6.7 Construction Trades and Specialties: Plumbing, Plastics, Doors and Windows, Finishes, and Electrical
Key Takeaways
Every plumbing fixture needs a trap with a water seal, and a vent system that keeps the seal from being siphoned.
CPVC and PPR pipes are rated for hot water, while ordinary uPVC is used for cold water and drainage.
Tempered glass breaks into small blunt pieces, while laminated glass is held together by its interlayer when broken.
Paint systems are applied as surface preparation, primer, intermediate coats and finish, each compatible with the substrate.
Branch-circuit conductors are sized for at least 125% of continuous load and protected by a circuit breaker matched to the conductor ampacity.
6.7 Construction Trades and Specialties: Plumbing, Plastics, Doors and Windows, Finishes, and Electrical
The AMSTHC TOS area "Construction Trades and Specialties" has five one-item competencies:
- Recall basic plumbing design, construction and installation.
- Classify and determine plastics for construction.
- Select details of doors and windows for proper application.
- Identify and select finishing materials.
- Understand basic electrical design, construction and installation.
Civil engineers coordinate these trades and are expected to know their vocabulary and basic rules. The governing codes are:
- the National Plumbing Code of the Philippines, under the Plumbing Law (RA 1378);
- the Philippine Electrical Code (PEC Part 1, under the Electrical Engineering Law, RA 7920);
- the Fire Code (RA 9514) for fire-rated doors.
Plumbing Basics
| System | Components | Key rules |
|---|---|---|
| Water supply | Service connection, water meter, gate valves, risers, branches, storage tank, booster pump | Size pipes for peak demand and residual pressure; prevent backflow with air gaps or check valves |
| Drainage (sanitary) | Fixture drains, traps, branch drains, soil and waste stacks, building drain and sewer | Grade horizontal drains at about 2% (1:50) for small pipes; provide cleanouts at changes of direction |
| Venting | Vent pipes from fixture traps to the vent stack and roof | Keeps air pressure balanced so trap seals are not siphoned or blown out |
| Storm drainage | Gutters, downspouts, catch basins | Kept separate from sanitary drainage |
| Private disposal | Septic tank with leaching field | Sized for population; two compartments; watertight |
Traps. A P-trap holds a water seal, typically about 50 to 100 mm deep, that blocks sewer gas. Seal loss is caused by siphonage (inadequate venting), evaporation (unused fixtures) and back-pressure.
Drainage fixture units express the relative discharge load of fixtures; pipe sizes are chosen from code tables based on total fixture units.
Common pipe materials:
- uPVC for cold water, drainage and vents;
- CPVC or PPR for hot water;
- galvanized iron (older systems);
- copper;
- HDPE for service lines and underground mains.
Plastics in Construction
| Plastic | Main uses | Notes |
|---|---|---|
| PVC / uPVC (polyvinyl chloride) | Cold water and drainage pipes, electrical conduit, window frames | Rigid; joined by solvent cement; not for hot water |
| CPVC (chlorinated PVC) | Hot and cold water pipes | Higher temperature rating than PVC |
| PPR (polypropylene random copolymer) | Hot and cold water | Joined by heat fusion, giving leak-free joints |
| PE / HDPE (polyethylene) | Water mains, gas lines, geomembranes, vapor barriers | Flexible and tough; butt- or electro-fusion joints |
| Polycarbonate | Skylights, roofing sheets | High impact strength; needs UV protection |
| Acrylic (PMMA) | Glazing, signage | Clear, but scratches more easily |
| Fiber-reinforced plastic (FRP) | Tanks, gratings, strengthening wraps for concrete | High strength-to-weight ratio; corrosion resistant |
| Expanded and extruded polystyrene | Insulation, lightweight fill | Combustible; must be protected |
Thermoplastics (PVC, PE, PP) soften when heated and can be reshaped or welded. Thermosets (epoxy, polyester, phenolic) cure permanently. Plastics expand far more with temperature than steel, so long runs need expansion allowances. Many degrade in sunlight unless UV-stabilized.
Doors and Windows
Door parts:
- the frame or jamb (head and side jambs, with a threshold at the floor);
- the leaf or shutter;
- the stop;
- the hardware: hinges, lockset, closer, panic bar.
Window parts:
- the frame (head, jambs, sill);
- the sash;
- mullions (vertical dividers) and transoms (horizontal dividers);
- glazing.
| Type | Typical application |
|---|---|
| Swing (hinged) door | Rooms, exits; exit doors swing in the direction of travel |
| Sliding door or window | Limited swing space |
| Folding or accordion door | Wide openings |
| Casement window (side-hinged) | Good ventilation, tight seal |
| Awning (top-hinged) or jalousie window | Ventilation in rain; jalousies are common in tropical houses |
| Fire door (labeled, self-closing) | Exit stairs, rated walls under the Fire Code |
Glazing options:
- Annealed float glass is the basic type and breaks into sharp shards.
- Tempered glass is about four to five times stronger and breaks into small blunt pieces. It is required in hazardous locations such as doors and low panels.
- Laminated glass keeps its interlayer intact when broken; it is used in overhead and security glazing.
- Insulating glass units improve thermal performance.
Aluminum and uPVC frames resist rot. Wood needs treatment and finishing. All windows need proper sill slope and flashing to shed water.
Finishing Materials
| Element | Common materials | Selection points |
|---|---|---|
| Walls | Cement plaster with paint; ceramic tiles; stone; wall panels | Moisture exposure, cleanability, impact |
| Floors | Ceramic or porcelain tiles, granite, terrazzo, vinyl, epoxy, polished concrete, wood | Abrasion, slip resistance (wet areas), loads, maintenance |
| Ceilings | Gypsum board, fiber-cement board, acoustic tiles on metal grid | Fire rating, humidity, acoustics |
| Roofing | Pre-painted metal sheets, tiles, waterproofing membranes for flat roofs | Slope, wind uplift, corrosion |
| Waterproofing | Cementitious coatings, bituminous or liquid membranes | Toilets, roof decks, basements, water tanks |
Paint systems follow a sequence: surface preparation (clean and repair; let new concrete or plaster cure and dry), primer or sealer, putty or skim coat where needed, then two or more finish coats. Alkali-resistant primers are used on new masonry. Epoxy or polyurethane systems are used for chemical or heavy-wear areas.
Basic Electrical Design and Installation
The Philippine Electrical Code (PEC Part 1) governs building wiring. Houses are typically served at a nominal 220–230 V single-phase, and larger buildings by three-phase services.
| Concept | Rule of practice |
|---|---|
| Power | for single-phase loads ( is the power factor) |
| Branch circuits | Separate circuits for lighting, convenience outlets and large appliances (air conditioners, water heaters) |
| Conductor sizing | Ampacity at least the load current, and at least 125% of continuous loads |
| Overcurrent protection | Circuit breaker rating not exceeding the conductor ampacity |
| Voltage drop | Commonly limited to about 3% in a branch circuit and 5% overall |
| Grounding and bonding | Equipment grounding conductor to every outlet and metal enclosure |
| Raceways | Rigid steel, intermediate metal, EMT, or PVC conduit with boxes and fittings |
Example. A air conditioner on with power factor draws . Treated as a continuous load, the circuit needs of conductor capacity. The conductor size and breaker rating are then selected from the PEC ampacity tables for the insulation type and installation method.
Why is a vent connected to the drainage pipe downstream of each plumbing fixture trap?
To replace the need for a trap
To let rainwater enter the sanitary system
To keep air pressure balanced so the trap's water seal is not siphoned or blown out
To increase water pressure at the fixture
Which glass should be specified for a full-height glass door because it breaks into small, relatively harmless pieces?
Tempered glass
Wired annealed glass
Tinted float glass
Annealed float glass
A 230-V single-phase water heater draws 18 A continuously. What minimum conductor capacity is required for the branch circuit?
20.7 A
18.0 A
22.5 A
36.0 A