13.2 Unsymmetrical Fault Analysis (SLG, L-L, DLG Fault Calculations)

Key Takeaways

  • Symmetrical components decompose unbalanced three-phase systems into three uncoupled sequence networks: Positive sequence (012→1012\to 1), Negative sequence (012→2012\to 2), and Zero sequence (012→0012\to 0) via the Fortescue transformation matrix A\mathbf{A} with a=1∠120∘a = 1\angle 120^\circ.

  • Single Line-to-Ground (SLG) faults require connecting positive, negative, and zero sequence networks in series: Ia0=Ia1=Ia2=VFZ1+Z2+Z0+3ZfI_{a0} = I_{a1} = I_{a2} = \frac{V_F}{Z_1 + Z_2 + Z_0 + 3Z_f}, with total fault current If=3Ia0I_f = 3I_{a0}.

  • Line-to-Line (L-L) faults involve only positive and negative sequence networks connected in parallel (Ia0=0,Ia1=−Ia2I_{a0} = 0, I_{a1} = -I_{a2}), yielding ∣If,LL∣=3∣Ia1∣=3VF∣Z1+Z2+Zf∣|I_{f,LL}| = \sqrt{3}|I_{a1}| = \frac{\sqrt{3}V_F}{|Z_1 + Z_2 + Z_f|}, which equals 86.6%86.6\% of I3ϕI_{3\phi} when Z1=Z2Z_1 = Z_2.

  • Double Line-to-Ground (DLG) faults connect positive, negative, and zero sequence networks in parallel: Ia1=VFZ1+(Z2∥(Z0+3Zf))I_{a1} = \frac{V_F}{Z_1 + (Z_2 \parallel (Z_0 + 3Z_f))}, where total ground return current is Ig=3Ia0I_g = 3I_{a0}.

  • When zero-sequence impedance is less than positive-sequence impedance (Z0<Z1Z_0 < Z_1, common near solidly grounded generators and Δ−Yg\Delta-Y_g transformers), the SLG fault current strictly exceeds the symmetrical 3-phase fault current (ISLG>I3ϕI_{SLG} > I_{3\phi}).

Last updated: August 2026

13.2 Unsymmetrical Fault Analysis (SLG, L-L, DLG Fault Calculations)

Executive Overview: While three-phase faults represent the most severe balanced condition, the vast majority of real-world power system faults are unsymmetrical: Single Line-to-Ground (SLG, ∼70%\sim 70\% of all faults), Line-to-Line (L-L, ∼15%\sim 15\%), and Double Line-to-Ground (DLG, ∼10%\sim 10\%). Analyzing unsymmetrical faults requires Fortescue symmetrical component transformations to decouple mutually coupled three-phase networks into independent Positive (11), Negative (22), and Zero (00) sequence networks. On the NCEES PE Power exam, candidates must master the boundary conditions, sequence network interconnections, ground potential rise (GPRGPR), and unfaulted phase voltage shifts across all fault types.


1. Symmetrical Components Matrix Foundations

In 1918, Charles LeGeyt Fortescue proved that any unbalanced set of three-phase phasors (Ia,Ib,Ic\mathbf{I}_a, \mathbf{I}_b, \mathbf{I}_c) can be decomposed into three symmetrical sequence components:

[IaIbIc]=[1111a2a1aa2][Ia0Ia1Ia2]=AI012\begin{bmatrix} \mathbf{I}_a \\ \mathbf{I}_b \\ \mathbf{I}_c \end{bmatrix} = \begin{bmatrix} 1 & 1 & 1 \\ 1 & a^2 & a \\ 1 & a & a^2 \end{bmatrix} \begin{bmatrix} \mathbf{I}_{a0} \\ \mathbf{I}_{a1} \\ \mathbf{I}_{a2} \end{bmatrix} = \mathbf{A} \mathbf{I}_{012}

where the complex rotation operator a=1∠120∘=−0.5+j32=−0.5+j0.8660a = 1\angle 120^\circ = -0.5 + j\frac{\sqrt{3}}{2} = -0.5 + j0.8660 has properties:

  • a2=1∠240∘=1∠−120∘=−0.5−j0.8660a^2 = 1\angle 240^\circ = 1\angle -120^\circ = -0.5 - j0.8660
  • a3=1∠360∘=1.0∠0∘a^3 = 1\angle 360^\circ = 1.0\angle 0^\circ
  • 1+a+a2=01 + a + a^2 = 0

Inverting the transformation matrix A\mathbf{A} gives sequence currents from phase currents:

I012=A−1Iabc=13[1111aa21a2a][IaIbIc]\mathbf{I}_{012} = \mathbf{A}^{-1} \mathbf{I}_{abc} = \frac{1}{3} \begin{bmatrix} 1 & 1 & 1 \\ 1 & a & a^2 \\ 1 & a^2 & a \end{bmatrix} \begin{bmatrix} \mathbf{I}_a \\ \mathbf{I}_b \\ \mathbf{I}_c \end{bmatrix} Ia0=13(Ia+Ib+Ic)[Zero Sequence: In-phase, returns via ground]Ia1=13(Ia+aIb+a2Ic)[Positive Sequence: Normal a−b−c phase rotation]Ia2=13(Ia+a2Ib+aIc)[Negative Sequence: Reversed a−c−b phase rotation]\begin{aligned} \mathbf{I}_{a0} &= \frac{1}{3} (\mathbf{I}_a + \mathbf{I}_b + \mathbf{I}_c) \quad &[\text{Zero Sequence: In-phase, returns via ground}] \\ \mathbf{I}_{a1} &= \frac{1}{3} (\mathbf{I}_a + a\mathbf{I}_b + a^2\mathbf{I}_c) \quad &[\text{Positive Sequence: Normal } a-b-c \text{ phase rotation}] \\ \mathbf{I}_{a2} &= \frac{1}{3} (\mathbf{I}_a + a^2\mathbf{I}_b + a\mathbf{I}_c) \quad &[\text{Negative Sequence: Reversed } a-c-b \text{ phase rotation}] \end{aligned}

2. Single Line-to-Ground (SLG) Fault Analysis

Consider an SLG fault on phase aa through fault impedance ZfZ_f to ground:

Boundary Conditions in Physical Domain

  1. Ib=0\mathbf{I}_b = 0
  2. Ic=0\mathbf{I}_c = 0
  3. Va=IaZf\mathbf{V}_a = \mathbf{I}_a Z_f

Sequence Domain Transformations

Substituting boundary conditions into A−1\mathbf{A}^{-1}:

Ia0=13(Ia+0+0)=13Ia,Ia1=13Ia,Ia2=13Ia\mathbf{I}_{a0} = \frac{1}{3}(\mathbf{I}_a + 0 + 0) = \frac{1}{3}\mathbf{I}_a, \qquad \mathbf{I}_{a1} = \frac{1}{3}\mathbf{I}_a, \qquad \mathbf{I}_{a2} = \frac{1}{3}\mathbf{I}_a ∴Ia0=Ia1=Ia2=13Ia\therefore \mathbf{I}_{a0} = \mathbf{I}_{a1} = \mathbf{I}_{a2} = \frac{1}{3}\mathbf{I}_a

Because the sequence currents are strictly identical, the positive, negative, and zero sequence networks are connected in SERIES.

Sequence Network Connection for Single Line-to-Ground (SLG) Fault:

      (+) o---(~) V_F ---[ Z_1 ]---o
                                   |
      (+) o--------------[ Z_2 ]---o  (SERIES CONNECTION)
                                   |
      (+) o--------------[ Z_0 ]---o
                                   |
                                  [ 3*Z_f ]
                                   |
      (-) o------------------------o Neutral Reference Bus

SLG Fault Current Formulas

Ia0=Ia1=Ia2=VFZ1+Z2+Z0+3Zf\mathbf{I}_{a0} = \mathbf{I}_{a1} = \mathbf{I}_{a2} = \frac{\mathbf{V}_F}{\mathbf{Z}_1 + \mathbf{Z}_2 + \mathbf{Z}_0 + 3 Z_f} If=Ia=Ia0+Ia1+Ia2=3Ia0=3VFZ1+Z2+Z0+3Zf\mathbf{I}_f = \mathbf{I}_a = \mathbf{I}_{a0} + \mathbf{I}_{a1} + \mathbf{I}_{a2} = 3\mathbf{I}_{a0} = \frac{3\mathbf{V}_F}{\mathbf{Z}_1 + \mathbf{Z}_2 + \mathbf{Z}_0 + 3 Z_f}

Ground Potential Rise & Unfaulted Phase Voltage Swell

When an SLG fault occurs, current returning through grounding resistance RgR_g elevates substation ground grid voltage:

GPR=∣Ig∣⋅Rg=3∣Ia0∣⋅RgGPR = |\mathbf{I}_g| \cdot R_g = 3|\mathbf{I}_{a0}| \cdot R_g

On ungrounded systems (Z0→∞Z_0 \to \infty), the fault current is limited only by distributed line-to-ground capacitance (If≈3IC0I_f \approx 3 I_{C0}), but the voltages of unfaulted phases bb and cc shift from line-to-neutral to full line-to-line magnitude:

Vb,fault=3VLN∠−150∘,Vc,fault=3VLN∠150∘⟹∣Vunfaulted∣=3∣VLN∣=∣VLL∣V_{b,fault} = \sqrt{3} V_{LN} \angle -150^\circ, \qquad V_{c,fault} = \sqrt{3} V_{LN} \angle 150^\circ \quad \Longrightarrow \quad |V_{unfaulted}| = \sqrt{3} |V_{LN}| = |V_{LL}|

3. Line-to-Line (L-L) Fault Analysis

Consider an L-L fault between phases bb and cc through fault impedance ZfZ_f:

Boundary Conditions in Physical Domain

  1. Ia=0\mathbf{I}_a = 0
  2. Ib=−Ic\mathbf{I}_b = -\mathbf{I}_c
  3. Vb−Vc=IbZf\mathbf{V}_b - \mathbf{V}_c = \mathbf{I}_b Z_f

Sequence Domain Transformations

Ia0=13(Ia+Ib+Ic)=13(0+Ib−Ib)=0\mathbf{I}_{a0} = \frac{1}{3}(\mathbf{I}_a + \mathbf{I}_b + \mathbf{I}_c) = \frac{1}{3}(0 + \mathbf{I}_b - \mathbf{I}_b) = 0 Ia1=13(0+aIb−a2Ib)=a−a23Ib=j33Ib=j3Ib\mathbf{I}_{a1} = \frac{1}{3}(0 + a\mathbf{I}_b - a^2\mathbf{I}_b) = \frac{a - a^2}{3}\mathbf{I}_b = \frac{j\sqrt{3}}{3}\mathbf{I}_b = \frac{j}{\sqrt{3}}\mathbf{I}_b Ia2=13(0+a2Ib−aIb)=−Ia1\mathbf{I}_{a2} = \frac{1}{3}(0 + a^2\mathbf{I}_b - a\mathbf{I}_b) = -\mathbf{I}_{a1}

Because Ia0=0\mathbf{I}_{a0} = 0 and Ia1=−Ia2\mathbf{I}_{a1} = -\mathbf{I}_{a2}, the zero-sequence network is completely isolated (open-circuit), and the positive and negative sequence networks are connected in PARALLEL.

Sequence Network Connection for Line-to-Line (L-L) Fault:

      (+) o---(~) V_F ---[ Z_1 ]---+---o
                                   |   |
                                  [Z_f]|
                                   |   |
      (+) o--------------[ Z_2 ]---+---o  (PARALLEL: Pos || Neg)

      (+) o--------------[ Z_0 ]   (OPEN CIRCUIT: I_a0 = 0)

L-L Fault Current Formulas

Ia1=−Ia2=VFZ1+Z2+Zf,Ia0=0\mathbf{I}_{a1} = -\mathbf{I}_{a2} = \frac{\mathbf{V}_F}{\mathbf{Z}_1 + \mathbf{Z}_2 + Z_f}, \qquad \mathbf{I}_{a0} = 0 Ib=−Ic=−j3Ia1=−j3VFZ1+Z2+Zf\mathbf{I}_b = -\mathbf{I}_c = -j\sqrt{3}\mathbf{I}_{a1} = \frac{-j\sqrt{3}\mathbf{V}_F}{\mathbf{Z}_1 + \mathbf{Z}_2 + Z_f} ∣If,LL∣=3∣Ia1∣=3∣VF∣∣Z1+Z2+Zf∣|\mathbf{I}_{f,LL}| = \sqrt{3}|\mathbf{I}_{a1}| = \frac{\sqrt{3}|\mathbf{V}_F|}{|\mathbf{Z}_1 + \mathbf{Z}_2 + Z_f|}

Note

L-L vs. 3-Phase Ratio: If Z1=Z2Z_1 = Z_2 and Zf=0Z_f = 0, the bolted line-to-line fault current is: ∣If,LL∣=3VF2Z1=32(VFZ1)=32If,3ϕ≈0.8660⋅If,3ϕ|\mathbf{I}_{f,LL}| = \frac{\sqrt{3} V_F}{2 Z_1} = \frac{\sqrt{3}}{2} \left( \frac{V_F}{Z_1} \right) = \frac{\sqrt{3}}{2} I_{f,3\phi} \approx 0.8660 \cdot I_{f,3\phi}


4. Double Line-to-Ground (DLG) Fault Analysis

Consider a DLG fault where phases bb and cc contact each other and ground through fault impedance ZfZ_f:

Boundary Conditions in Physical Domain

  1. Ia=0\mathbf{I}_a = 0
  2. Vb=Vc=(Ib+Ic)Zf=IgZf\mathbf{V}_b = \mathbf{V}_c = (\mathbf{I}_b + \mathbf{I}_c) Z_f = \mathbf{I}_g Z_f

Sequence Domain Transformations

Connecting positive, negative, and zero sequence networks in PARALLEL:

Sequence Network Connection for Double Line-to-Ground (DLG) Fault:

               +---[ Z_1 ]---(~) V_F
               |
      (+) o----+---[ Z_2 ]-----------o (-)  (PARALLEL COMBINATION)
               |
               +---[ Z_0 + 3*Z_f ]---o

DLG Fault Current Formulas

Ia1=VFZ1+(Z2(Z0+3Zf)Z2+Z0+3Zf)\mathbf{I}_{a1} = \frac{\mathbf{V}_F}{\mathbf{Z}_1 + \left( \frac{\mathbf{Z}_2 (\mathbf{Z}_0 + 3Z_f)}{\mathbf{Z}_2 + \mathbf{Z}_0 + 3Z_f} \right)}

Using current division to find negative and zero sequence currents:

Ia2=−Ia1(Z0+3ZfZ2+Z0+3Zf),Ia0=−Ia1(Z2Z2+Z0+3Zf)\mathbf{I}_{a2} = -\mathbf{I}_{a1} \left( \frac{\mathbf{Z}_0 + 3Z_f}{\mathbf{Z}_2 + \mathbf{Z}_0 + 3Z_f} \right), \qquad \mathbf{I}_{a0} = -\mathbf{I}_{a1} \left( \frac{\mathbf{Z}_2}{\mathbf{Z}_2 + \mathbf{Z}_0 + 3Z_f} \right)

Total ground return current:

Ig=Ib+Ic=3Ia0=−3Ia1(Z2Z2+Z0+3Zf)\mathbf{I}_g = \mathbf{I}_b + \mathbf{I}_c = 3\mathbf{I}_{a0} = -3\mathbf{I}_{a1} \left( \frac{\mathbf{Z}_2}{\mathbf{Z}_2 + \mathbf{Z}_0 + 3Z_f} \right)

5. Fault Severity Comparison (Z0Z_0 vs. Z1Z_1 Dynamics)

Many engineers intuitively assume that three-phase faults always produce the highest current. However, in solidly grounded transmission substations and near generating stations, the zero-sequence impedance is frequently lower than positive-sequence impedance (Z0<Z1Z_0 < Z_1).

When is SLG Fault Current Greater than 3-Phase Fault Current?

If,SLG=3VFZ1+Z2+Z0>VFZ1=If,3ϕI_{f,SLG} = \frac{3 V_F}{Z_1 + Z_2 + Z_0} > \frac{V_F}{Z_1} = I_{f,3\phi}

Assuming Z1=Z2Z_1 = Z_2:

32Z1+Z0>1Z1  ⟹  3Z1>2Z1+Z0  ⟹  Z0<Z1\frac{3}{2 Z_1 + Z_0} > \frac{1}{Z_1} \implies 3 Z_1 > 2 Z_1 + Z_0 \implies \mathbf{Z}_0 < \mathbf{Z}_1 Fault TypeSequence InterconnectionFault Current Formula (Zf=0)Ratio to I3ϕ (when Z1=Z2=Z0)3-Phase Bolted (3ϕ)Positive Sequence OnlyIf=VFZ11.000Single Line-to-Ground (SLG)Series: Z1+Z2+Z0If=3VFZ1+Z2+Z01.000Line-to-Line (L−L)Parallel: Z1∥Z2If=3VFZ1+Z20.866Double Line-to-Ground (DLG)Parallel: Z1∥Z2∥Z0If=Phase Current: Ib,Ic0.866−1.732\begin{array}{|l|c|c|c|} \hline \textbf{Fault Type} & \textbf{Sequence Interconnection} & \textbf{Fault Current Formula } (Z_f = 0) & \textbf{Ratio to } I_{3\phi} \text{ (when } Z_1 = Z_2 = Z_0) \\ \hline \textbf{3-Phase Bolted } (3\phi) & \text{Positive Sequence Only} & I_f = \frac{V_F}{Z_1} & 1.000 \\ \hline \textbf{Single Line-to-Ground } (SLG) & \text{Series: } Z_1 + Z_2 + Z_0 & I_f = \frac{3 V_F}{Z_1 + Z_2 + Z_0} & 1.000 \\ \hline \textbf{Line-to-Line } (L-L) & \text{Parallel: } Z_1 \parallel Z_2 & I_f = \frac{\sqrt{3} V_F}{Z_1 + Z_2} & 0.866 \\ \hline \textbf{Double Line-to-Ground } (DLG) & \text{Parallel: } Z_1 \parallel Z_2 \parallel Z_0 & I_f = \text{Phase Current: } I_b, I_c & 0.866 - 1.732 \\ \hline \end{array}

6. Comprehensive Worked Calculation: Multi-Fault Analysis

Problem Statement

A 13.8 kV13.8\text{ kV} solidly grounded substation bus has the following Thevenin sequence impedances:

  • Z1=j0.10 pu\mathbf{Z}_1 = j0.10\text{ pu}
  • Z2=j0.10 pu\mathbf{Z}_2 = j0.10\text{ pu}
  • Z0=j0.05 pu\mathbf{Z}_0 = j0.05\text{ pu} (Z0<Z1Z_0 < Z_1 due to proximity of a large solidly grounded Yg−ΔY_g-\Delta generator step-up transformer)
  • System Base: Sbase=100 MVAS_{base} = 100\text{ MVA}, Vbase=13.8 kVV_{base} = 13.8\text{ kV}
  • Prefault Voltage: VF=1.0∠0∘ pu\mathbf{V}_F = 1.0\angle 0^\circ\text{ pu}
  • Fault Impedance: Zf=0Z_f = 0 (bolted faults)

Calculate for all four fault types:

  1. Symmetrical three-phase (3ϕ3\phi) bolted fault current.
  2. Single line-to-ground (SLG) fault current and ground current.
  3. Line-to-line (L-L) fault current.
  4. Double line-to-ground (DLG) sequence currents, phase currents, and total ground return current.
============================== STEP-BY-STEP SOLUTION ==============================

Step 1: Compute System Base Current at 13.8 kV
  I_base = S_base / (sqrt(3) * V_base) = 100,000 kVA / (sqrt(3) * 13.8 kV)
         = 4,183.70 A = 4.1837 kA

Step 2: Symmetrical Three-Phase Fault (3ph)
  I_a1 = V_F / Z_1 = 1.0 / (j0.10) = -j10.00 pu = 10.00 /_ -90 deg pu
  I_f,3ph = 10.00 pu
  Physical Current: I_f,3ph = 10.00 * 4.1837 kA = 41.84 kA

Step 3: Single Line-to-Ground Fault (SLG on Phase a)
  Z_total = Z_1 + Z_2 + Z_0 = j0.10 + j0.10 + j0.05 = j0.25 pu
  I_a0 = I_a1 = I_a2 = V_F / Z_total = 1.0 / (j0.25) = -j4.00 pu = 4.00 /_ -90 deg pu
  
  Total Fault Current in Phase a:
  I_f,SLG = I_a = 3 * I_a0 = 3 * (-j4.00 pu) = -j12.00 pu = 12.00 /_ -90 deg pu
  Physical Current: I_f,SLG = 12.00 * 4.1837 kA = 50.20 kA
  
  >> CRITICAL OBSERVATION: I_SLG (50.20 kA) is 20% LARGER than I_3ph (41.84 kA) 
     because Z_0 (0.05 pu) < Z_1 (0.10 pu)!

Step 4: Line-to-Line Fault (L-L between Phases b and c)
  I_a0 = 0
  I_a1 = -I_a2 = V_F / (Z_1 + Z_2) = 1.0 / (j0.10 + j0.10) = 1.0 / (j0.20)
       = -j5.00 pu = 5.00 /_ -90 deg pu
  
  Fault Current Magnitude:
  |I_f,LL| = sqrt(3) * |I_a1| = sqrt(3) * 5.00 pu = 8.660 pu
  Physical Current: I_f,LL = 8.660 * 4.1837 kA = 36.23 kA
  Check Ratio: I_LL / I_3ph = 36.23 / 41.84 = 0.8660 = sqrt(3)/2  (Exact)

Step 5: Double Line-to-Ground Fault (DLG on Phases b and c)
  Parallel combination of Z_2 and Z_0:
  Z_parallel = (Z_2 * Z_0) / (Z_2 + Z_0) = (j0.10 * j0.05) / (j0.10 + j0.05)
             = -0.005 / (j0.15) = j0.03333 pu
  
  Positive-Sequence Current:
  I_a1 = V_F / (Z_1 + Z_parallel) = 1.0 / (j0.10 + j0.03333) = 1.0 / (j0.13333)
       = -j7.500 pu = 7.500 /_ -90 deg pu
  
  Negative and Zero Sequence Currents (Current Divider):
  I_a2 = -I_a1 * [ Z_0 / (Z_2 + Z_0) ] = -(-j7.500) * [ 0.05 / 0.15 ]
       = j2.500 pu = 2.500 /_ 90 deg pu
  I_a0 = -I_a1 * [ Z_2 / (Z_2 + Z_0) ] = -(-j7.500) * [ 0.10 / 0.15 ]
       = j5.000 pu = 5.000 /_ 90 deg pu
  
  Verify Phase a Current: I_a = I_a0 + I_a1 + I_a2 = j5.0 - j7.5 + j2.5 = 0 pu (Verified)
  
  Phase b and Phase c Fault Currents:
  I_b = I_a0 + (a^2)*I_a1 + a*I_a2
      = j5.0 + (-0.5 - j0.8660)*(-j7.5) + (-0.5 + j0.8660)*(j2.5)
      = j5.0 + (-6.495 + j3.750) + (-2.165 - j1.250)
      = -8.660 + j7.500 pu = 11.456 /_ 140.89 deg pu
  
  |I_b| = |I_c| = 11.456 pu
  Physical Phase Fault Current: I_b = 11.456 * 4.1837 kA = 47.93 kA
  
  Total Ground Return Current:
  I_g = 3 * I_a0 = 3 * (j5.000 pu) = j15.000 pu = 15.000 /_ 90 deg pu
  Physical Ground Current: I_g = 15.000 * 4.1837 kA = 62.76 kA

============================== SUMMARY OF RESULTS ==============================
  - 3-Phase Bolted Fault Current (I_3ph)  = 10.00 pu = 41.84 kA
  - Single Line-to-Ground Current (I_SLG) = 12.00 pu = 50.20 kA  (+20.0% vs 3ph)
  - Line-to-Line Fault Current (I_LL)     =  8.66 pu = 36.23 kA  (-13.4% vs 3ph)
  - DLG Phase Fault Current (|I_b|, |I_c|)= 11.46 pu = 47.93 kA  (+14.6% vs 3ph)
  - DLG Ground Return Current (I_g)       = 15.00 pu = 62.76 kA  (+50.0% vs 3ph)
===================================================================================

7. Common Exam Traps & Strategic Pitfalls

  • The "Factor of 3" Ground Current Omission: Calculating Ia0I_{a0} in an SLG fault and forgetting to multiply by 33 to obtain the physical phase/ground fault current (If=3Ia0I_f = 3 I_{a0}). Relay engineers size ground overcurrent elements (50N/51N) based on 3Ia03 I_{a0}.
  • Assuming Three-Phase Fault Current is Always the Highest: Sizing circuit breakers exclusively for I3ϕI_{3\phi} without checking ISLGI_{SLG}. If Z0<Z1Z_0 < Z_1, the SLG fault produces the maximum interrupting duty.
  • Applying Zero-Sequence Networks to Line-to-Line Faults: Incorrectly including Z0Z_0 in L-L fault calculations. Because the fault does not touch ground and Ib=−IcI_b = -I_c, no zero-sequence current can flow (Ia0=0I_{a0} = 0).
  • Confusing Fault Impedance Factor 3Zf3Z_f with ZfZ_f: In SLG and DLG sequence networks, the physical fault impedance to ground ZfZ_f must be multiplied by 33 in the zero-sequence branch (3Zf3Z_f) because 3Ia03I_{a0} flows through the neutral ground path.
Loading diagram...
Sequence Network Interconnection and Severity Decision Tree
Test Your Knowledge

In a 3-phase power system, which fault type produces boundary conditions that require the positive-sequence, negative-sequence, and zero-sequence networks to be connected strictly in series?

A

Three-Phase Symmetrical Bolted Fault

B

Single Line-to-Ground (SLG) Fault

C

Line-to-Line (L-L) Fault

D

Double Line-to-Ground (DLG) Fault

Test Your Knowledge

A 13.8 kV solidly grounded substation bus has sequence impedances Z1 = j0.12 pu, Z2 = j0.12 pu, and Z0 = j0.06 pu. For a bolted line-to-line (L-L) fault between phases b and c, what is the fault current magnitude |I_f| in per-unit?

A

4.17 pu

B

5.00 pu

C

7.22 pu

D

8.33 pu

Test Your Knowledge

Under what system impedance condition does a bolted Single Line-to-Ground (SLG) fault produce a higher short-circuit current magnitude than a bolted Three-Phase (3-phase) symmetrical fault at the same bus?

A

When the zero-sequence Thevenin impedance is strictly less than the positive-sequence Thevenin impedance (Z0 < Z1), assuming Z1 = Z2.

B

When the system is ungrounded or grounded through a high-resistance grounding (HRG) neutral resistor.

C

When the negative-sequence impedance is significantly larger than the positive-sequence impedance (Z2 >> Z1).

D

When the fault occurs through a high fault impedance (Zf > 1.0 pu).

Sections you finish are checked off in the contents.