8.1 Per-Unit System Fundamentals & Base Conversion Formulas

Key Takeaways

  • The per-unit (pu) normalization simplifies multi-voltage power system analysis by eliminating ideal transformer turns ratios and standardizing electrical parameters across diverse equipment ratings.

  • In balanced three-phase systems, selecting system base three-phase apparent power (Sbase,3ϕS_{base,3\phi}) and line-to-line voltage (Vbase,LLV_{base,LL}) establishes base impedance Zbase=(Vbase,LL)2/Sbase,3ϕ=(kVbase,LL)2/MVAbase,3ϕZ_{base} = (V_{base,LL})^2 / S_{base,3\phi} = (kV_{base,LL})^2 / MVA_{base,3\phi} and base current Ibase=Sbase,3ϕ/(3Vbase,LL)I_{base} = S_{base,3\phi} / (\sqrt{3} V_{base,LL}).

  • Equipment nameplate impedance must be converted to system base values using Zpu,new=Zpu,old×(Vbase,old/Vbase,new)2×(Sbase,new/Sbase,old)Z_{pu,new} = Z_{pu,old} \times (V_{base,old} / V_{base,new})^2 \times (S_{base,new} / S_{base,old}).

  • Per-unit impedance is identical whether viewed from the primary or secondary winding of an ideal transformer when base voltages match the transformer rated turns ratio.

Last updated: August 2026

8.1 Per-Unit System Fundamentals & Base Conversion Formulas

Key Exam Takeaway: In balanced three-phase power system calculations, base impedance is derived exclusively from the three-phase power base and the line-to-line voltage base: Zbase=(kVbase,LL)2MVAbase,3ϕZ_{base} = \frac{(kV_{base,LL})^2}{MVA_{base,3\phi}}. When converting equipment impedance to a new system base, always apply the ratio of voltages squared and the inverse ratio of power ratings: Zpu,new=Zpu,old(Vbase,oldVbase,new)2(Sbase,newSbase,old)Z_{pu,new} = Z_{pu,old} \left(\frac{V_{base,old}}{V_{base,new}}\right)^2 \left(\frac{S_{base,new}}{S_{base,old}}\right).


1. Rationale of the Per-Unit System

Modern electrical power networks span multiple voltage levels—ranging from generation (13.8 kV13.8\text{ kV} to 24 kV24\text{ kV}), extra-high-voltage transmission (138 kV138\text{ kV}, 230 kV230\text{ kV}, 500 kV500\text{ kV}), sub-transmission (69 kV69\text{ kV}, 34.5 kV34.5\text{ kV}), distribution (12.47 kV12.47\text{ kV}, 4.16 kV4.16\text{ kV}), down to utilization (480 V480\text{ V}, 208 V208\text{ V}, 120 V120\text{ V}). Analyzing these networks using actual physical quantities (Ohms, Volts, Amperes) requires reflecting impedances across transformer boundaries using the square of the turns ratio (a2=(N1/N2)2a^2 = (N_1/N_2)^2). In multi-bus interconnected networks with tens or hundreds of transformers, manual impedance reflection becomes intensely error-prone.

The per-unit (pu) system normalizes electrical quantities by expressing them as dimensionless decimal fractions or ratios of carefully defined base reference parameters:

Per-Unit Value=Actual Quantity (in Physical Units)Base Value (in Same Physical Units)\text{Per-Unit Value} = \frac{\text{Actual Quantity (in Physical Units)}}{\text{Base Value (in Same Physical Units)}}

Primary Advantages in Power Engineering

  1. Elimination of Transformer Turns Ratios: When base voltages in adjacent zones are selected in proportion to transformer turns ratios, the per-unit equivalent impedance of a transformer is identical whether calculated from the high-voltage or low-voltage winding.
  2. Parameter Standardization: Apparatus of similar design and construction exhibit per-unit impedances within narrow, predictable bands regardless of physical size or MVA rating. For example, large two-pole synchronous generator subtransient reactances consistently fall between 0.12 pu0.12\text{ pu} and 0.25 pu0.25\text{ pu}, and two-winding substation transformers typically have leakage reactances between 0.06 pu0.06\text{ pu} and 0.10 pu0.10\text{ pu}.
  3. Simplification of 3-Phase Formulations: Factors of 3\sqrt{3} and 33 vanish from balanced three-phase voltage, current, and complex power equations when standard three-phase base conventions are applied.
  4. Immediate Insight into Operating Limits: Operating at V=0.94 puV = 0.94\text{ pu} instantly conveys a 6%6\% undervoltage condition without needing to recall whether the nominal bus voltage is 13.8 kV13.8\text{ kV} or 115 kV115\text{ kV}.

2. Fundamental Base Relationships in Three-Phase Networks

To establish a per-unit system for a three-phase network, two independent base quantities must be selected. By universal utility and NCEES convention, these two quantities are:

  1. System Three-Phase Apparent Power Base (Sbase,3ϕS_{base,3\phi} or MVAbase,3ϕMVA_{base,3\phi}): A single common value selected for the entire power system (most commonly 100 MVA100\text{ MVA} or 10 MVA10\text{ MVA}).
  2. Line-to-Line Voltage Base (Vbase,LLV_{base,LL} or kVbase,LLkV_{base,LL}): Specified for a reference zone and transferred across transformer boundaries according to nominal voltage ratings.

All remaining base parameters (Base Current, Base Impedance, and Base Admittance) are strictly derived from these two fundamental quantities.

                                  ┌────────────────────────┐
                                  │  Selected System Base  │
                                  │  S_base,3φ & V_base,LL │
                                  └───────────┬────────────┘
                                              │
                     ┌────────────────────────┴────────────────────────┐
                     ▼                                                 ▼
        ┌─────────────────────────┐                       ┌─────────────────────────┐
        │       Base Current      │                       │      Base Impedance     │
        │         S_base          │                       │       (V_base,LL)^2     │
        │ I_base = ─────────────  │                       │ Z_base = ─────────────  │
        │          √3 · V_base    │                       │          S_base,3φ      │
        └─────────────────────────┘                       └───────────┬─────────────┘
                                                                      │
                                                                      ▼
                                                          ┌─────────────────────────┐
                                                          │     Base Admittance     │
                                                          │ Y_base = 1 / Z_base     │
                                                          └─────────────────────────┘

Mathematical Derivations of Derived Bases

Base Current (IbaseI_{base})

Starting from the balanced three-phase apparent power relation S3ϕ=3VLLILS_{3\phi} = \sqrt{3} V_{LL} I_L:

Ibase=Sbase,3ϕ3⋅Vbase,LL=MVAbase,3ϕ×1033⋅kVbase,LL[in Amperes or kA]I_{base} = \frac{S_{base,3\phi}}{\sqrt{3} \cdot V_{base,LL}} = \frac{MVA_{base,3\phi} \times 10^3}{\sqrt{3} \cdot kV_{base,LL}} \quad [\text{in Amperes or kA}]

Base Impedance (ZbaseZ_{base})

Base impedance per phase is defined as the ratio of base line-to-neutral voltage (Vbase,LN=Vbase,LL/3V_{base,LN} = V_{base,LL} / \sqrt{3}) to base line current (IbaseI_{base}):

Zbase=Vbase,LNIbase=Vbase,LL/3Sbase,3ϕ3⋅Vbase,LL=(Vbase,LL)2Sbase,3ϕZ_{base} = \frac{V_{base,LN}}{I_{base}} = \frac{V_{base,LL} / \sqrt{3}}{\frac{S_{base,3\phi}}{\sqrt{3} \cdot V_{base,LL}}} = \frac{(V_{base,LL})^2}{S_{base,3\phi}}

Expressing line-to-line voltage in kilovolts (kVkV) and three-phase power in megavolt-amperes (MVAMVA):

Zbase=(kVbase,LL×103)2MVAbase,3ϕ×106=(kVbase,LL)2MVAbase,3ϕ[Ω]Z_{base} = \frac{(kV_{base,LL} \times 10^3)^2}{MVA_{base,3\phi} \times 10^6} = \frac{(kV_{base,LL})^2}{MVA_{base,3\phi}} \quad [\Omega]

Base Admittance (YbaseY_{base})

Base admittance is the exact reciprocal of base impedance:

Ybase=1Zbase=Sbase,3ϕ(Vbase,LL)2=MVAbase,3ϕ(kVbase,LL)2[Siemens / ℧]Y_{base} = \frac{1}{Z_{base}} = \frac{S_{base,3\phi}}{(V_{base,LL})^2} = \frac{MVA_{base,3\phi}}{(kV_{base,LL})^2} \quad [\text{Siemens / }\mho]
ParameterFormula (Fundamental)Formula (Practical Engineering Units)Physical Unit
Base PowerSbase,3ϕ=3Sbase,1ϕS_{base,3\phi} = 3 S_{base,1\phi}Specified (100 MVA100\text{ MVA}, 10 MVA10\text{ MVA}, etc.)MVA\text{MVA}
Base VoltageVbase,LL=3Vbase,LNV_{base,LL} = \sqrt{3} V_{base,LN}Specified per voltage zonekV\text{kV}
Base CurrentIbase=Sbase,3ϕ3Vbase,LLI_{base} = \frac{S_{base,3\phi}}{\sqrt{3} V_{base,LL}}Ibase=MVAbase,3ϕ×10003⋅kVbase,LLI_{base} = \frac{MVA_{base,3\phi} \times 1000}{\sqrt{3} \cdot kV_{base,LL}}Amperes (A)\text{Amperes (A)}
Base ImpedanceZbase=(Vbase,LL)2Sbase,3ϕZ_{base} = \frac{(V_{base,LL})^2}{S_{base,3\phi}}Zbase=(kVbase,LL)2MVAbase,3ϕZ_{base} = \frac{(kV_{base,LL})^2}{MVA_{base,3\phi}}Ohms (Ω)\text{Ohms (}\Omega\text{)}
Base AdmittanceYbase=Sbase,3ϕ(Vbase,LL)2Y_{base} = \frac{S_{base,3\phi}}{(V_{base,LL})^2}Ybase=MVAbase,3ϕ(kVbase,LL)2Y_{base} = \frac{MVA_{base,3\phi}}{(kV_{base,LL})^2}Siemens (S)\text{Siemens (S)}

3. Converting Between Physical Units and Per-Unit

Converting between physical engineering units and per-unit quantities is governed by the following direct relations:

Zpu=Zactual (Ω)Zbase (Ω)=Zactual (Ω)×MVAbase,3ϕ(kVbase,LL)2Z_{pu} = \frac{Z_{actual\ (\Omega)}}{Z_{base\ (\Omega)}} = Z_{actual\ (\Omega)} \times \frac{MVA_{base,3\phi}}{(kV_{base,LL})^2} Zactual (Ω)=Zpu×Zbase (Ω)=Zpu×(kVbase,LL)2MVAbase,3ϕZ_{actual\ (\Omega)} = Z_{pu} \times Z_{base\ (\Omega)} = Z_{pu} \times \frac{(kV_{base,LL})^2}{MVA_{base,3\phi}} Vpu=Vactual (kV)kVbase,LL,Ipu=Iactual (A)Ibase (A),Spu=Sactual (MVA)MVAbase,3ϕV_{pu} = \frac{V_{actual\ (kV)}}{kV_{base,LL}}, \quad I_{pu} = \frac{I_{actual\ (A)}}{I_{base\ (A)}}, \quad S_{pu} = \frac{S_{actual\ (MVA)}}{MVA_{base,3\phi}}

4. Equipment Base Impedance Conversion Formula

Electrical equipment (generators, transformers, motors, reactors) is tested and stamped by manufacturers with per-unit or percent impedance (X′′X'', XdX_d, %Z\%Z) based on its own nameplate ratings (Srated,VratedS_{rated}, V_{rated}):

%Z=Zpu×100%  ⟹  Zpu,old=%Z100\%Z = Z_{pu} \times 100\% \implies Z_{pu,old} = \frac{\%Z}{100}

When incorporating equipment into a system-wide study with a common system power base (Sbase,newS_{base,new}) and zone voltage base (Vbase,newV_{base,new}), the per-unit impedance must be adjusted to the new base.

Derivation of the Base Conversion Formula

Because the actual ohmic impedance Zactual (Ω)Z_{actual\ (\Omega)} of the physical device is a constant physical property:

Zactual=Zpu,old×Zbase,old=Zpu,new×Zbase,newZ_{actual} = Z_{pu,old} \times Z_{base,old} = Z_{pu,new} \times Z_{base,new}

Solving for Zpu,newZ_{pu,new}:

Zpu,new=Zpu,old×Zbase,oldZbase,new=Zpu,old×(Vbase,old)2/Sbase,old(Vbase,new)2/Sbase,newZ_{pu,new} = Z_{pu,old} \times \frac{Z_{base,old}}{Z_{base,new}} = Z_{pu,old} \times \frac{(V_{base,old})^2 / S_{base,old}}{(V_{base,new})^2 / S_{base,new}}

Rearranging into the standard base conversion equation:

Zpu,new=Zpu,old×(Vbase,oldVbase,new)2×(Sbase,newSbase,old)Z_{pu,new} = Z_{pu,old} \times \left(\frac{V_{base,old}}{V_{base,new}}\right)^2 \times \left(\frac{S_{base,new}}{S_{base,old}}\right)

Where:

  • Zpu,oldZ_{pu,old} = Nameplate per-unit impedance of the equipment
  • Vbase,oldV_{base,old} = Nameplate rated voltage of the equipment (kV)
  • Vbase,newV_{base,new} = System base voltage of the specific zone where equipment resides (kV)
  • Sbase,oldS_{base,old} = Nameplate rated apparent power of the equipment (MVA)
  • Sbase,newS_{base,new} = Common system base apparent power (MVA)

Important

If the equipment rated voltage exactly equals the zone base voltage (Vbase,old=Vbase,newV_{base,old} = V_{base,new}), the voltage ratio is 1.01.0, and the conversion simplifies to scaling by the power ratio: Zpu,new=Zpu,old×(Sbase,newSbase,old)Z_{pu,new} = Z_{pu,old} \times \left(\frac{S_{base,new}}{S_{base,old}}\right).


5. Comprehensive Step-by-Step Worked Calculation Example

Problem Statement

A radial three-phase utility interconnection consists of:

  • Generator G1: Rated 50 MVA50\text{ MVA}, 13.8 kV13.8\text{ kV}, with subtransient reactance Xd′′=0.18 puX_d'' = 0.18\text{ pu}.
  • Step-Up Transformer T1: Rated 60 MVA60\text{ MVA}, 13.2 kVΔ−115 kV Y13.2\text{ kV} \Delta - 115\text{ kV}\text{ Y}, with leakage reactance XT1=0.09 puX_{T1} = 0.09\text{ pu} (9%9\%).
  • Transmission Line TL1: 115 kV115\text{ kV}, 20 miles20\text{ miles} in length, with series impedance z=0.12+j0.48 Ω/milez = 0.12 + j0.48\ \Omega/\text{mile}.

Task: Using a system base of Sbase,3ϕ=100 MVAS_{base,3\phi} = 100\text{ MVA} and Vbase,1=13.8 kVV_{base,1} = 13.8\text{ kV} at the generator bus (Zone 1), calculate the per-unit impedance of all components on the system base.

  Zone 1 (13.8 kV)              Zone 2 (120.23 kV or 115 kV)
 ┌───────────────┐           ┌────────────────────────────────┐
 │  Generator G1 │    T1     │         Line TL1 (20 mi)       │
 │   50 MVA      ├───[88]───┬┼───────────────────────────────■ Load Bus
 │   13.8 kV     │ 13.2/115 ││     z = 0.12 + j0.48 Ω/mi      │
 │  X'' = 0.18   │   60 MVA ││                                │
 └───────────────┘  X = 0.09│└────────────────────────────────┘
                            │
                     Zone Boundary

Step-by-Step Solution

Step 1: Establish System Voltage Zones

  • Zone 1 (Generator Zone): Given Vbase,1=13.8 kVV_{base,1} = 13.8\text{ kV}.
  • Zone 2 (Transmission Line Zone): Determined by transformer T1 turns ratio (13.2 kV:115 kV13.2\text{ kV} : 115\text{ kV}): Vbase,2=Vbase,1×(VT1,secVT1,pri)=13.8 kV×(115 kV13.2 kV)=120.227 kVV_{base,2} = V_{base,1} \times \left(\frac{V_{T1,sec}}{V_{T1,pri}}\right) = 13.8\text{ kV} \times \left(\frac{115\text{ kV}}{13.2\text{ kV}}\right) = 120.227\text{ kV}

Step 2: Convert Generator G1 Reactance

  • Sbase,old=50 MVAS_{base,old} = 50\text{ MVA}, Vbase,old=13.8 kVV_{base,old} = 13.8\text{ kV}, Xold=0.18 puX_{old} = 0.18\text{ pu}
  • Sbase,new=100 MVAS_{base,new} = 100\text{ MVA}, Vbase,new=13.8 kVV_{base,new} = 13.8\text{ kV}
XG1,pu=0.18×(13.8 kV13.8 kV)2×(100 MVA50 MVA)=0.18×(1.0)2×2.0=0.3600 puX_{G1,pu} = 0.18 \times \left(\frac{13.8\text{ kV}}{13.8\text{ kV}}\right)^2 \times \left(\frac{100\text{ MVA}}{50\text{ MVA}}\right) = 0.18 \times (1.0)^2 \times 2.0 = 0.3600\text{ pu}

Step 3: Convert Transformer T1 Reactance

Let us evaluate the conversion from both the primary (LV) and secondary (HV) sides to prove mathematical invariance:

  • From Primary (LV) Side: Vbase,old=13.2 kVV_{base,old} = 13.2\text{ kV}, Vbase,new=13.8 kVV_{base,new} = 13.8\text{ kV}, Sold=60 MVAS_{old} = 60\text{ MVA}, Snew=100 MVAS_{new} = 100\text{ MVA}: XT1,pu=0.09×(13.2 kV13.8 kV)2×(100 MVA60 MVA)=0.09×0.91493×1.6667=0.1372 puX_{T1,pu} = 0.09 \times \left(\frac{13.2\text{ kV}}{13.8\text{ kV}}\right)^2 \times \left(\frac{100\text{ MVA}}{60\text{ MVA}}\right) = 0.09 \times 0.91493 \times 1.6667 = 0.1372\text{ pu}
  • From Secondary (HV) Side: Vbase,old=115 kVV_{base,old} = 115\text{ kV}, Vbase,new=120.227 kVV_{base,new} = 120.227\text{ kV}, Sold=60 MVAS_{old} = 60\text{ MVA}, Snew=100 MVAS_{new} = 100\text{ MVA}: XT1,pu=0.09×(115 kV120.227 kV)2×(100 MVA60 MVA)=0.09×0.91493×1.6667=0.1372 puX_{T1,pu} = 0.09 \times \left(\frac{115\text{ kV}}{120.227\text{ kV}}\right)^2 \times \left(\frac{100\text{ MVA}}{60\text{ MVA}}\right) = 0.09 \times 0.91493 \times 1.6667 = 0.1372\text{ pu}

Both perspectives yield the exact same per-unit impedance (0.1372 pu0.1372\text{ pu}).

Step 4: Convert Transmission Line TL1 Impedance

  • Calculate total actual ohmic impedance: Zline,actual=20 miles×(0.12+j0.48 Ω/mile)=2.40+j9.60 ΩZ_{line,actual} = 20\text{ miles} \times (0.12 + j0.48\ \Omega/\text{mile}) = 2.40 + j9.60\ \Omega
  • Calculate Zone 2 Base Impedance: Zbase,2=(Vbase,2)2Sbase,3ϕ=(120.227 kV)2100 MVA=14454.53100=144.545 ΩZ_{base,2} = \frac{(V_{base,2})^2}{S_{base,3\phi}} = \frac{(120.227\text{ kV})^2}{100\text{ MVA}} = \frac{14454.53}{100} = 144.545\ \Omega
  • Convert actual ohms to per-unit: Rline,pu=2.40 Ω144.545 Ω=0.0166 puR_{line,pu} = \frac{2.40\ \Omega}{144.545\ \Omega} = 0.0166\text{ pu} Xline,pu=9.60 Ω144.545 Ω=0.0664 puX_{line,pu} = \frac{9.60\ \Omega}{144.545\ \Omega} = 0.0664\text{ pu} Zline,pu=0.0166+j0.0664 puZ_{line,pu} = 0.0166 + j0.0664\text{ pu}

Summary of Network Impedances on 100 MVA Base

  • XG1=j0.3600 puX_{G1} = j0.3600\text{ pu}
  • XT1=j0.1372 puX_{T1} = j0.1372\text{ pu}
  • ZTL1=0.0166+j0.0664 puZ_{TL1} = 0.0166 + j0.0664\text{ pu}
  • Total Series Impedance Ztotal=0.0166+j(0.3600+0.1372+0.0664)=0.0166+j0.5636 puZ_{total} = 0.0166 + j(0.3600 + 0.1372 + 0.0664) = 0.0166 + j0.5636\text{ pu}

6. Common NCEES Exam Pitfalls & Traps

Warning

Exam Trap 1: Forgetting to Square the Voltage Ratio. Candidates frequently write Vbase,oldVbase,new\frac{V_{base,old}}{V_{base,new}} instead of (Vbase,oldVbase,new)2\left(\frac{V_{base,old}}{V_{base,new}}\right)^2. Remember that impedance is proportional to voltage squared (Z∝V2/SZ \propto V^2 / S).

Caution

Exam Trap 2: Mixing Single-Phase and Three-Phase Formulas. When applying Zbase=Vbase2SbaseZ_{base} = \frac{V_{base}^2}{S_{base}}, always use Line-to-Line kV with Three-Phase MVA. If using Line-to-Neutral kV, you must divide by single-phase MVA (Zbase=(kVLN)2MVA1ϕZ_{base} = \frac{(kV_{LN})^2}{MVA_{1\phi}}), which yields the identical numeric value.

Note

Exam Trap 3: Percent vs. Per-Unit Confusion. Transformer nameplate impedance is almost always given as a percentage (e.g., 7.5%Z7.5\%Z). You must divide by 100100 (0.075 pu0.075\text{ pu}) before entering it into any base conversion formula.

Loading diagram...
Per-Unit Base Conversion Workflow Across System Voltage Zones
Test Your Knowledge

A 3-phase, 138 kV transmission line has a system base power of 100 MVA. What is the base impedance of this transmission zone, and what is the per-unit reactance of a 25-mile line segment with an actual series inductive reactance of 0.762 Ω/mile?

A

Base impedance is 190.44 Ω; line per-unit reactance is 0.100 pu

B

Base impedance is 110.00 Ω; line per-unit reactance is 0.173 pu

C

Base impedance is 330.00 Ω; line per-unit reactance is 0.058 pu

D

Base impedance is 190.44 Ω; line per-unit reactance is 0.033 pu

Test Your Knowledge

A 3-phase generator is rated at 25 MVA, 13.2 kV, with a subtransient reactance of X_d'' = 0.18 pu. If the system base is selected as 100 MVA and 13.8 kV at the generator bus, what is the converted subtransient reactance on the system base?

A

0.041 pu

B

0.688 pu

C

0.659 pu

D

0.752 pu

Test Your Knowledge

Which of the following expressions correctly defines the base current in Amperes for a balanced three-phase circuit with base power S_base,3phi (in VA) and base line-to-line voltage V_base,LL (in Volts)?

A

I_base = S_base,3phi / (3 * V_base,LL)

B

I_base = S_base,3phi / V_base,LL

C

I_base = (sqrt(3) * S_base,3phi) / V_base,LL

D

I_base = S_base,3phi / (sqrt(3) * V_base,LL)

Sections you finish are checked off in the contents.