13.2 Unsymmetrical Fault Analysis (SLG, L-L, DLG Fault Calculations)
Key Takeaways
Symmetrical components decompose unbalanced three-phase systems into three uncoupled sequence networks: Positive sequence (), Negative sequence (), and Zero sequence () via the Fortescue transformation matrix with .
Single Line-to-Ground (SLG) faults require connecting positive, negative, and zero sequence networks in series: , with total fault current .
Line-to-Line (L-L) faults involve only positive and negative sequence networks connected in parallel (), yielding , which equals of when .
Double Line-to-Ground (DLG) faults connect positive, negative, and zero sequence networks in parallel: , where total ground return current is .
When zero-sequence impedance is less than positive-sequence impedance (, common near solidly grounded generators and transformers), the SLG fault current strictly exceeds the symmetrical 3-phase fault current ().
13.2 Unsymmetrical Fault Analysis (SLG, L-L, DLG Fault Calculations)
Executive Overview: While three-phase faults represent the most severe balanced condition, the vast majority of real-world power system faults are unsymmetrical: Single Line-to-Ground (SLG, of all faults), Line-to-Line (L-L, ), and Double Line-to-Ground (DLG, ). Analyzing unsymmetrical faults requires Fortescue symmetrical component transformations to decouple mutually coupled three-phase networks into independent Positive (), Negative (), and Zero () sequence networks. On the NCEES PE Power exam, candidates must master the boundary conditions, sequence network interconnections, ground potential rise (), and unfaulted phase voltage shifts across all fault types.
1. Symmetrical Components Matrix Foundations
In 1918, Charles LeGeyt Fortescue proved that any unbalanced set of three-phase phasors () can be decomposed into three symmetrical sequence components:
where the complex rotation operator has properties:
Inverting the transformation matrix gives sequence currents from phase currents:
2. Single Line-to-Ground (SLG) Fault Analysis
Consider an SLG fault on phase through fault impedance to ground:
Boundary Conditions in Physical Domain
Sequence Domain Transformations
Substituting boundary conditions into :
Because the sequence currents are strictly identical, the positive, negative, and zero sequence networks are connected in SERIES.
Sequence Network Connection for Single Line-to-Ground (SLG) Fault:
(+) o---(~) V_F ---[ Z_1 ]---o
|
(+) o--------------[ Z_2 ]---o (SERIES CONNECTION)
|
(+) o--------------[ Z_0 ]---o
|
[ 3*Z_f ]
|
(-) o------------------------o Neutral Reference Bus
SLG Fault Current Formulas
Ground Potential Rise & Unfaulted Phase Voltage Swell
When an SLG fault occurs, current returning through grounding resistance elevates substation ground grid voltage:
On ungrounded systems (), the fault current is limited only by distributed line-to-ground capacitance (), but the voltages of unfaulted phases and shift from line-to-neutral to full line-to-line magnitude:
3. Line-to-Line (L-L) Fault Analysis
Consider an L-L fault between phases and through fault impedance :
Boundary Conditions in Physical Domain
Sequence Domain Transformations
Because and , the zero-sequence network is completely isolated (open-circuit), and the positive and negative sequence networks are connected in PARALLEL.
Sequence Network Connection for Line-to-Line (L-L) Fault:
(+) o---(~) V_F ---[ Z_1 ]---+---o
| |
[Z_f]|
| |
(+) o--------------[ Z_2 ]---+---o (PARALLEL: Pos || Neg)
(+) o--------------[ Z_0 ] (OPEN CIRCUIT: I_a0 = 0)
L-L Fault Current Formulas
Note
L-L vs. 3-Phase Ratio: If and , the bolted line-to-line fault current is:
4. Double Line-to-Ground (DLG) Fault Analysis
Consider a DLG fault where phases and contact each other and ground through fault impedance :
Boundary Conditions in Physical Domain
Sequence Domain Transformations
Connecting positive, negative, and zero sequence networks in PARALLEL:
Sequence Network Connection for Double Line-to-Ground (DLG) Fault:
+---[ Z_1 ]---(~) V_F
|
(+) o----+---[ Z_2 ]-----------o (-) (PARALLEL COMBINATION)
|
+---[ Z_0 + 3*Z_f ]---o
DLG Fault Current Formulas
Using current division to find negative and zero sequence currents:
Total ground return current:
5. Fault Severity Comparison ( vs. Dynamics)
Many engineers intuitively assume that three-phase faults always produce the highest current. However, in solidly grounded transmission substations and near generating stations, the zero-sequence impedance is frequently lower than positive-sequence impedance ().
When is SLG Fault Current Greater than 3-Phase Fault Current?
Assuming :
6. Comprehensive Worked Calculation: Multi-Fault Analysis
Problem Statement
A solidly grounded substation bus has the following Thevenin sequence impedances:
- ( due to proximity of a large solidly grounded generator step-up transformer)
- System Base: ,
- Prefault Voltage:
- Fault Impedance: (bolted faults)
Calculate for all four fault types:
- Symmetrical three-phase () bolted fault current.
- Single line-to-ground (SLG) fault current and ground current.
- Line-to-line (L-L) fault current.
- Double line-to-ground (DLG) sequence currents, phase currents, and total ground return current.
============================== STEP-BY-STEP SOLUTION ==============================
Step 1: Compute System Base Current at 13.8 kV
I_base = S_base / (sqrt(3) * V_base) = 100,000 kVA / (sqrt(3) * 13.8 kV)
= 4,183.70 A = 4.1837 kA
Step 2: Symmetrical Three-Phase Fault (3ph)
I_a1 = V_F / Z_1 = 1.0 / (j0.10) = -j10.00 pu = 10.00 /_ -90 deg pu
I_f,3ph = 10.00 pu
Physical Current: I_f,3ph = 10.00 * 4.1837 kA = 41.84 kA
Step 3: Single Line-to-Ground Fault (SLG on Phase a)
Z_total = Z_1 + Z_2 + Z_0 = j0.10 + j0.10 + j0.05 = j0.25 pu
I_a0 = I_a1 = I_a2 = V_F / Z_total = 1.0 / (j0.25) = -j4.00 pu = 4.00 /_ -90 deg pu
Total Fault Current in Phase a:
I_f,SLG = I_a = 3 * I_a0 = 3 * (-j4.00 pu) = -j12.00 pu = 12.00 /_ -90 deg pu
Physical Current: I_f,SLG = 12.00 * 4.1837 kA = 50.20 kA
>> CRITICAL OBSERVATION: I_SLG (50.20 kA) is 20% LARGER than I_3ph (41.84 kA)
because Z_0 (0.05 pu) < Z_1 (0.10 pu)!
Step 4: Line-to-Line Fault (L-L between Phases b and c)
I_a0 = 0
I_a1 = -I_a2 = V_F / (Z_1 + Z_2) = 1.0 / (j0.10 + j0.10) = 1.0 / (j0.20)
= -j5.00 pu = 5.00 /_ -90 deg pu
Fault Current Magnitude:
|I_f,LL| = sqrt(3) * |I_a1| = sqrt(3) * 5.00 pu = 8.660 pu
Physical Current: I_f,LL = 8.660 * 4.1837 kA = 36.23 kA
Check Ratio: I_LL / I_3ph = 36.23 / 41.84 = 0.8660 = sqrt(3)/2 (Exact)
Step 5: Double Line-to-Ground Fault (DLG on Phases b and c)
Parallel combination of Z_2 and Z_0:
Z_parallel = (Z_2 * Z_0) / (Z_2 + Z_0) = (j0.10 * j0.05) / (j0.10 + j0.05)
= -0.005 / (j0.15) = j0.03333 pu
Positive-Sequence Current:
I_a1 = V_F / (Z_1 + Z_parallel) = 1.0 / (j0.10 + j0.03333) = 1.0 / (j0.13333)
= -j7.500 pu = 7.500 /_ -90 deg pu
Negative and Zero Sequence Currents (Current Divider):
I_a2 = -I_a1 * [ Z_0 / (Z_2 + Z_0) ] = -(-j7.500) * [ 0.05 / 0.15 ]
= j2.500 pu = 2.500 /_ 90 deg pu
I_a0 = -I_a1 * [ Z_2 / (Z_2 + Z_0) ] = -(-j7.500) * [ 0.10 / 0.15 ]
= j5.000 pu = 5.000 /_ 90 deg pu
Verify Phase a Current: I_a = I_a0 + I_a1 + I_a2 = j5.0 - j7.5 + j2.5 = 0 pu (Verified)
Phase b and Phase c Fault Currents:
I_b = I_a0 + (a^2)*I_a1 + a*I_a2
= j5.0 + (-0.5 - j0.8660)*(-j7.5) + (-0.5 + j0.8660)*(j2.5)
= j5.0 + (-6.495 + j3.750) + (-2.165 - j1.250)
= -8.660 + j7.500 pu = 11.456 /_ 140.89 deg pu
|I_b| = |I_c| = 11.456 pu
Physical Phase Fault Current: I_b = 11.456 * 4.1837 kA = 47.93 kA
Total Ground Return Current:
I_g = 3 * I_a0 = 3 * (j5.000 pu) = j15.000 pu = 15.000 /_ 90 deg pu
Physical Ground Current: I_g = 15.000 * 4.1837 kA = 62.76 kA
============================== SUMMARY OF RESULTS ==============================
- 3-Phase Bolted Fault Current (I_3ph) = 10.00 pu = 41.84 kA
- Single Line-to-Ground Current (I_SLG) = 12.00 pu = 50.20 kA (+20.0% vs 3ph)
- Line-to-Line Fault Current (I_LL) = 8.66 pu = 36.23 kA (-13.4% vs 3ph)
- DLG Phase Fault Current (|I_b|, |I_c|)= 11.46 pu = 47.93 kA (+14.6% vs 3ph)
- DLG Ground Return Current (I_g) = 15.00 pu = 62.76 kA (+50.0% vs 3ph)
===================================================================================
7. Common Exam Traps & Strategic Pitfalls
- The "Factor of 3" Ground Current Omission: Calculating in an SLG fault and forgetting to multiply by to obtain the physical phase/ground fault current (). Relay engineers size ground overcurrent elements (50N/51N) based on .
- Assuming Three-Phase Fault Current is Always the Highest: Sizing circuit breakers exclusively for without checking . If , the SLG fault produces the maximum interrupting duty.
- Applying Zero-Sequence Networks to Line-to-Line Faults: Incorrectly including in L-L fault calculations. Because the fault does not touch ground and , no zero-sequence current can flow ().
- Confusing Fault Impedance Factor with : In SLG and DLG sequence networks, the physical fault impedance to ground must be multiplied by in the zero-sequence branch () because flows through the neutral ground path.
In a 3-phase power system, which fault type produces boundary conditions that require the positive-sequence, negative-sequence, and zero-sequence networks to be connected strictly in series?
Three-Phase Symmetrical Bolted Fault
Single Line-to-Ground (SLG) Fault
Line-to-Line (L-L) Fault
Double Line-to-Ground (DLG) Fault
A 13.8 kV solidly grounded substation bus has sequence impedances Z1 = j0.12 pu, Z2 = j0.12 pu, and Z0 = j0.06 pu. For a bolted line-to-line (L-L) fault between phases b and c, what is the fault current magnitude |I_f| in per-unit?
4.17 pu
5.00 pu
7.22 pu
8.33 pu
Under what system impedance condition does a bolted Single Line-to-Ground (SLG) fault produce a higher short-circuit current magnitude than a bolted Three-Phase (3-phase) symmetrical fault at the same bus?
When the zero-sequence Thevenin impedance is strictly less than the positive-sequence Thevenin impedance (Z0 < Z1), assuming Z1 = Z2.
When the system is ungrounded or grounded through a high-resistance grounding (HRG) neutral resistor.
When the negative-sequence impedance is significantly larger than the positive-sequence impedance (Z2 >> Z1).
When the fault occurs through a high fault impedance (Zf > 1.0 pu).
Sections you finish are checked off in the contents.