Cheat sheet

ICC Fire Inspector I Cheat Sheet

Quick Facts

ICC exam
66 · National Certification
Questions
60 multiple-choice
Time limit
2 hours
Format
Open book
Passing score
75 scaled
Code editions offered
2021 and 2024
Code books
IFC and IBC, selected edition
IFSTA manual
Fire Inspection & Code Enforcement, 9th
Delivery
PRONTO in-person or remote
Digital exam references
IFC and IBC

Inspection Report Memory

Where, what, code, correction, follow-up

Exact locationObserved conditionApplicable provisionCorrection record

Operational vs Construction Permit

Operational permit

  • Regulated activity or operation
  • IFC §105.5

Construction permit

  • Installation or modification scope
  • IFC §105.6

Check both permit categories

Inspection Response Picker

  1. New regulated operation proposed→Check operational permit triggers(IFC §105.5)
  2. System installation or alteration planned→Check construction permit triggers(IFC §105.6)
  3. Permit work requires plans→Review construction document requirements(IFC §106)
  4. Access refused→Follow lawful entry process(IFC §104.4)
  5. Violation observed→Record facts and cite requirement(Use written notice procedure)
  6. Interpretation formally disputed→Follow local appeal procedure(IFC §112)

Permits and Plans

Operational permit
Regulates listed activities and operationsIFC §105.5
Construction permit
Covers listed installations or alterationsIFC §105.6
Construction documents
Review scope and required detailsIFC §106
Plan revision
Review changes through approval processIFC §106
Field comparison
Use latest approved drawingsIFC §109
Code research
Check adoption, scope, referenced standards

Inspection and Enforcement

Complaint intake
Record allegation and exact location
Right of entry
Request lawful accessIFC §104.4
Inspection report
Record condition, location, code basis
Inspection records
Retain findings and follow-upIFC §104.7
Violation notice
Document required correctionIFC §113
Reinspection
Verify and record correction
Appeal
Route disputed interpretation through processIFC §112
Legal testimony
Use factual observations and records
Public inquiry
Explain requirement and applicable citation

Egress Sequence

Access → Exit → Discharge

Approach the exitUse the protected portionContinue toward public way

Common Path vs Travel Distance

Common path

  • Ends at route choice
  • IFC §1006.2.1

Exit access travel distance

  • Ends at an exit
  • IFC §1017

Measure to the correct endpoint

Egress Lookup Picker

  1. Single path before a choice→Check common path limit(IFC §1006.2.1)
  2. Farthest point to exit→Measure exit access travel(IFC §1017)
  3. Exit number in question→Check space and story rules(IFC §1006)
  4. Exit door difficult to open→Check operation and locking rules(IFC §1010)
  5. Emergency lighting in question→Check illumination requirements(IFC §1008)
  6. Stock blocks required route→Check egress maintenance(IFC §1032)

Means of Egress

Exit access
Travel leading to an exit
Exit
Protected path to exit discharge
Exit discharge
Exit termination to public way
Common path
Travel before two distinct routesIFC §1006.2.1
Exit access travel distance
Measure along path to exitIFC §1017
Egress capacity
Load × applicable capacity factorIFC §1005
Stairway base capacity factor
0.3 in. per occupantIFC §1005.3.1
Other egress base capacity factor
0.2 in. per occupantIFC §1005.3.2
Exit count
Check space and story rulesIFC §1006
Exit separation
Check required remotenessIFC §1007
Egress lighting
Check normal and emergency illuminationIFC §1008
Door operation
Check locks, latches, panic hardwareIFC §1010
Exit signs
Verify required locations and visibilityIFC §1013
Existing egress upkeep
Keep required routes clearIFC §1032

Acceptance vs Ongoing Maintenance

Acceptance

  • New installation performance
  • IFC §901.5

Ongoing maintenance

  • Existing system reliability
  • IFC §901.6

Match evidence to inspection purpose

System and Preparedness Picker

  1. New system installation complete→Verify required acceptance testing(IFC §901.5)
  2. Equipment differs from approved plan→Document and resolve discrepancy(Compare approved revisions)
  3. Existing system service uncertain→Check condition and maintenance records(IFC §901.6)
  4. Required system out of service→Follow impairment notification procedures(IFC §901.7)
  5. Tested water supply in question→Review flow and pressure data(IFC §507)
  6. Need to determine plan applicability→Check occupancy-based requirements(IFC §403)
  7. Required drill history uncertain→Check drill records and frequency(IFC §405)

Fire Protection Lookup

Sprinklers
Automatic fire suppressionIFC §903
Other extinguishing systems
Special-agent or application-specific protectionIFC §904
Standpipes
Water through hose connectionsIFC §905
Portable extinguishers
Check hazard, rating, placementIFC §906
Fire alarm and detection
Initiation, notification and system controlsIFC §907
Smoke control
Manage smoke movementIFC §909
Fire department connection
Fire service supplies system waterIFC §912
Fire pump
Provides required system pressureIFC §913
Existing building requirements
Check specific retrofit triggersIFC Ch. 11

Supervisory vs Trouble Signal

Supervisory

  • Monitored condition off normal
  • Example: valve position change

Trouble

  • System fault indication
  • Example: circuit fault

Identify the initiating condition

System Readiness

Approved system plan
Match installed equipment and layout
Acceptance test
Verify installation performanceIFC §901.5
Ongoing readiness
Review inspection, testing, maintenance recordsIFC §901.6
Sprinkler control valve
Verify normal open positionIFC §903.4
Sprinkler supervisory signal
Investigate off-normal monitored condition
Alarm trouble signal
Investigate system fault
Alarm notification appliance
Warn occupants audibly or visiblyIFC §907.5
System impairment
Notify and follow impairment proceduresIFC §901.7
Impairment response
Fire watch or evacuation, as directedIFC §901.7

Fire Service Access and Water

Apparatus route
Check access, clearance, obstructionsIFC §503
Premises identification
Verify visible address numbersIFC §505
Key box
Check required responder accessIFC §506
Water supply
Verify available fire protection supplyIFC §507
Water supply test
Review approved test resultsIFC §507.4
Static pressure
Pressure before test flow
Residual pressure
Pressure during test flow
Hydrant access
Keep approach and clearance openIFC §507.5
Fire-flow benchmarks
Check locally adopted requirementsIFC App. B

Emergency Preparedness

Plan applicability
Identify occupancy and triggerIFC §403
Evacuation plan
Routes, evacuation roles, occupant accountingIFC §404
Fire safety plan
Hazards, safeguards and response assignmentsIFC §404
Evacuation drills
Check frequency and participationIFC §405
Drill records
Check date, participants and resultsIFC §405
Employee training
Prevention and emergency dutiesIFC §406
Hazardous field condition
Document and escalate under authority

Construction Types

Types I and II
Generally noncombustible listed elementsIBC §602.2
Type III
Generally noncombustible exterior wallsIBC §602.3
Type IV
Mass timber or noncombustible elementsIBC §602.4
Type V
Code-permitted structural materialsIBC §602.5
Element fire-resistance ratings
Check type and subtypeIBC Table 601
Height and area
Check use, type, sprinkler protectionIBC Ch. 5
Fire-resistance features
Verify barrier openings and penetrationsIFC Ch. 7

Occupant Load Memory

Function picks factor, area supplies numerator

Match gross or netCount fixed seats separately

Gross vs Net Floor Area

Gross

  • Generally includes accessory circulation
  • Use gross factor where listed

Net

  • Actual occupied area
  • Excludes unoccupied accessory areas

Use the table's area basis

Occupancy Inspection Picker

  1. Tenant activity has changed→Reevaluate occupancy and approvals(IBC Ch. 3)
  2. Multiple uses share building→Check mixed-occupancy provisions(IBC §508)
  3. Area without fixed seats→Divide area by function factor(Use specified gross or net)
  4. Individual fixed seats installed→Count installed seats(Include applicable unseated areas)
  5. Assembly load sign missing→Check posting requirement(IFC §1004.9)
  6. Need occupancy-specific protection→Check applicable sprinkler and alarm triggers(IFC §§903, 907)

Occupancy Groups

Group A
AssemblyIBC §303
Group B
BusinessIBC §304
Group E
EducationalIBC §305
Group F
Factory and industrialIBC §306
Group H
High hazardIBC §307
Group I
InstitutionalIBC §308
Group M
MercantileIBC §309
Group R
ResidentialIBC §310
Group S
StorageIBC §311
Group U
Utility and miscellaneousIBC §312
Mixed occupancies
Check accessory, nonseparated, separated provisionsIBC §508

Occupancy vs Construction Type

Occupancy group

  • Use and associated hazards
  • IBC Chapter 3

Construction type

  • Materials and element ratings
  • IBC Chapter 6

Classify both before applying limits

Occupant Load

Classification input
Actual use and activities
Area-based load
Applicable floor area ÷ factorIFC §1004.5
Factor lookup
Match function and area basisIFC Table 1004.5
Assembly chairs only, unfixed
7 net ft² per occupantIFC Table 1004.5
Assembly tables and chairs
15 net ft² per occupantIFC Table 1004.5
Tables and chairs example
300 ÷ 15 = 20 occupants300 ft² net
Fixed seating
Seats plus applicable unseated loadIFC §1004.6
Bench seating without divisions
One person per 18 inchesIFC §1004.6
Booth seating
One person per 24 inchesIFC §1004.6
Intervening egress route
Account for combined occupant loadsIFC §1004.2
Assembly capacity sign
Verify required occupant-load postingIFC §1004.9

Hazard Quantity Memory

Hazard, amount, activity, area

Identify hazard classInventory quantityStorage or useCheck each control area

Storage vs Use

Storage

  • Materials held for later use
  • Check storage column

Use

  • Materials handled in process
  • Select open or closed use

Check aggregate limits and footnotes

Hazards Lookup Picker

  1. Torch cutting proposed→Check hot work safeguards(IFC Ch. 35)
  2. Spray operation observed→Check spray finishing requirements(IFC Ch. 24)
  3. Tall racks of combustibles→Check high-piled storage applicability(IFC Ch. 32)
  4. Hazardous materials being dispensed→Identify open or closed use(Select quantity column)
  5. Inventory exceeds applicable limit→Check high-hazard classification(Verify adjustments and exceptions)
  6. Wall finish replaced→Check permitted finish classification(IFC §803)

Process and Storage Lookup

Commercial cooking
Extinguishing protection and hood upkeepIFC §§606, 904.14
Spray finishing
Check ventilation and ignition controlIFC Ch. 24
High-piled combustible storage
Check commodity, arrangement and protectionIFC Ch. 32
Welding and other hot work
Check permit applicability and safeguardsIFC Ch. 35
Compressed gas cylinders
Check securement and valve protectionIFC Ch. 53
Flammable and combustible liquids
Check classification, storage, dispensingIFC Ch. 57
Combustible waste
Control accumulation and disposalIFC §304

Hazardous Material Quantities

Hazard inventory
Identify material, hazard class, quantity
Safety data sheet
Confirm hazards and incompatibilitiesIFC §407
Maximum allowable quantity
Compare by hazard and conditionIFC §5003.1.1
Control area
Protected area with quantity limits
Physical versus health hazards
Use applicable hazard tables
Quantity columns
Storage, closed use, open use
Quantity adjustments
Read qualifying footnotes and exceptions
Above applicable limits
Evaluate Group H and exceptionsIBC §307
Incompatible materials
Check required separationIFC §5003

Finishes and Fire Growth

Wall and ceiling finish
Check occupancy and finish locationIFC §803
Finish documentation
Verify applicable test classification
Flame spread index
Relative surface flame propagation
Smoke-developed index
Relative smoke generation in test
Floor finishes
Check separate finish criteriaIFC §804
Decorations
Check material and placement rulesIFC §§806–807
Fire growth potential
Assess fuel load and arrangement
Blocked protection
Check storage against required clearances

Common Traps

Passing score

75 scaled ≠ 75 percent correct

Inspection history

Complaint allegation ≠ Observed violation

System condition

Installed equipment ≠ Operationally ready equipment

Water supply

Static pressure before flow ≠ Residual pressure under flow

Occupancy assignment

Tenant business name ≠ Actual use of space

Fixed seats

Installed seat count ≠ Loose seating area factor

Hazard quantities

Control area quantity ≠ Building-wide inventory total

Material performance

Finish flame spread index ≠ Assembly fire-resistance rating

Last Minute

  1. 1.Match books to registered edition
  2. 2.Leave study sheets outside exam
  3. 3.Use adopted code in field
  4. 4.Record observation, location, code citation
  5. 5.Trace access, exit, discharge
  6. 6.Verify routes remain unobstructed
  7. 7.Compare installed systems with approved plans
  8. 8.Check maintenance and impairment records
  9. 9.Check plan triggers and drill logs
  10. 10.Classify actual building use
  11. 11.Match load factor to function
  12. 12.Check storage, open-use, closed-use limits
Same family resources

Explore More ICC Certifications

Continue into nearby exams from the same family. Each card keeps practice questions, study guides, flashcards, videos, and articles in one place.