mathbf{I}_1 - \mathbf{I}_2'|$ trips when exceeding the dual-slope restraint characteristic $I_{diff} > \text{Slope} \times I_{rest} + I_{pickup}$, providing high-speed unit protection without coordination delays.
- Transformer differential relays (87T) must compensate for CT ratio mismatch, $30^\circ$ Wye-Delta phase shifts, zero-sequence ground fault trapping, magnetizing inrush (using 2nd harmonic restraint where $I_{2f}/I_{fund} > 15\%$), and overexcitation (using 5th harmonic restraint where $I_{5f}/I_{fund} > 30\%$).
- Distance relays (ANSI 21) compute apparent impedance $\mathbf{Z}_{app} = \mathbf{V}/\mathbf{I}$ on the $R-X$ plane across stepped reach zones: Zone 1 (80-85% instantaneous), Zone 2 (120-150% with 0.3-0.4 s delay), and Zone 3 (remote backup with 0.6-1.0 s delay).
- Pilot communication schemes (POTT, PUTT, DCB, and Line Differential 87L) overcome Zone 1 underreach by exchanging permissive or blocking signals across high-speed teleprotection channels for 100% line coverage at high speed.
- System stability relays safeguard critical infrastructure: ANSI 27 (undervoltage) prevents motor stalling and drives UVLS, while ANSI 81U (under-frequency) coordinates NERC-mandated Under-Frequency Load Shedding (UFLS) stages.
14.2 Protective Relaying Schemes (Differential 87, Distance 21, Undervoltage 27)
Executive Overview: Modern power systems rely on specialized relaying schemes to protect apparatus and maintain grid stability. While simple overcurrent relays provide non-unit backup, critical infrastructure—transformers, generators, transmission lines, and major switchgear buses—demands unit protection (ANSI 87 Differential), impedance-based protection (ANSI 21 Distance), and voltage/frequency health monitoring (ANSI 27/59, ANSI 81). On the PE Power examination, candidates must understand ANSI device numbering, dual-slope percentage differential calculations, harmonic restraint for inrush, stepped distance zone parameterization, and teleprotection pilot schemes.
1. ANSI Standard Device Numbers & Function Taxonomy
The standard IEEE/ANSI C37.2 device numbers categorize protective relay functions across electrical substations:
| ANSI Code | Standard Device Function | Operating Philosophy & Application |
|---|---|---|
| 21 | Distance / Impedance Relay | Measures apparent impedance $\mathbf{Z} = \mathbf{V}/\mathbf{I}$; protects transmission and subtransmission lines |
| 25 | Synchronism-Check Relay | Verifies $\Delta V, \Delta \theta, \Delta f$ across an open breaker prior to interconnection closure |
| 27 | Undervoltage Relay | Senses voltage collapse ($V < V_{set}$); drives motor drop-out, bus transfer, and UVLS load shedding |
| 46 | Reverse-Phase / Negative-Sequence | Protects generators and motors against unbalance rotor overheating ($I_2^2 t = K$) |
| 49 | Thermal Overload Relay | Protects transformer and machine windings based on RTD or thermal replica models |
| 50 / 51 | Instantaneous / Time-Overcurrent | Senses phase overcurrents with zero delay (50) or inverse time curves (51) |
| 50N / 51N | Residual Ground Overcurrent | Calculated neutral/ground current ($3\mathbf{I}_0 = \mathbf{I}_a + \mathbf{I}_b + \mathbf{I}_c$) from 3-phase CT secondary residual |
| 50G / 51G | Direct Ground Overcurrent | Senses ground return current directly via a dedicated window / zero-sequence CT |
| 59 | Overvoltage Relay | Senses excessive system voltage ($V > V_{set}$); protects against insulation stress and Ferranti rise |
| 67 / 67N | Directional Overcurrent Relay | Evaluates current relative to polarizing voltage/current; used in loop or multi-source lines |
| 81U / 81O | Under- / Over-Frequency Relay | Detects active power imbalance ($P_{gen} \ne P_{load}$); drives NERC UFLS stages |
| 86 | Master Lockout Relay | High-speed electromechanical latching auxiliary relay; trips all sources and blocks reclosing |
| 87 | Differential Protective Relay | Compares current entering and leaving bounded zone; instantaneous unit protection |
| 87T / 87G / 87L | Transformer / Generator / Line Diff | Specialized differential relays with harmonic restraint (87T) or teleprotection (87L) |
2. Differential Protection (ANSI 87)
Differential protection is based on Kirchhoff's Current Law: under normal or external through-fault conditions, the sum of currents entering a bounded zone equals the sum of currents leaving the zone. If a fault occurs inside the zone, current flows into the fault from one or both ends, creating an imbalance.
Percentage Differential Relay Schematic (External Through-Fault vs. Internal Fault):
External Through-Fault (NO TRIP):
Zone In -------------------[ Protected Equipment ]-------------------> Zone Out
I_1 = 1000 A ---> I_2 = 1000 A --->
(CT 1) 1000:5 (CT 2) 1000:5
| |
i_1 = 5 A i_2 = 5 A
+-----[ Restraint 1 ]----o----[ Restraint 2 ]-------+
|
i_op = i_1 - i_2 = 0 A
[ Operating Coil ]
|
(No Trip: i_op = 0)
Internal Fault (TRIP):
Zone In -------------------[ Fault: 2000 A ]<------------------------- Zone Out
I_1 = 1000 A ---> | I_2 = 1000 A <---
(CT 1) 1000:5 v (CT 2) 1000:5
| |
i_1 = 5 A i_2 = -5 A
+-----[ Restraint 1 ]----o----[ Restraint 2 ]-------+
|
i_op = i_1 - (-i_2) = 10 A
[ Operating Coil ]
|
(TRIP: i_op > Pickup)
Dual-Slope Percentage Differential Characteristic
CT errors, CT saturation during asymmetric through-faults, and transformer LTC tap changes create fictitious differential currents during external faults. To prevent misoperation, differential relays utilize a restraint current ($I_{rest}$) and a dual-slope operating curve:
Dual-Slope Operating Characteristic:
I_diff (Operating Current) ^
| / Slope 2 (50% - 80%)
| / (Severe CT Saturation Region)
| /
| Slope 1 /
| (20% - 40%) /
I_pickup ---- |----.--------o (Break Point I_BP)
| / |
| / TRIP | BLOCK (Restraint Region)
| / |
+-------------+---------------------> I_rest (Restraint)
I_BP
- Slope 1 Region ($I_{rest} < I_{BP}$): Set low ($20% - 35%$) to provide high sensitivity for high-impedance internal faults while accommodating minor CT ratio mismatch and transformer LTC tap excursions (typically $\pm 10%$).
- Slope 2 Region ($I_{rest} \ge I_{BP}$): Set steep ($50% - 80%$) to prevent false tripping during heavy through-faults where severe DC offset causes CT core saturation and large false differential currents.
Transformer Differential Protection (87T) Challenges
Transformer differential protection requires four critical compensations:
- Voltage & Current Ratio Matching: CT ratios must be balanced so that secondary currents equal each other at rated MVA: $I_{sec1} \approx I_{sec2}$.
- Phase Angle Displacement: A Delta-Wye transformer introduces a $30^\circ$ phase shift (${DAB, Y} = 30^\circ$ lag). Legacy electromechanical relays used Delta-connected CTs on the Wye winding and Wye-connected CTs on the Delta winding to cancel the shift. Modern microprocessor relays use Wye-Wye CTs everywhere and execute numerical matrix phase-angle compensation internally.
- Zero-Sequence Filtering: External ground faults on the Wye-grounded side create zero-sequence current $I_0$ that does not pass through the Delta winding, producing a false differential current. Numerical algorithms filter out zero-sequence currents ($I_{a}' = I_a - I_0$).
- Magnetizing Inrush & Overexcitation Restraint:
- Magnetizing Inrush (2nd Harmonic): Energizing a transformer creates high, unipolar inrush currents ($8-12 \times FLA$) rich in second harmonic content. Relays block tripping if $\frac{I_{2nd}}{I_{fundamental}} \ge 15%$.
- Overexcitation (5th Harmonic): System overvoltage or low frequency ($V/Hz$) drives core saturation, generating fifth harmonic currents. Relays block or alarm if $\frac{I_{5th}}{I_{fundamental}} \ge 30%$.
3. Distance Protection (ANSI 21)
Distance relays measure the ratio of local voltage to local current to calculate the apparent positive-sequence impedance from the relay terminal to the fault point:
Since transmission line impedance is strictly proportional to physical length ($z_{line} = r + jx ; \Omega/\text{mile}$), the apparent impedance directly indicates the distance to the fault.
Complex R-X Impedance Plane and Mho Operating Characteristic:
+jX (Reactance) ^
| Zone 3 Reach (100% Line 1 + 120% Line 2, t3 = 0.8s)
| .-----------------------------.
| / Zone 2 Reach (120% Line 1, t2 = 0.35s)
| / .---------------------.
| / / Zone 1 Reach \
| / / (80-85% Line 1, t1=0) \
| | | .-------------.
Line Angle Theta ->| | | / \
. - - - - -|-+--|--o-----------------o
/ | | | \ /
/ | | | `-------------'
/ | \ \
/ | \ `---------------------'
/ | \ /
-------o----------------+------------------------------------> +R (Resistance)
Relay Location (0,0) | `-----------------------------'
|
Stepped Distance Zones of Protection
| Zone | Reach Coverage | Operating Time | Purpose & Design Rationale |
|---|---|---|---|
| Zone 1 | $80% - 85%$ of protected line ($Z_L$) | Instantaneous ($t_1 = 0\text{ s}$, $<30\text{ ms}$) | High-speed primary protection for the line interior. Never set to $100%$ to prevent overreaching past the remote bus due to CT/PT transient errors, line parameter errors, and DC offset. |
| Zone 2 | $120% - 150%$ of protected line ($Z_L$) | Time-Delayed ($t_2 = 0.30 - 0.40\text{ s}$) | Covers the remaining $15-20%$ of the line and provides backup for the remote substation bus. Time delay coordinates with adjacent line Zone 1 clearing. |
| Zone 3 | $100% Z_L + 120% - 150%$ of longest adjacent line | Time-Delayed ($t_3 = 0.60 - 1.00\text{ s}$) | Full remote backup protection for the entire adjacent transmission line and substation. |
Pilot Teleprotection Communication Schemes
To achieve $100%$ instantaneous clearing across the entire line length without waiting for Zone 2 time delays, relays at both line terminals exchange logic signals over fiber optic, power line carrier (PLC), or microwave channels:
- Permissive Overreaching Transfer Trip (POTT): Both ends set Zone 2 (overreaching, $>100%$). If terminal A sees an in-zone fault, it sends a permissive key to terminal B. Terminal B trips instantaneously only if it simultaneously senses a forward Zone 2 fault and receives the permission signal.
- Directional Comparison Blocking (DCB): Relays look reverse into their own system. If terminal B sees a reverse external fault, it immediately transmits a high-speed BLOCK signal to terminal A to prevent terminal A's overreaching Zone 2 element from tripping.
- Line Current Differential (87L): Direct digital exchange of synchronized current phasors via fiber-optic communication. Enforces strict unit differential protection without impedance reach limitations.
4. Voltage, Frequency & Auxiliary Relaying
Undervoltage Protection (ANSI 27)
- Motor Stall Protection: Severe voltage depressions ($V < 70-80%$) cause induction motors to decelerate toward high-current stall conditions. ANSI 27 trips feeder breakers or unlatches contactors.
- Under-Voltage Load Shedding (UVLS): Deployed across transmission load pockets experiencing reactive power deficits to prevent catastrophic system voltage collapse.
Frequency Protection (ANSI 81U / 81O)
- Operating Dynamic: System frequency reflects active power balance: $\frac{df}{dt} = \frac{f_0}{2H} (P_{gen} - P_{load})$. Sudden loss of generation causes system frequency to plunge.
- NERC Under-Frequency Load Shedding (UFLS): Regional entities mandate stepped automatic customer load shedding to arrest frequency decline:
- Stage 1: $59.5\text{ Hz}$, drop $10%$ total system load.
- Stage 2: $59.1\text{ Hz}$, drop additional $10%$ load.
- Stage 3: $58.7\text{ Hz}$, drop additional $10%$ load.
5. Comprehensive Worked Calculations
Part A: Dual-Slope Transformer Differential (87T) Evaluation
A $30\text{ MVA}$, $115\text{ kV} / 13.8\text{ kV}$ Delta-Wye transformer has:
- High-Voltage CT Ratio: $200:5\text{ A}$ ($CTR_1 = 40$)
- Low-Voltage CT Ratio: $1,500:5\text{ A}$ ($CTR_2 = 300$)
- Differential Relay Settings: $I_{pickup} = 0.30\text{ A sec}$, $\text{Slope 1} = 30%$, $I_{BP} = 2.0\text{ A sec}$, $\text{Slope 2} = 60%$.
- Restraint current formulation: $I_{rest} = \frac{|I_{1,sec}| + |I_{2,sec}|}{2}$.
Calculate:
- Full-load primary and secondary currents on HV and LV sides.
- Relay tap compensation multipliers ($CTC$) required to balance secondary currents.
- Differential current $I_{diff}$ and restraint current $I_{rest}$ during an external through-fault producing $I_{HV,pri} = 1,800\text{ A}$ and a $10%$ CT saturation error on the LV side ($I_{LV,sec} = 0.90 \times I_{balanced}$). Determine if the relay restrains properly.
============================== STEP-BY-STEP SOLUTION ==============================
Step 1: Compute Rated Full-Load Currents
HV Full-Load Primary Current:
I_FLA,HV = S / (sqrt(3) * V_HV) = 30,000,000 / (sqrt(3) * 115,000) = 150.61 A pri
LV Full-Load Primary Current:
I_FLA,LV = S / (sqrt(3) * V_LV) = 30,000,000 / (sqrt(3) * 13,800) = 1,255.1 A pri
Secondary Currents at Rated Load:
I_sec,HV = 150.61 A / (200 / 5) = 150.61 / 40 = 3.765 A sec
I_sec,LV = 1,255.1 A / (1500 / 5) = 1,255.1 / 300 = 4.184 A sec
Step 2: Establish Digital Relay Tap Balancing (CTC Factors)
To equalize secondary currents, define matching factors:
Tap_HV = 3.765 A, Tap_LV = 4.184 A
Normalized per-unit secondary current = 1.0 pu at rated load for both sides.
Step 3: Evaluate External Through-Fault with 10% CT Saturation Error
HV Through-Fault Current: I_fault,HV = 1,800 A pri (11.95x rated FLA)
Ideal LV Through-Fault Current: I_fault,LV = 1,800 * (115 / 13.8) = 15,000 A pri
Secondary Currents entering relay:
I_1 = 1,800 A / 40 = 45.0 A sec
Normalized I_1,pu = 45.0 / 3.765 = 11.952 pu
With 10% saturation error on LV side:
Normalized I_2,pu = 0.90 * 11.952 pu = 10.757 pu
Compute Differential and Restraint Currents in per-unit:
I_diff = |I_1,pu - I_2,pu| = |11.952 - 10.757| = 1.195 pu
I_rest = (I_1,pu + I_2,pu) / 2 = (11.952 + 10.757) / 2 = 11.355 pu
Step 4: Verify Relay Restraint Threshold
Since I_rest = 11.355 pu > I_BP (where I_BP = 2.0 / 3.765 = 0.531 pu):
Operating Threshold I_diff,trip = I_pickup + Slope 1 * I_BP + Slope 2 * (I_rest - I_BP)
Let base threshold = Slope 2 * I_rest = 0.60 * 11.355 = 6.813 pu
Compare Operating vs Trip Threshold:
Actual I_diff = 1.195 pu
Required Trip I_diff = 6.813 pu
Since 1.195 pu << 6.813 pu, the relay RESTRAINS (Does NOT false trip!).
===================================================================================
Part B: Transmission Line Distance (ANSI 21) Mho Reach Sizing
A $230\text{ kV}$, $60\text{ Hz}$, $40\text{ mile}$ overhead transmission line connects Substation A to Substation B. An adjacent line of $30\text{ miles}$ extends from Substation B to Substation C.
- Line positive-sequence impedance: $\mathbf{z}_1 = 0.12 + j0.68; \Omega/\text{mile}$
- $CTR = 1200:5 = 240$, $PTR = 230,000:115 = 2000$
Calculate:
- Total primary impedance $\mathbf{Z}_{AB,pri}$.
- Secondary impedance scale factor $k_Z = \frac{CTR}{PTR}$.
- Zone 1 reach in primary and secondary ohms ($85%$ reach).
- Zone 2 reach in primary and secondary ohms ($125%$ reach).
============================== STEP-BY-STEP SOLUTION ==============================
Step 1: Compute Total Primary Line Impedance (Z_AB)
Length l_AB = 40 miles
Z_AB,pri = (0.12 + j0.68) * 40 = 4.80 + j27.20 ohms = 27.620 /_ 79.99 deg ohms pri
Step 2: Determine Impedance Conversion Factor (k_Z)
k_Z = Z_sec / Z_pri = CTR / PTR = 240 / 2,000 = 0.120
Z_AB,sec = Z_AB,pri * 0.120 = (4.80 + j27.20) * 0.120
= 0.576 + j3.264 ohms = 3.314 /_ 79.99 deg ohms sec
Step 3: Calculate Zone 1 Mho Reach Setting (85% Reach, t1 = 0 s)
Primary Reach:
Z_Z1,pri = 0.85 * Z_AB,pri = 0.85 * 27.620 ohms = 23.477 ohms pri
Secondary Reach Setting:
Z_Z1,sec = 0.85 * Z_AB,sec = 0.85 * 3.314 ohms = 2.817 ohms sec
Step 4: Calculate Zone 2 Mho Reach Setting (125% Reach, t2 = 0.35 s)
Primary Reach:
Z_Z2,pri = 1.25 * Z_AB,pri = 1.25 * 27.620 ohms = 34.525 ohms pri
Secondary Reach Setting:
Z_Z2,sec = 1.25 * Z_AB,sec = 1.25 * 3.314 ohms = 4.143 ohms sec
===================================================================================
6. Common Exam Traps & Strategic Pitfalls
- Setting Distance Zone 1 to 100%: Attempting to protect $100%$ of the transmission line with Zone 1 instantaneous tripping. Transient overreach caused by DC offset, CVT transient response, and line data errors will cause the relay to trip instantaneously on out-of-zone faults past the remote bus.
- Overlooking Phase Angle Compensation in Delta-Wye 87T Relays: Failing to recognize that a Delta-Wye transformer shifts currents by $30^\circ$. If not compensated numerically or via CT connections, full load current creates a $52%$ false differential current ($|1 - 1\angle 30^\circ| = 0.518$), causing instant trip upon energization.
- Inverting the Impedance Ratio ($k_Z$): Multiplying primary ohms by $PTR/CTR$ instead of $CTR/PTR$. Because secondary voltage is small ($1/2000$) and secondary current is moderate ($1/240$), secondary impedance is always much smaller than primary impedance: $Z_{sec} = Z_{pri} \times (CTR/PTR)$.
- Confusing 2nd Harmonic Inrush with 5th Harmonic Overexcitation: 2nd harmonic ($120\text{ Hz}$) indicates magnetizing inrush during transformer energization; 5th harmonic ($300\text{ Hz}$) indicates severe core overfluxing ($V/Hz$) from overvoltage.
A 115 kV transmission line has a positive-sequence impedance of Z_1 = 4.0 + j20.0 ohms. The line is equipped with CTs of ratio 600:5 and PTs of ratio 115,000:115. What is the Zone 1 secondary reach setting in ohms if Zone 1 is calibrated for 80% line reach?
During the energization of a large power transformer, a microprocessor differential relay (87T) avoids false tripping on magnetizing inrush by employing which restraint technique?
Which of the following describes the standard reach and timing configuration for Zone 2 distance protection on an overhead transmission line?