8.1 Per-Unit System Fundamentals & Base Conversion Formulas
Key Takeaways
- The per-unit (pu) normalization simplifies multi-voltage power system analysis by eliminating ideal transformer turns ratios and standardizing electrical parameters across diverse equipment ratings.
- In balanced three-phase systems, selecting system base three-phase apparent power ($S_{base,3\phi}$) and line-to-line voltage ($V_{base,LL}$) establishes base impedance $Z_{base} = (V_{base,LL})^2 / S_{base,3\phi} = (kV_{base,LL})^2 / MVA_{base,3\phi}$ and base current $I_{base} = S_{base,3\phi} / (\sqrt{3} V_{base,LL})$.
- Equipment nameplate impedance must be converted to system base values using $Z_{pu,new} = Z_{pu,old} \times (V_{base,old} / V_{base,new})^2 \times (S_{base,new} / S_{base,old})$.
- Per-unit impedance is identical whether viewed from the primary or secondary winding of an ideal transformer when base voltages match the transformer rated turns ratio.
8.1 Per-Unit System Fundamentals & Base Conversion Formulas
Key Exam Takeaway: In balanced three-phase power system calculations, base impedance is derived exclusively from the three-phase power base and the line-to-line voltage base: $Z_{base} = \frac{(kV_{base,LL})^2}{MVA_{base,3\phi}}$. When converting equipment impedance to a new system base, always apply the ratio of voltages squared and the inverse ratio of power ratings: $Z_{pu,new} = Z_{pu,old} \left(\frac{V_{base,old}}{V_{base,new}}\right)^2 \left(\frac{S_{base,new}}{S_{base,old}}\right)$.
1. Rationale of the Per-Unit System
Modern electrical power networks span multiple voltage levels—ranging from generation ($13.8\text{ kV}$ to $24\text{ kV}$), extra-high-voltage transmission ($138\text{ kV}$, $230\text{ kV}$, $500\text{ kV}$), sub-transmission ($69\text{ kV}$, $34.5\text{ kV}$), distribution ($12.47\text{ kV}$, $4.16\text{ kV}$), down to utilization ($480\text{ V}$, $208\text{ V}$, $120\text{ V}$). Analyzing these networks using actual physical quantities (Ohms, Volts, Amperes) requires reflecting impedances across transformer boundaries using the square of the turns ratio ($a^2 = (N_1/N_2)^2$). In multi-bus interconnected networks with tens or hundreds of transformers, manual impedance reflection becomes intensely error-prone.
The per-unit (pu) system normalizes electrical quantities by expressing them as dimensionless decimal fractions or ratios of carefully defined base reference parameters:
Primary Advantages in Power Engineering
- Elimination of Transformer Turns Ratios: When base voltages in adjacent zones are selected in proportion to transformer turns ratios, the per-unit equivalent impedance of a transformer is identical whether calculated from the high-voltage or low-voltage winding.
- Parameter Standardization: Apparatus of similar design and construction exhibit per-unit impedances within narrow, predictable bands regardless of physical size or MVA rating. For example, large two-pole synchronous generator subtransient reactances consistently fall between $0.12\text{ pu}$ and $0.25\text{ pu}$, and two-winding substation transformers typically have leakage reactances between $0.06\text{ pu}$ and $0.10\text{ pu}$.
- Simplification of 3-Phase Formulations: Factors of $\sqrt{3}$ and $3$ vanish from balanced three-phase voltage, current, and complex power equations when standard three-phase base conventions are applied.
- Immediate Insight into Operating Limits: Operating at $V = 0.94\text{ pu}$ instantly conveys a $6%$ undervoltage condition without needing to recall whether the nominal bus voltage is $13.8\text{ kV}$ or $115\text{ kV}$.
2. Fundamental Base Relationships in Three-Phase Networks
To establish a per-unit system for a three-phase network, two independent base quantities must be selected. By universal utility and NCEES convention, these two quantities are:
- System Three-Phase Apparent Power Base ($S_{base,3\phi}$ or $MVA_{base,3\phi}$): A single common value selected for the entire power system (most commonly $100\text{ MVA}$ or $10\text{ MVA}$).
- Line-to-Line Voltage Base ($V_{base,LL}$ or $kV_{base,LL}$): Specified for a reference zone and transferred across transformer boundaries according to nominal voltage ratings.
All remaining base parameters (Base Current, Base Impedance, and Base Admittance) are strictly derived from these two fundamental quantities.
┌────────────────────────┐
│ Selected System Base │
│ S_base,3φ & V_base,LL │
└───────────┬────────────┘
│
┌────────────────────────┴────────────────────────┐
▼ ▼
┌─────────────────────────┐ ┌─────────────────────────┐
│ Base Current │ │ Base Impedance │
│ S_base │ │ (V_base,LL)^2 │
│ I_base = ───────────── │ │ Z_base = ───────────── │
│ √3 · V_base │ │ S_base,3φ │
└─────────────────────────┘ └───────────┬─────────────┘
│
▼
┌─────────────────────────┐
│ Base Admittance │
│ Y_base = 1 / Z_base │
└─────────────────────────┘
Mathematical Derivations of Derived Bases
Base Current ($I_{base}$)
Starting from the balanced three-phase apparent power relation $S_{3\phi} = \sqrt{3} V_{LL} I_L$:
Base Impedance ($Z_{base}$)
Base impedance per phase is defined as the ratio of base line-to-neutral voltage ($V_{base,LN} = V_{base,LL} / \sqrt{3}$) to base line current ($I_{base}$):
Expressing line-to-line voltage in kilovolts ($kV$) and three-phase power in megavolt-amperes ($MVA$):
Base Admittance ($Y_{base}$)
Base admittance is the exact reciprocal of base impedance:
| Parameter | Formula (Fundamental) | Formula (Practical Engineering Units) | Physical Unit |
|---|---|---|---|
| Base Power | $S_{base,3\phi} = 3 S_{base,1\phi}$ | Specified ($100\text{ MVA}$, $10\text{ MVA}$, etc.) | $\text{MVA}$ |
| Base Voltage | $V_{base,LL} = \sqrt{3} V_{base,LN}$ | Specified per voltage zone | $\text{kV}$ |
| Base Current | $I_{base} = \frac{S_{base,3\phi}}{\sqrt{3} V_{base,LL}}$ | $I_{base} = \frac{MVA_{base,3\phi} \times 1000}{\sqrt{3} \cdot kV_{base,LL}}$ | $\text{Amperes (A)}$ |
| Base Impedance | $Z_{base} = \frac{(V_{base,LL})^2}{S_{base,3\phi}}$ | $Z_{base} = \frac{(kV_{base,LL})^2}{MVA_{base,3\phi}}$ | $\text{Ohms (}\Omega\text{)}$ |
| Base Admittance | $Y_{base} = \frac{S_{base,3\phi}}{(V_{base,LL})^2}$ | $Y_{base} = \frac{MVA_{base,3\phi}}{(kV_{base,LL})^2}$ | $\text{Siemens (S)}$ |
3. Converting Between Physical Units and Per-Unit
Converting between physical engineering units and per-unit quantities is governed by the following direct relations:
4. Equipment Base Impedance Conversion Formula
Electrical equipment (generators, transformers, motors, reactors) is tested and stamped by manufacturers with per-unit or percent impedance ($X''$, $X_d$, $%Z$) based on its own nameplate ratings ($S_{rated}, V_{rated}$):
When incorporating equipment into a system-wide study with a common system power base ($S_{base,new}$) and zone voltage base ($V_{base,new}$), the per-unit impedance must be adjusted to the new base.
Derivation of the Base Conversion Formula
Because the actual ohmic impedance $Z_{actual\ (\Omega)}$ of the physical device is a constant physical property:
Solving for $Z_{pu,new}$:
Rearranging into the standard base conversion equation:
Where:
- $Z_{pu,old}$ = Nameplate per-unit impedance of the equipment
- $V_{base,old}$ = Nameplate rated voltage of the equipment (kV)
- $V_{base,new}$ = System base voltage of the specific zone where equipment resides (kV)
- $S_{base,old}$ = Nameplate rated apparent power of the equipment (MVA)
- $S_{base,new}$ = Common system base apparent power (MVA)
[!IMPORTANT] If the equipment rated voltage exactly equals the zone base voltage ($V_{base,old} = V_{base,new}$), the voltage ratio is $1.0$, and the conversion simplifies to scaling by the power ratio: $Z_{pu,new} = Z_{pu,old} \times \left(\frac{S_{base,new}}{S_{base,old}}\right)$.
5. Comprehensive Step-by-Step Worked Calculation Example
Problem Statement
A radial three-phase utility interconnection consists of:
- Generator G1: Rated $50\text{ MVA}$, $13.8\text{ kV}$, with subtransient reactance $X_d'' = 0.18\text{ pu}$.
- Step-Up Transformer T1: Rated $60\text{ MVA}$, $13.2\text{ kV} \Delta - 115\text{ kV}\text{ Y}$, with leakage reactance $X_{T1} = 0.09\text{ pu}$ ($9%$).
- Transmission Line TL1: $115\text{ kV}$, $20\text{ miles}$ in length, with series impedance $z = 0.12 + j0.48\ \Omega/\text{mile}$.
Task: Using a system base of $S_{base,3\phi} = 100\text{ MVA}$ and $V_{base,1} = 13.8\text{ kV}$ at the generator bus (Zone 1), calculate the per-unit impedance of all components on the system base.
Zone 1 (13.8 kV) Zone 2 (120.23 kV or 115 kV)
┌───────────────┐ ┌────────────────────────────────┐
│ Generator G1 │ T1 │ Line TL1 (20 mi) │
│ 50 MVA ├───[88]───┬┼───────────────────────────────■ Load Bus
│ 13.8 kV │ 13.2/115 ││ z = 0.12 + j0.48 Ω/mi │
│ X'' = 0.18 │ 60 MVA ││ │
└───────────────┘ X = 0.09│└────────────────────────────────┘
│
Zone Boundary
Step-by-Step Solution
Step 1: Establish System Voltage Zones
- Zone 1 (Generator Zone): Given $V_{base,1} = 13.8\text{ kV}$.
- Zone 2 (Transmission Line Zone): Determined by transformer T1 turns ratio ($13.2\text{ kV} : 115\text{ kV}$):
Step 2: Convert Generator G1 Reactance
- $S_{base,old} = 50\text{ MVA}$, $V_{base,old} = 13.8\text{ kV}$, $X_{old} = 0.18\text{ pu}$
- $S_{base,new} = 100\text{ MVA}$, $V_{base,new} = 13.8\text{ kV}$
Step 3: Convert Transformer T1 Reactance
Let us evaluate the conversion from both the primary (LV) and secondary (HV) sides to prove mathematical invariance:
- From Primary (LV) Side: $V_{base,old} = 13.2\text{ kV}$, $V_{base,new} = 13.8\text{ kV}$, $S_{old} = 60\text{ MVA}$, $S_{new} = 100\text{ MVA}$:
- From Secondary (HV) Side: $V_{base,old} = 115\text{ kV}$, $V_{base,new} = 120.227\text{ kV}$, $S_{old} = 60\text{ MVA}$, $S_{new} = 100\text{ MVA}$: Both perspectives yield the exact same per-unit impedance ($0.1372\text{ pu}$).
Step 4: Convert Transmission Line TL1 Impedance
- Calculate total actual ohmic impedance:
- Calculate Zone 2 Base Impedance:
- Convert actual ohms to per-unit:
Summary of Network Impedances on 100 MVA Base
- $X_{G1} = j0.3600\text{ pu}$
- $X_{T1} = j0.1372\text{ pu}$
- $Z_{TL1} = 0.0166 + j0.0664\text{ pu}$
- Total Series Impedance $Z_{total} = 0.0166 + j(0.3600 + 0.1372 + 0.0664) = 0.0166 + j0.5636\text{ pu}$
6. Common NCEES Exam Pitfalls & Traps
[!WARNING] Exam Trap 1: Forgetting to Square the Voltage Ratio. Candidates frequently write $\frac{V_{base,old}}{V_{base,new}}$ instead of $\left(\frac{V_{base,old}}{V_{base,new}}\right)^2$. Remember that impedance is proportional to voltage squared ($Z \propto V^2 / S$).
[!CAUTION] Exam Trap 2: Mixing Single-Phase and Three-Phase Formulas. When applying $Z_{base} = \frac{V_{base}^2}{S_{base}}$, always use Line-to-Line kV with Three-Phase MVA. If using Line-to-Neutral kV, you must divide by single-phase MVA ($Z_{base} = \frac{(kV_{LN})^2}{MVA_{1\phi}}$), which yields the identical numeric value.
[!NOTE] Exam Trap 3: Percent vs. Per-Unit Confusion. Transformer nameplate impedance is almost always given as a percentage (e.g., $7.5%Z$). You must divide by $100$ ($0.075\text{ pu}$) before entering it into any base conversion formula.
A 3-phase, 138 kV transmission line has a system base power of 100 MVA. What is the base impedance of this transmission zone, and what is the per-unit reactance of a 25-mile line segment with an actual series inductive reactance of 0.762 Ω/mile?
A 3-phase generator is rated at 25 MVA, 13.2 kV, with a subtransient reactance of X_d'' = 0.18 pu. If the system base is selected as 100 MVA and 13.8 kV at the generator bus, what is the converted subtransient reactance on the system base?
Which of the following expressions correctly defines the base current in Amperes for a balanced three-phase circuit with base power S_base,3phi (in VA) and base line-to-line voltage V_base,LL (in Volts)?