Career upgrade: Learn practical AI skills for better jobs and higher pay.
Level up
Cheat sheet

ICC E1 Residential Electrical Inspector Cheat Sheet

General Requirements

10%of exam

IRC Part VIII MapClearancesWorking SpaceSplicesDefinitions

Services

17%of exam

Service Load CalcService ConductorsDisconnectsGrounding ElectrodeBonding

Branch Circuits + Feeders

28%of exam

Required CircuitsReceptacle SpacingConductor AmpacityOvercurrentFeeders

Wiring Methods + Distribution

21%of exam

GFCI LocationsAFCI LocationsBox FillCable SupportEquipment Ground

Devices, Lighting, Appliances

19%of exam

Lighting OutletsCloset LuminairesTamper-ResistantAppliance CircuitsWet Location

Swimming Pools

5%of exam

Equipotential BondingPool GFCIUnderwater LuminairesPool ClearancesPool Receptacles

Quick Facts

Exam
ICC E1
Credential
Residential Electrical Inspector
Questions
60 multiple-choice
Time
2 hours
Pass
Scaled 75 (~45/60)
Format
Open-book
Fee
$199-$249
Validity
3 years (1.5 CEUs)
Reference
2024 IRC Chs. 34-43

IRC Electrical Spine

34 General, 36 Service, 37 Branch

Ch. 34: generalCh. 36: servicesCh. 37: branch/feederCh. 38-43: methods

IRC Part VIII Map

Ch. 34
General requirements
Ch. 35
Definitions
Ch. 36
Services
Ch. 37
Branch/feederHeaviest
Ch. 38-39
Wiring methods
Ch. 40-42
Devices/appliances
Ch. 43
Class 2, low-voltage

Clearances + Working Space

Panel depth
36 in working space
Panel width
30 in front
Headroom
6 ft 6 in
Service over roof
8 ft typical
Over driveway
12 ft (residential)
Over public road
18 ft
Above grade
10 ft min

General Rules

Splices
Approved devices/connectors
Splice location
Inside accessible box
Made electrode GEC
6 AWG copper max
Conductor material
Copper or aluminum
Ampacity basis
60/75°C terminals
Identification
Grounded = white/gray

Grounding vs Bonding

Grounding

  • Earth connection
  • GEC to electrode
  • Stabilize voltage

Bonding

  • Joins metal parts
  • Fault current path
  • EGC continuity

To earth vs together

Grounding Electrode Picker

  1. Concrete footing rebarUfer/CEE(Preferred)
  2. Metal water pipeBond + electrode(Within 5 ft)
  3. Ground rod onlyTwo rods(Unless 25 ohm)
  4. Made electrode GEC6 AWG copper(Max needed)
  5. Service enclosureMain bonding jumper(Neutral-to-can)
  6. SubpanelSeparate EGC bus(No N-G bond)

Service Load Calc

General lighting
3 VA per sq ft
Small appliance
1500 VA x 2
Laundry
1500 VA circuit
First 3000 VA
100% demand factor
3001-120,000 VA
35% demand factor
Range
Table demand factor
Dryer
5000 VA or nameplate
Largest motor
Add 25%

Neutral vs EGC

Grounded (neutral)

  • Carries current
  • White/gray
  • Insulated

EGC

  • No normal current
  • Green/bare
  • Fault path

Current vs fault only

Service Equipment

Min service rating
100 A dwelling
200 A copper SE
2/0 AWG typical
Max disconnects
Up to 6 motions
Disconnect location
Readily accessible
SE conductor sizing
Per dwelling table
Grounded conductor
Sized to GEC

Grounding + Bonding

GEC
To grounding electrode
EGC
Equipment fault path
Grounded conductor
Neutral, current-carrying
Main bonding jumper
Neutral-to-enclosure (service)
Ground rod
8 ft, two if needed
Ufer/CEE
Concrete-encased electrode
Metal water pipe
Bond within 5 ft
Neutral-ground bond
Service only, once

Required 20 A Circuits

Two SA, one Laundry, one Bath

2x small-appliance1x laundry1x bathroomPlus dedicated appliances

Service vs Feeder

Service

  • Utility supply
  • Neutral bonded
  • Before disconnect

Feeder

  • Between panels
  • Neutral isolated
  • Has EGC

Source vs distribution

Service vs Feeder vs Branch

  1. Utility to disconnectService conductors(Calc load)
  2. Panel to subpanelFeeder(EGC + neutral)
  3. Last OCPD to outletBranch circuit(Rated amps)
  4. Sizing dwelling serviceStandard calc(IRC E3602)
  5. 14 AWG copper15 A max(Lighting OK)
  6. 12 AWG copper20 A max(Recep./SA)
  7. Subpanel neutralIsolated(No bond)
  8. Service neutralBonded(Main jumper)

Required Branch Circuits

Small-appliance
Two 20 A min
Laundry
One 20 A
Bathroom
One 20 A
Dishwasher
Individual circuit
Disposal
Individual circuit
HVAC
Per nameplate
Range
Dedicated 240 V

Wire to Breaker

14=15, 12=20, 10=30

14 AWG: 15 A12 AWG: 20 A10 AWG: 30 ACopper, 60°C

Receptacle Spacing

Wall rule
12 ft max spacing
From opening
6 ft max
Wall width
2 ft or wider counts
Kitchen counter
4 ft max apart
Counter island
Min one receptacle
Hallway 10 ft+
One receptacle
Bathroom
Within 3 ft of basin

Conductor + OCPD

14 AWG Cu
15 A breaker
12 AWG Cu
20 A breaker
10 AWG Cu
30 A breaker
8 AWG Cu
40 A
6 AWG Cu
55 A (60°C)
Continuous load
Max 80% rating
Fastened appliance
Max 50% on shared

GFCI Locations

Bad Girls Often Kiss Boys Causing Laughter

BathroomGarageOutdoorKitchenBasementCrawl spaceLaundry

GFCI vs AFCI

GFCI

  • Shock protection
  • Wet/grounded areas
  • Trips ~5 mA

AFCI

  • Arc-fault/fire
  • Living areas
  • Detects arcing

Shock vs fire

GFCI vs AFCI Required

  1. Bathroom receptacleGFCI(Not AFCI)
  2. Bedroom circuitAFCI(All outlets)
  3. Kitchen counter recep.Both(GFCI + AFCI)
  4. Garage receptacleGFCI(All)
  5. Outdoor receptacleGFCI(Wet rated)
  6. Within 6 ft of sinkGFCI(Any sink)
  7. Unfinished basementGFCI(All recep.)
  8. Living room circuitAFCI(All outlets)

GFCI-Required Locations

Bathrooms
All receptacles
Garages
All receptacles
Outdoors
All receptacles
Kitchens
Counter-serving receptacles
Within 6 ft sink
GFCI required
Unfinished basement
All receptacles
Crawl spaces
At/below grade
Laundry areas
All receptacles

Box Fill Volumes

14=2.0, 12=2.25, 10=2.5

Device yoke: x2Clamps: x1Grounds: x1Largest conductor

AFCI-Required Areas

Scope
120 V, 15/20 A circuits
Bedrooms
AFCI required
Living/family rooms
AFCI required
Kitchens
AFCI required
Hallways/closets
AFCI required
Laundry areas
AFCI required
Bathrooms
Not AFCI required

Box Fill Volume

14 AWG
2.00 cu in each
12 AWG
2.25 cu in each
10 AWG
2.50 cu in each
Internal clamps
One conductor allowance
Each device yoke
Two (largest) allowances
Equipment grounds
One allowance total
Pigtail
Not counted

Cable + Support

NM cable
Dry interior, dwelling
NM support
Within 12 in box
NM staple
Every 4.5 ft
Bored holes
1.25 in from edge
Protect plate
Steel where <1.25 in
EGC required
Metal enclosures bonded

Tamper vs Weather Resistant

Tamper-resistant

  • Shutter mechanism
  • Child safety
  • Dwelling interior

Weather-resistant

  • Corrosion rated
  • Damp/wet
  • Outdoor use

Kids vs weather

Required Lighting

Habitable rooms
Switched lighting outlet
Bathrooms/halls
Switched lighting outlet
Stairways
Switched both ends
Outdoor entrances
Switched lighting outlet
Attic/crawl w/ equip
Light at access
Garage
Switched lighting outlet

Damp vs Wet Location

Damp

  • Protected outdoor
  • Under eave
  • Listed damp

Wet

  • Direct exposure
  • In-use cover
  • Listed wet

Sheltered vs exposed

Luminaires + Wet

Closet surface incand.
12 in clearance
Closet recessed
6 in clearance
Closet LED/fluor.
6 in surface
Open lamp closet
Not permitted
Wet location fixture
Listed wet location
Damp location
Listed damp minimum

Receptacles + Devices

Tamper-resistant
Dwelling 15/20 A
Weather-resistant
Damp/wet outdoor
Outdoor in-use cover
Wet location
Receptacle grounding
EGC connected
Switch in wet box
Weatherproof enclosure
Faceplate
Cover finished opening

Pool Equipotential Bond

Bonding conductor
8 AWG solid copper
Bonded parts
Shell, deck, equipment
Perimeter surface
Within 3 ft bonded
Pump motor
Bonded to grid
Metal fittings
Bonded together
Purpose
Reduce voltage gradient

Pool GFCI + Clearances

Pump receptacle
GFCI protected
Within 20 ft
GFCI receptacles
Receptacle distance
Min 6 ft from wall
Underwater luminaire
GFCI if >15 V
Wet-niche max
150 V to ground
Overhead conductors
22.5 ft over water

Common Traps

GFCI vs AFCI scope

GFCI = shock/wet AFCI = arc/living areas

Bathroom protection

GFCI required AFCI not required

Neutral vs ground bond

Bonded at service only Isolated at subpanel

Grounding vs bonding

Grounding to earth Bonding joins metal

Wall vs counter spacing

Wall: 12 ft / 6 ft Counter: 4 ft / 2 ft

Code reference

E1 uses IRC Not standalone NEC

TR vs WR receptacle

TR = shutters WR = weather rated

Last Minute

  1. 1.E1 = 60 Q, 2 hr, open-book
  2. 2.Pass = scaled 75, ~45/60
  3. 3.Reference 2024 IRC Chs. 34-43
  4. 4.Heaviest domain: branch circuits 28%
  5. 5.GFCI: bath, garage, outdoor, kitchen
  6. 6.GFCI within 6 ft of sink
  7. 7.AFCI: bedrooms, living, kitchen
  8. 8.Bathroom GFCI yes, AFCI no
  9. 9.Required circuits: 2 SA, 1 bath
  10. 10.Wall receptacle 12 ft spacing
  11. 11.Kitchen counter: 4 ft max apart
  12. 12.Copper wire: 14=15A, 12=20A
  13. 13.Box fill 14 AWG = 2.0
  14. 14.Device yoke counts as two
  15. 15.Pool bond: 8 AWG solid copper
  16. 16.Neutral-ground bonded service only
  17. 17.Min dwelling service 100 A
Same family resources

Explore More ICC Certifications

Continue into nearby exams from the same family. Each card keeps practice questions, study guides, flashcards, videos, and articles in one place.