7.4 Bathtubs, Shower Compartments, and Seats

Key Takeaways

  • Bathtubs need a clearance 30 inches deep along the full length (extending 12 inches past the head end where a permanent seat is provided), a permanent or removable seat, and grab bars arranged for the seat type.

  • Transfer showers are 36 x 36 inches inside with a 36-inch entry and a clearance 52 inches long (48 inches existing) by 36 inches deep; the seat is on the wall opposite the controls.

  • Standard roll-in showers are 60 x 30 inches with a 60-inch entry and a 60 x 30-inch clearance; alternate roll-in showers are 60 x 36 inches with a 36-inch entry at one end.

  • Shower controls and hand showers are 38 to 48 inches above the shower floor; hand shower hoses are 59 inches long with a nonpositive shut-off.

  • Seats are 17 to 19 inches high and resist 250 pounds; shower and bathtub water is limited to 120 degrees F; roll-in thresholds are 1/2 inch maximum.

Last updated: October 2026

7.4 Bathtubs, Shower Compartments, and Seats

Bathtubs (A117.1 Section 607)

ItemSectionRequirement
Clearance607.2Full length of the tub, 30 in. deep; where a permanent seat is at the head end, the clearance extends 12 in. beyond the head-end wall
Seat607.3Permanent seat at the head end or removable in-tub seat, per 610
Controls607.5On an end wall, between the rim and grab bar, and between the open side and the centerline of the tub width; comply with 309.4
Hand shower607.6Hose 59 in. minimum, usable as a fixed head and a hand shower, with a nonpositive shut-off; a vertical-bar mount may not obstruct grab bars
Enclosures607.7May not obstruct controls or transfer; no tracks on the tub rim
Water temperature607.8120 degrees F maximum

Bathtub Grab Bars (607.4)

BarTub with permanent seat (607.4.1)Tub with removable seat (607.4.2)
Back wall, upperPer 609.4 (33 to 36 in.), within 15 in. of the head end wall, to within 12 in. of the control end wall24 in. minimum long, within 24 in. of the head end wall, to within 12 in. of the control end wall
Back wall, lower8 to 10 in. above the rim, same extents8 to 10 in. above the rim, same extents
Control end wall, horizontal24 in. minimum, from near the front edge toward the inside cornerSame
Control end wall, vertical18 in. minimum, 3 to 6 in. above the horizontal bar, 4 in. maximum inward from the front edgeSame
Head end wall-12 in. minimum at the front edge

An L-shaped continuous bar of equivalent dimensions may replace the separate control-end horizontal and vertical bars.

Shower Compartments (A117.1 Section 608)

TypeInside sizeEntryClearanceSeat
Transfer-type (608.2.1)36 x 36 in.36 in.New: 52 in. long x 36 in. deep adjacent to the open face, measured from the control wall or from 4 in. behind it; existing: 48 x 36 in.Folding or non-folding seat on the wall opposite the control wall
Standard roll-in (608.2.2)60 in. wide x 30 in. deep60 in.60 x 30 in. adjacent to the 60 in. open face; a lavatory may be at the end opposite the seatFolding seat on an end wall (fixed seat allowed if outside the minimum inside dimension)
Alternate roll-in (608.2.3)60 in. wide x 36 in. deep36 in. at one end of the 60 in. width-Folding seat on a seat wall 24 to 36 in. long on the entry side, opposite the back wall

Shower Grab Bars (608.3)

  • Required horizontal bars are at the same height where multiple bars are used.
  • Transfer showers: across the control wall and on the back wall to a point 18 in. from the control wall, plus a vertical bar 18 in. minimum, 3 to 6 in. above the horizontal bar and 4 in. maximum in from the front edge.
  • Standard roll-in: back-wall bar from the edge of the seat, not above the seat, extending within 6 in. of the side wall opposite the seat (need not exceed 48 in.); where a side wall is opposite the seat within 72 in., a side-wall bar (need not exceed 30 in.) and a vertical bar are required.
  • Alternate roll-in: bars on the back wall and the side wall adjacent to the seat, not above the seat, within 6 in. of the adjacent wall.

Controls and Hand Showers (608.4 and 608.5)

ShowerControl location
TransferOn the control wall opposite the seat, 38 to 48 in. above the shower floor, 15 in. maximum from the centerline of the control wall toward the opening
Standard roll-inOn the back wall above the seat, 38 to 48 in. high, 16 to 27 in. from the wall behind the seat
Alternate roll-in38 to 48 in. high; on the end wall adjacent to the seat 16 to 27 in. from the wall behind the seat, or on the back wall within 15 in. of the seat centerline

Hand showers have a 59 in. minimum hose, a nonpositive shut-off, and a holder 38 to 48 in. above the shower floor. In other than Accessible and Type A units, a fixed shower head 48 in. maximum above the shower floor may replace the hand shower.

Thresholds, Enclosures and Temperature

  • Thresholds (608.6): Roll-in showers 1/2 in. maximum per 303; transfer showers 1/2 in. maximum, beveled, rounded or vertical. In existing transfer showers where a 1/2 in. threshold would disturb the slab reinforcement, up to 2 in. is allowed.
  • Enclosures (608.7): May not obstruct controls or transfer.
  • Water temperature (608.8): 120 degrees F maximum.

Seats (Section 610)

SeatRequirement
Height (610.2, 610.3)17 to 19 in. above the bathroom floor to the top of the seat
Removable in-tub seat15 to 16 in. deep, capable of secure placement
Permanent tub seat15 in. minimum deep, from the back wall to or beyond the outer edge of the tub, at the head end
Shower seat extentTransfer and alternate roll-in: along the seat wall to within 3 in. of the entry; standard roll-in: from the control wall to within 3 in. of the entry
Rectangular shower seatRear edge 2 1/2 in. maximum and front edge 15 to 16 in. from the seat wall; side edge 1 1/2 in. maximum from the back wall (transfer) or control wall (roll-in)
Strength (610.4)250 lb vertical or horizontal at any point

Assisted Bathing (IBC 1110.2.3)

Where Section 1108 permits, bathrooms serving Accessible units may use a standard roll-in shower designed for assisted bathing: 60 x 30 in. minimum with a 60-in. entry and a 60 x 30 in. clearance; grab bars on three walls at the same height; no wall-mounted folding seats; controls and hand shower 38 to 48 in. high located to facilitate caregiver access.

Test Your Knowledge

A new transfer-type shower compartment is being reviewed. What clearance must be provided adjacent to its open face under ICC A117.1-2017?

A

48 inches long by 36 inches deep

B

60 inches long by 30 inches deep

C

36 inches long by 48 inches deep

D

52 inches long by 36 inches deep

Test Your Knowledge

What are the minimum inside dimensions and entry width of a standard roll-in-type shower compartment under ICC A117.1 Section 608.2.2?

A

60 inches wide by 30 inches deep with a 60-inch entry

B

36 inches by 36 inches with a 36-inch entry

C

60 inches wide by 36 inches deep with a 36-inch entry

D

48 inches by 30 inches with a 32-inch entry

Test Your Knowledge

In a transfer-type shower, at what height must the controls and hand shower be located under ICC A117.1 Section 608.4.1?

A

34 to 48 inches above the shower floor

B

38 to 48 inches above the shower floor

C

15 to 48 inches above the shower floor

D

40 to 54 inches above the shower floor

Sections you finish are checked off in the contents.