8.3 Telephones, ATMs and Fare Machines, Two-Way Communication Systems, and Detectable Warnings

Key Takeaways

  • Wheelchair accessible telephones need a clear floor space, a 10-inch maximum reach over an enclosure edge for a parallel approach (20 inches for forward), push-button controls and a 29-inch cord.

  • Volume-control telephones provide gain up to 20 dB with an intermediate step of 12 dB and automatic reset; TTY keypads are 34 inches minimum high when in use.

  • ATMs and fare machines need a clear floor space, Section 309 operable parts, a 12-key layout with a raised dot on 5, raised function key symbols, a screen visible from 40 inches, speech output and braille instructions.

  • Detectable warnings use truncated domes 0.9 to 1.4 inches in base diameter, 0.2 inch high, 1.6 to 2.4 inches on center in a square grid, 24 inches deep, contrasting light-on-dark or dark-on-light.

  • Two-way communication systems provide both visual and audible signals, handset cords are 29 inches minimum, and telephone entry systems comply with DASMA 303.

Last updated: October 2026

8.3 Telephones, ATMs and Fare Machines, Two-Way Communication Systems, and Detectable Warnings

These elements are a small share of the outline (Telephones, Assistive Listening Systems and ATMs 1%; Detectable Warnings 1%), but the questions are usually direct recall of A117.1 numbers.

Where the Scoping Comes From

IBC Chapter 11 does not itself scope public telephones, ATMs or entry systems. Those are scoped in IBC Appendix E (Supplementary Accessibility Requirements), which applies only where the jurisdiction adopts it, and in federal ADA regulations. Appendix E requires, for example, at least one machine of each type at each location where ATMs or fare machines are provided, accessible two-way communication systems used to gain admittance, and wheelchair accessible, volume-control and TTY telephones in specified numbers. Detectable warnings are scoped in IBC 1110.13 (2024; 1110.11 in 2021) for transit platform edges and in A117.1 406.6.2 for street crossings.

Public Telephones (A117.1 Section 704)

ItemSectionRequirement
Clear floor space704.2.1Not obstructed by bases, enclosures or seats (drive-up only phones exempt)
Parallel approach704.2.1.1Edge of the enclosure to the face of the telephone 10 in. maximum
Forward approach704.2.1.2Front edge of a counter in the enclosure to the face of the telephone 20 in. maximum
Operable parts704.2.2Comply with 309; push-button controls where service is available
Directories704.2.3Comply with 309
Cord length704.2.429 in. minimum
Volume control704.3Gain adjustable up to 20 dB minimum; incremental controls have at least one intermediate step of 12 dB; automatic reset
TTY704.4Permanently affixed within or adjacent to the enclosure
TTY height704.5Touch surface of the keypad 34 in. minimum above the floor (not required where seats are provided)
TTY shelf704.6Shelf and outlet where phones accommodate portable TTYs, with 6 in. vertical clearance above the TTY area
Visual relay service booth704.7Seating and privacy enclosure, two-way video, 20 footcandles diffuse lighting, flat bright green or blue background

Volume-controlled telephones are identified by a handset with radiating sound waves (703.6.3.4) and TTYs by the International Symbol of TTY (703.6.3.2).

ATMs and Fare Machines (A117.1 Section 707)

ItemSectionRequirement
Clear floor space707.2In front of the machine (not required at drive-up only machines)
Operable parts707.3Comply with 309; each part distinguishable by sound or touch without activation, unless a clear or correct key is provided
Privacy707.4Same degree of privacy of input and output for all users
Numeric keys707.512-key ascending or descending telephone layout; the 5 key has a single raised dot
Function keys707.6Raised symbols: Enter or Proceed = circle; Clear or Correct = left arrow; Cancel = X; Add value = plus; Decrease value = minus; keys contrast with the background
Display screen707.7Visible from 40 in. above the center of the clear floor space; sans serif characters with the "I" 3/16 in. minimum
Speech output707.8Speech enabled; instructions, prompts, verification, errors and all displayed information usable by people with vision impairments; delivered through an industry standard connector or handset; user can repeat, interrupt and adjust volume; receipts provided audibly except for location, date, time, account number and machine identifier
Input controls707.9At least one tactually discernible control for each function
Braille instructions707.10Braille instructions for initiating speech mode

Two-Way Communication Systems (A117.1 Section 708)

Two-way communication systems, such as entry intercoms, provide both visual and audible signals (708.2); handset cords are 29 in. minimum (708.3); telephone entry systems comply with ANSI/DASMA 303 (708.4). The IBC 1009.8 egress communication system is a separate requirement covered in Section 5.3.

Detectable Warnings (A117.1 Section 705)

ItemSectionRequirement
Standardization705.2Standard within a building, facility, site or complex
Contrast705.3Contrast visually with adjacent surfaces, light-on-dark or dark-on-light
Interior locations705.4Differ from adjoining walking surfaces in resiliency or sound-on-cane contact
Dome size705.5.1Base diameter 0.9 to 1.4 in.; top diameter 50 to 65 percent of the base
Dome height705.5.20.2 in.
Dome spacing705.5.31.6 to 2.4 in. center to center; 0.65 in. minimum base to base
Alignment705.5.4Square grid
Depth705.624 in. minimum in the direction of travel
Width705.6Full width of the curb ramp run (excluding flares) or blended transition; full width of at-grade rail crossings; full length of public use areas of bus and rail boarding platforms

Placement (705.7)

  • Perpendicular curb ramps: at the back of curb where the ends of the bottom grade break are in front of the back of curb; on the ramp run within one dome spacing of the bottom grade break where the grade break is behind the back of curb by 60 in. or less; on the lower landing at the back of curb where that distance is more than 60 in.
  • Parallel curb ramps: on the turning space at the flush transition between street and sidewalk.
  • Blended transitions: at the back of curb, or at the flush transition for raised crossings and depressed corners.
  • Cut-through refuge islands: at the island edges, separated by at least 24 in. without warnings.
  • At-grade rail crossings: on each side, the nearest edge 6 to 15 ft from the centerline of the nearest rail (on the side of any pedestrian gates away from the rail).
  • Boarding platforms: at the boarding edge.
Test Your Knowledge

Under ICC A117.1 Section 705.5, what is the required height of a truncated dome on a detectable warning surface?

A

0.2 inch

B

0.1 inch

C

0.25 inch

D

0.375 inch

Test Your Knowledge

What raised symbol identifies the Enter or Proceed function key on an accessible ATM under ICC A117.1 Section 707.6.1?

A

A left arrow

B

An X

C

A plus sign

D

A circle

Test Your Knowledge

A volume-control public telephone is installed. What gain must its receiver volume control provide under ICC A117.1 Section 704.3?

A

Up to 12 dB with no intermediate step

B

Up to 20 dB, a 12 dB intermediate step, and automatic reset

C

Fixed amplification of 30 dB

D

Adjustable up to 15 dB, with a manual reset after each call