13.3 Vapour Compression & Vapour Absorption Refrigeration Systems

Key Takeaways

  • The standard Vapour Compression Refrigeration System (VCRS) operates on four state changes: isentropic compression (1-2), isobaric condensation (2-3), isenthalpic throttling expansion (3-4, h3=h4), and isobaric evaporation (4-1), with COP = (h1-h4)/(h2-h1).

  • Operating conditions dictate performance: liquid subcooling at condenser exit always increases refrigeration effect RE and COP; suction vapor superheating in evaporator increases RE but also compressor work Wc; decreasing evaporator temperature drastically reduces COP and increases compressor displacement volume.

  • One Ton of Refrigeration (1 TR) is defined as the heat extraction rate of 3.517 kW (210 kJ/min or 12,000 Btu/hr), equivalent to the latent heat rate required to freeze 1 short ton of water at 0°C into ice at 0°C in 24 hours.

  • Multi-stage compression with intermediate flash chambers and intercooling minimizes power consumption and prevents excessive discharge temperatures when total pressure ratio r_p > 6 to 8, with optimum intermediate pressure P_i = sqrt(P_e * P_c).

  • Vapour Absorption Systems (VARS) replace the mechanical compressor with an absorber, solution pump, and generator to utilize low-grade thermal energy; maximum theoretical COP equals eta_Carnot_HE * COP_Carnot_Refrig = [(T_g - T_a)/T_g] * [T_e/(T_a - T_e)].

Last updated: August 2026

Vapour Compression & Vapour Absorption Refrigeration Systems

Refrigeration is the process of removing thermal energy from a low-temperature reservoir and discharging it to a higher-temperature reservoir through the input of mechanical or thermal work. In modern industrial mining operations, massive refrigeration systems provide chilling for underground mine ventilation air (counteracting rock geothermal gradients and equipment heat loads), industrial chiller plants for heavy equipment lubricants, and cooling systems in Coal Handling Plants (CHP).


1. Thermodynamic Fundamentals & The Ton of Refrigeration

A refrigerator operates on a reversed thermodynamic cycle. The performance index is the Coefficient of Performance (COP):

COPRef=Desired Refrigerating Effect (QL)Net Work Input (Wnet)=QLQH−QL\text{COP}_{\text{Ref}} = \frac{\text{Desired Refrigerating Effect } (Q_L)}{\text{Net Work Input } (W_{\text{net}})} = \frac{Q_L}{Q_H - Q_L}

For a Reversed Carnot Cycle operating between low temperature TLT_L and high temperature THT_H (in Kelvin):

COPCarnot, Ref=TLTH−TL\text{COP}_{\text{Carnot, Ref}} = \frac{T_L}{T_H - T_L} COPCarnot, Heat Pump=THTH−TL=COPCarnot, Ref+1\text{COP}_{\text{Carnot, Heat Pump}} = \frac{T_H}{T_H - T_L} = \text{COP}_{\text{Carnot, Ref}} + 1

The Ton of Refrigeration (TR)

The commercial unit of cooling capacity is the Ton of Refrigeration (TR), defined as the steady rate of heat removal required to freeze 1 short ton (2000 lb=907.185 kg2000\text{ lb} = 907.185\text{ kg}) of pure water at 0∘C0^{\circ}\text{C} into ice at 0∘C0^{\circ}\text{C} in exactly 24 hours:

Latent heat of fusion of ice hsf=333.55 kJ/kg\text{Latent heat of fusion of ice } h_{sf} = 333.55 \ \text{kJ/kg} 1 TR=907.185 kg×333.55 kJ/kg24×3600 s=302,601 kJ86,400 s=3.502 kW(Standard Definition: 3.51685≈3.517 kW)1 \ \text{TR} = \frac{907.185 \ \text{kg} \times 333.55 \ \text{kJ/kg}}{24 \times 3600 \ \text{s}} = \frac{302,601 \ \text{kJ}}{86,400 \ \text{s}} = 3.502 \ \text{kW} \quad (\text{Standard Definition: } 3.51685 \approx 3.517 \ \text{kW}) 1 TR=3.517 kW=210 kJ/min=12,000 Btu/hr1 \ \text{TR} = 3.517 \ \text{kW} = 210 \ \text{kJ/min} = 12,000 \ \text{Btu/hr}

2. Standard Vapour Compression Refrigeration System (VCRS)

The Vapour Compression Refrigeration System (VCRS) is the most widely utilized refrigeration cycle. It eliminates the impractical wet compression and expansion cylinder expansion work of the reversed Carnot cycle by employing dry isentropic compression and an isenthalpic throttling expansion valve.

+-----------------------------------------------------------------------------------------+
|                        STANDARD VCRS SCHEMATIC & CYCLE DIAGRAMS                         |
|                                                                                         |
|   SCHEMATIC:                                                                            |
|               +------------------- [ CONDENSER ] <-------------------+                  |
|               |                     (Q_out = q_c)                     |                 |
|               v                                                       | (State 2: Super-|
|        (State 3: Sat Liquid)                                          |  heated vapor)  |
|        [ EXPANSION VALVE ]                                     [ COMPRESSOR ]           |
|          (h3 = h4 Throttling)                                   (W_in = W_c)            |
|               |                                                       ^                 |
|               v                                                       | (State 1: Sat   |
|               +------------------> [ EVAPORATOR ] --------------------+  vapor)         |
|                                     (Q_in = RE)                                         |
|                                                                                         |
|   PRESSURE-ENTHALPY (P-h) DIAGRAM:            TEMPERATURE-ENTROPY (T-s) DIAGRAM:        |
|   P ^                                         T ^                                       |
|     |       2-3: Condenser                      |         2-3: Condenser                |
|  Pc |--------* 3 <=========== 2 (Superheated)   |          * 3 <========= 2             |
|     |       /|                 \                |         / |            |  (s1 = s2)   |
|     |      / |                  \               |        /  |            |              |
|  Pe |-----*--* 4 -----------> 1 *               |       /   * 4 -------> * 1            |
|     |    /   |   4-1: Evaporator                |      /                  \             |
|     +---+----+--------------------> h           +-----+--------------------> s          |
|         h3=h4                 h1  h2                                                    |
+-----------------------------------------------------------------------------------------+

The Four Thermodynamic Processes

  1. Process 1-2 (Isentropic Compression): Saturated vapor at evaporator pressure PeP_e is compressed isentropically (s1=s2s_1 = s_2) in a mechanical compressor to superheated vapor at condenser pressure PcP_c. Work input: wc=h2−h1w_c = h_2 - h_1.
  2. Process 2-3 (Isobaric Heat Rejection): Superheated refrigerant vapor is desuperheated, condensed to saturated liquid, and subcooled inside the condenser at constant pressure PcP_c. Heat rejected: qc=h2−h3q_c = h_2 - h_3.
  3. Process 3-4 (Isenthalpic Throttling Expansion): Saturated liquid expands irreversibly through a throttling capillary tube or thermostatic expansion valve (TXV) from PcP_c down to PeP_e. Throttling is adiabatic with zero work output: h4=h3h_4 = h_3.
  4. Process 4-1 (Isobaric Evaporation): Low-quality liquid-vapor mixture absorbs thermal energy from the cold refrigerated space at constant pressure PeP_e until it reaches saturated vapor (state 1). Refrigerating effect: RE=qe=h1−h4=h1−h3\text{RE} = q_e = h_1 - h_4 = h_1 - h_3.

Mathematical Formulation of Performance

Refrigerating Effect (RE)=h1−h4=h1−h3(kJ/kg)\text{Refrigerating Effect (RE)} = h_1 - h_4 = h_1 - h_3 \quad (\text{kJ/kg}) Compressor Work (wc)=h2−h1(kJ/kg)\text{Compressor Work } (w_c) = h_2 - h_1 \quad (\text{kJ/kg}) Coefficient of Performance (COP)=REwc=h1−h4h2−h1=h1−h3h2−h1\text{Coefficient of Performance (COP)} = \frac{\text{RE}}{w_c} = \frac{h_1 - h_4}{h_2 - h_1} = \frac{h_1 - h_3}{h_2 - h_1} Refrigerant Mass Flow Rate (m˙r)=Plant Capacity (kW)RE=Plant Capacity (kW)h1−h3(kg/s)\text{Refrigerant Mass Flow Rate } (\dot{m}_r) = \frac{\text{Plant Capacity (kW)}}{\text{RE}} = \frac{\text{Plant Capacity (kW)}}{h_1 - h_3} \quad (\text{kg/s}) Compressor Power Input (P)=m˙rwc=m˙r(h2−h1)(kW)\text{Compressor Power Input } (P) = \dot{m}_r w_c = \dot{m}_r (h_2 - h_1) \quad (\text{kW}) Heat Rejection Ratio (HRR)=qcRE=h2−h3h1−h3=1+1COP\text{Heat Rejection Ratio (HRR)} = \frac{q_c}{\text{RE}} = \frac{h_2 - h_3}{h_1 - h_3} = 1 + \frac{1}{\text{COP}}

3. Influence of Operating Parameters on VCRS Performance

+-----------------------------------------------------------------------------------------+
|                        VCRS OPERATING PARAMETER SENSITIVITY                             |
|                                                                                         |
|   Parameter Modification       RE (kJ/kg)      W_c (kJ/kg)     COP         V_piston     |
|   --------------------------   -------------   -------------   ---------   ---------    |
|   1. Subcooling of Liquid      Increases       Unchanged       Increases   Unchanged    |
|      at Condenser Exit (3->3')                                                          |
|   2. Superheating Vapor        Increases       Increases       Varies      Increases    |
|      in Evaporator (1->1')                                     (R134a +)                |
|   3. Decreasing Evaporator     Decreases       Increases       Decreases   Increases    |
|      Temperature (Te drops)                    sharply         severely    greatly      |
|   4. Increasing Condenser      Decreases       Increases       Decreases   Slight       |
|      Temperature (Tc rises)                                    moderately  increase     |
+-----------------------------------------------------------------------------------------+
+-----------------------------------------------------------------------------------------+
|                         EFFECTS ON P-h DIAGRAM: SUBCOOLING & SUPERHEAT                  |
|                                                                                         |
|   P ^                                                                                   |
|     |           3'    3                                   2      2'                     |
|  Pc |-----------*<----*===================================*=====>*                      |
|     |          /|     |                                    \      \                     |
|     |         / |     |                                     \      \                    |
|  Pe |--------*--*<----*--------------------------------------*----->*                   |
|     |       /   4'    4                                      1      1'                  |
|     +------+----+-----+--------------------------------------+------+--> h              |
|            |<-Delta_h->|                                     |<-Dh->|                   |
|            Subcooling Gain (RE increases)                   Superheating Gain           |
+-----------------------------------------------------------------------------------------+

1. Subcooling of Liquid Refrigerant (3→3′3 \to 3')

Cooling liquid refrigerant below saturation temperature before throttling (T3′<Tsat(Pc)T_{3'} < T_{\text{sat}}(P_c)):

  • State 4 shifts left to 4′4' (h4′<h4h_{4'} < h_4).
  • Refrigerating effect increases: RE′=h1−h4′>RE\text{RE}' = h_1 - h_{4'} > \text{RE}.
  • Compressor work wc=h2−h1w_c = h_2 - h_1 is unaffected.
  • COP\text{COP} always increases.

2. Superheating of Suction Vapor (1→1′1 \to 1')

Heating vapor above saturation temperature prior to compression (T1′>Tsat(Pe)T_{1'} > T_{\text{sat}}(P_e)):

  • Useful Superheating (inside refrigerated space): Increases RE\text{RE} (h1′−h3>h1−h3h_{1'} - h_3 > h_1 - h_3) while increasing wc=h2′−h1′w_c = h_{2'} - h_{1'} due to diverging constant entropy lines at higher temperatures. For R-134a and R-12, COP increases slightly; for Ammonia (R-717), COP decreases.
  • Non-Useful Superheating (in connecting pipework outside cold room): RE\text{RE} remains unchanged while wcw_c increases, leading to a decrease in COP.

3. Evaporator Temperature Drop

Lowering TeT_e decreases suction pressure PeP_e:

  • Specific volume v1v_1 at compressor suction increases exponentially (v1∝1/Pev_1 \propto 1/P_e).
  • Compressor volumetric efficiency drops: ηv=1+c−c(PcPe)1/γ\eta_v = 1 + c - c\left(\frac{P_c}{P_e}\right)^{1/\gamma}.
  • Mass flow rate delivered by a fixed displacement compressor drops drastically.

4. Multi-Stage Compression with Flash Intercooling

When the overall pressure ratio rp=Pc/Per_p = P_c / P_e exceeds 6 to 86\text{ to }8 (e.g., low-temperature blast freezing or deep-shaft mine cooling), single-stage VCRS suffers from:

  1. Severe deterioration in compressor volumetric efficiency.
  2. Extremely high compressor discharge temperatures (T2>130∘CT_2 > 130^{\circ}\text{C}), which break down lubricating oils and cause valve carbonization.
  3. Large throttling irreversibility losses.
+-----------------------------------------------------------------------------------------+
|                        TWO-STAGE COMPRESSION WITH FLASH INTERCOOLER                     |
|                                                                                         |
|   SCHEMATIC:                                                                            |
|                                                                                         |
|               +---------------- [ CONDENSER (Pc) ] <----------------+                   |
|               |                                                     |                   |
|               v                                                     | (HP Compressor)   |
|        [ EXPANSION VALVE 1 ]                                        |                   |
|               |                                                     |                   |
|               v (State 5: Flash Liquid)       (State 3: Saturated)  |                   |
|       +-> [ FLASH CHAMBER (Pi) ] -----------> [ INTERCOOLER ] ------+                   |
|       |       |                                     ^                                   |
|       |       v                                     | (LP Compressor)                   |
|       | [ EXPANSION VALVE 2 ]                       |                                   |
|       |       |                                     |                                   |
|       |       v                                     |                                   |
|       +-------+----------------> [ EVAPORATOR (Pe) ]+                                   |
|                                                                                         |
|   Optimum Intermediate Pressure:   P_i = sqrt( P_e * P_c )                              |
+-----------------------------------------------------------------------------------------+

Optimum Intermediate Pressure (PiP_i)

To minimize total compressor power input for a two-stage system with perfect intercooling between stages:

Pi=PePcP_i = \sqrt{P_e P_c} Pressure Ratio per Stage: rp,1=rp,2=PcPe\text{Pressure Ratio per Stage: } \quad r_{p,1} = r_{p,2} = \sqrt{\frac{P_c}{P_e}}

5. Vapour Absorption Refrigeration System (VARS)

The Vapour Absorption Refrigeration System (VARS) replaces the power-hungry mechanical compressor of the VCRS with a thermal compressor assembly comprising an Absorber, Solution Pump, Generator, and Pressure Reducing Valve. It is driven primarily by low-grade thermal waste heat (steam from mine boilers, exhaust gas from diesel generators, or solar collectors).

+-----------------------------------------------------------------------------------------+
|                        VAPOUR ABSORPTION SYSTEM (VARS) SCHEMATIC                        |
|                                                                                         |
|                      Heat In (Q_g at T_g)                                               |
|                               v                                                         |
|                     +-------------------+                                               |
|                     |   GENERATOR       |                                               |
|                     | (Vapor Separated) |                                               |
|                     +-------------------+                                               |
|                       | High-P Vapor      ^ Weak Solution (Rich in Refrigerant)         |
|                       v                   |                                             |
|               [ CONDENSER (Pc) ]     [ SOLUTION PUMP ] (Work input W_p ~ 0)             |
|                       |                   ^                                             |
|                       v                   |                                             |
|               [ EXPANSION VALVE ]   +-------------------+                               |
|                       |             |   ABSORBER        | ---> Heat Out (Q_a at T_a)    |
|                       v             | (Vapor Absorbed)  |                               |
|               [ EVAPORATOR (Pe) ]-> +-------------------+                               |
|                       ^                                                                 |
|                       |                                                                 |
|                 Cooling Load (Q_e at T_e)                                               |
+-----------------------------------------------------------------------------------------+

Maximum Theoretical COP of VARS (Carnot Analysis)

A VARS can be modeled as a combined system: a reversible Carnot Heat Engine operating between generator temperature TgT_g and ambient/absorber temperature TaT_a, producing mechanical work WW that directly drives a reversible Carnot Refrigerator operating between TeT_e and TaT_a.

ηCarnot, HE=WQg=Tg−TaTg\eta_{\text{Carnot, HE}} = \frac{W}{Q_g} = \frac{T_g - T_a}{T_g} COPCarnot, Ref=QeW=TeTa−Te\text{COP}_{\text{Carnot, Ref}} = \frac{Q_e}{W} = \frac{T_e}{T_a - T_e} COPmax, VARS=QeQg=ηCarnot, HE×COPCarnot, Ref=(Tg−TaTg)(TeTa−Te)\text{COP}_{\text{max, VARS}} = \frac{Q_e}{Q_g} = \eta_{\text{Carnot, HE}} \times \text{COP}_{\text{Carnot, Ref}} = \left(\frac{T_g - T_a}{T_g}\right) \left(\frac{T_e}{T_a - T_e}\right)

Where all temperatures (Tg,Ta,TeT_g, T_a, T_e) must be expressed in Kelvin.

Comparison of Commercial Absorption Systems

FeatureAqua-Ammonia (NH3-H2O\text{NH}_3\text{-H}_2\text{O}) SystemLithium Bromide-Water (LiBr-H2O\text{LiBr-H}_2\text{O}) System
RefrigerantAmmonia (NH3\text{NH}_3)Water (H2O\text{H}_2\text{O})
AbsorbentWater (H2O\text{H}_2\text{O})Lithium Bromide Salt (LiBr\text{LiBr})
Volatility of AbsorbentVolatile (water evaporates with NH3\text{NH}_3)Completely non-volatile (salt does not evaporate)
Rectifier / AnalyzerMandatory (to remove water trace vapor)Not required (pure water vapor leaves generator)
Operating PressureHigh positive pressures (10–18 bar10\text{--}18\text{ bar})Deep vacuum (0.008–0.08 bar0.008\text{--}0.08\text{ bar})
Minimum TemperatureSub-zero capability down to −40∘C-40^{\circ}\text{C}Limited to Te>0∘CT_e > 0^{\circ}\text{C} (water freezes at 0∘C0^{\circ}\text{C})
Primary ApplicationIndustrial freezing & low-temp mining cold storesCentral commercial Air Conditioning systems

The Three-Fluid Electrolux (Platen-Munters) System

Designed for domestic refrigerators where electricity or mechanical pumps are unavailable:

  • Working Fluids: Ammonia (Refrigerant), Water (Absorbent), Hydrogen (Inert Auxiliary Gas).
  • Eliminates Solution Pump: Operates at uniform total pressure (Ptotal≈15 barP_{\text{total}} \approx 15\text{ bar}) throughout the system.
  • Evaporator Principle: Dalton's law of partial pressures: Ptotal=PNH3+PH2P_{\text{total}} = P_{\text{NH}_3} + P_{\text{H}_2}. Hydrogen gas introduced into the evaporator lowers the partial pressure of ammonia (PNH3≈2 barP_{\text{NH}_3} \approx 2\text{ bar}), allowing liquid ammonia to evaporate at low temperature (−15∘C-15^{\circ}\text{C}) without requiring a mechanical throttling valve or compressor.
  • Zero Moving Parts: Circulation occurs entirely via natural thermosiphon buoyancy.

6. Refrigerant Chemistry, Nomenclature & Environmental Protocols

ASHRAE Standard Refrigerant Nomenclature

For halogenated hydrocarbons with chemical formula CmHnFpClq\text{C}_m \text{H}_n \text{F}_p \text{Cl}_q where 2m+2=n+p+q2m + 2 = n + p + q:

Refrigerant Number: R-(m−1)(n+1)(p)\text{Refrigerant Number: } \quad \text{R-}(m-1)(n+1)(p)
  • Inorganic Compounds: Numbered as R-(700+Molecular Weight)\text{R-}(700 + \text{Molecular Weight}):
    • Ammonia (NH3\text{NH}_3, M=17M = 17): R-717\text{R-717}
    • Water (H2O\text{H}_2\text{O}, M=18M = 18): R-718\text{R-718}
    • Carbon Dioxide (CO2\text{CO}_2, M=44M = 44): R-744\text{R-744}
    • Air (M=29M = 29): R-729\text{R-729}

Environmental Impact Metrics & Global Treaties

  1. Ozone Depletion Potential (ODP): Relative index measuring damage to the stratospheric ozone layer compared to trichlorofluoromethane (R-11\text{R-11}, baseline ODP=1.0\text{ODP} = 1.0).
  2. Global Warming Potential (GWP): Index measuring thermal radiation trapped in the atmosphere over 100 years relative to carbon dioxide (CO2\text{CO}_2, baseline GWP=1.0\text{GWP} = 1.0).
+-----------------------------------------------------------------------------------------+
|                        REFRIGERANT ENVIRONMENTAL CLASSIFICATION                         |
|                                                                                         |
|   Class        Examples           ODP        GWP (100-yr)    Regulatory Status          |
|   ---------    ----------------   --------   -------------   ------------------------   |
|   CFC          R-11, R-12, R-115  0.6 - 1.0  4,500 - 10,000  BANNED (Montreal Protocol) |
|   HCFC         R-22, R-123        0.02-0.05  700 - 1,800     PHASED OUT (Montreal)      |
|   HFC          R-134a, R-410A     0.00       1,300 - 4,000   PHASE DOWN (Kigali Amend.) |
|   HFO          R-1234yf, R-1234ze 0.00       < 1             Modern Low-GWP Standard    |
|   Natural      R-290 (Propane)    0.00       3               Eco-friendly Hydrocarbons  |
|   Refrigerants R-600a (Isobutane) 0.00       3               Zero ODP, Ultra-low GWP    |
|                R-717 (Ammonia)    0.00       0               High efficiency, toxic     |
|                R-744 (CO2)        0.00       1               Transcritical cycle        |
+-----------------------------------------------------------------------------------------+

7. Step-by-Step Worked Problems: VCRS Cycle & VARS Thermal Efficiency

Worked Example 1: Standard Industrial VCRS Chiller Performance

A 10 TR R-134a industrial water chilling plant operates on a standard VCRS cycle between an evaporator temperature of −10∘C-10^{\circ}\text{C} (Pe=2.01 barP_e = 2.01\text{ bar}) and a condenser temperature of +40∘C+40^{\circ}\text{C} (Pc=10.17 barP_c = 10.17\text{ bar}). Saturated vapor leaves the evaporator and saturated liquid leaves the condenser. The refrigerant enthalpy values are:

  • Saturated vapor at −10∘C-10^{\circ}\text{C}: h1=392.8 kJ/kgh_1 = 392.8\text{ kJ/kg}, s1=1.733 kJ/kg⋅Ks_1 = 1.733\text{ kJ/kg}\cdot\text{K}
  • Superheated vapor after isentropic compression at PcP_c: h2=425.8 kJ/kgh_2 = 425.8\text{ kJ/kg}
  • Saturated liquid at +40∘C+40^{\circ}\text{C}: h3=256.4 kJ/kgh_3 = 256.4\text{ kJ/kg}

Calculate the COP, mass flow rate of refrigerant (kg/s), and compressor power input (kW).

+-----------------------------------------------------------------------------------------+
|                        VCRS CHILLER CALCULATION STEPS                                   |
|                                                                                         |
|   STEP 1: Identify Enthalpies at Key State Points                                       |
|           h1 = 392.8 kJ/kg (Evaporator Exit)                                            |
|           h2 = 425.8 kJ/kg (Compressor Exit)                                            |
|           h3 = 256.4 kJ/kg (Condenser Exit)                                             |
|           h4 = h3 = 256.4 kJ/kg (Expansion Valve Exit, Isenthalpic)                     |
|                                                                                         |
|   STEP 2: Calculate Refrigeration Effect (RE) and Compressor Work (Wc)                  |
|           RE = h1 - h4 = 392.8 - 256.4 = 136.4 kJ/kg                                    |
|           w_c = h2 - h1 = 425.8 - 392.8 = 33.0 kJ/kg                                     |
|                                                                                         |
|   STEP 3: Calculate Coefficient of Performance (COP)                                    |
|           COP = RE / w_c = 136.4 / 33.0 = 4.133                                         |
|                                                                                         |
|   STEP 4: Calculate Total Plant Capacity in kW                                          |
|           Capacity = 10 TR * 3.517 kW/TR = 35.17 kW                                     |
|                                                                                         |
|   STEP 5: Calculate Refrigerant Mass Flow Rate                                          |
|           m_dot_r = Capacity / RE = 35.17 kW / 136.4 kJ/kg = 0.2578 kg/s                |
|                                                                                         |
|   STEP 6: Calculate Compressor Power Input                                              |
|           Power = m_dot_r * w_c = 0.2578 kg/s * 33.0 kJ/kg = 8.507 kW                   |
+-----------------------------------------------------------------------------------------+
Test Your Knowledge

A standard Vapour Compression Refrigeration plant operating on R-134a produces 70.34 kW of refrigeration (20 TR). The enthalpy values are: Evaporator exit h1 = 400 kJ/kg, Compressor discharge h2 = 440 kJ/kg, and Condenser exit h3 = 260 kJ/kg. What is the plant COP and the power required to drive the compressor?

A

COP = 3.50; Power = 20.10 kW

B

COP = 4.50; Power = 15.63 kW

C

COP = 3.50; Power = 28.14 kW

D

COP = 2.80; Power = 25.12 kW

Test Your Knowledge

Which of the following modifications will unequivocally increase the Coefficient of Performance (COP) of a standard Vapour Compression Refrigeration System without changing the compressor isentropic efficiency?

A

Increasing the condensing pressure Pc while keeping evaporator pressure Pe constant

B

Decreasing the evaporator pressure Pe while keeping condensing pressure Pc constant

C

Non-useful superheating of the suction vapor occurring inside the suction line piping

D

Subcooling the liquid refrigerant leaving the condenser prior to entering the expansion valve

Test Your Knowledge

A solar-assisted Vapour Absorption Refrigeration System (VARS) receives heat at the generator at Tg = 127°C (400 K) from solar parabolic collectors. The system provides chilled brine at Te = -3°C (270 K) and rejects heat to the environment at Ta = 27°C (300 K). What is the maximum theoretical Carnot COP of this absorption system?

A

1.85

B

2.25

C

3.00

D

0.75

Sections you finish are checked off in the contents.