7.5 Plumbing Scoping: Family Rooms, Adult Changing Stations, Drinking Fountains, Laundry, and Saunas
Key Takeaways
Assembly and mercantile occupancies need an accessible family or assisted-use toilet room where an aggregate of six or more male and female water closets is required.
Family or assisted-use toilet rooms have one water closet and one lavatory (a urinal and child-height fixtures may be added), are within 500 feet and one story of separate-sex rooms, are lockable and have an 'occupied' indicator.
Where drinking fountains are provided, at least two are required: one for wheelchair users (spout 36 inches maximum, 15 inches from the vertical support, 5 inches from the front) and one for standing persons (spout 38 to 43 inches).
The 2024 IBC requires adult changing stations in assembly and mercantile buildings that need family rooms, certain college classroom buildings, E assembly spaces and highway rest stops.
Washing machines and dryers have a parallel-approach clear floor space and openings 15 to 36 inches high; saunas and steam rooms need a turning space and a compliant bench where seating is provided.
7.5 Plumbing Scoping: Family Rooms, Adult Changing Stations, Drinking Fountains, Laundry, and Saunas
This section collects the plumbing-related scoping in IBC Section 1110 that is not covered by compartments, lavatories and showers. Section numbers shift between editions because the 2024 IBC inserted adult changing stations and laundry equipment.
| Topic | 2021 IBC | 2024 IBC | A117.1-2017 technical |
|---|---|---|---|
| Family or assisted-use rooms | 1110.2.1 | 1110.2.1 | 603, 604, 606, 607, 608 |
| Adult changing stations | - | 1110.4 | (scoping only) |
| Kitchens and kitchenettes | 1110.4 | 1110.5 | 804 |
| Laundry equipment | - | 1110.6 | 611 |
| Drinking fountains | 1110.5 | 1110.7 | 602 |
| Bottle-filling stations | 1110.6 | 1110.8 | 602.4 |
| Saunas and steam rooms | 1110.7 | 1110.9 | 612 |
Family or Assisted-Use Toilet and Bathing Rooms (1110.2.1)
When required: In assembly and mercantile occupancies, an accessible family or assisted-use toilet room is required where an aggregate of six or more male and female water closets is required. In mixed occupancies, count only the water closets required for the assembly or mercantile occupancy. In recreational facilities with separate-sex bathing rooms, an accessible family or assisted-use bathing room is required, unless each separate-sex bathing room has only one shower or bathtub. Fixtures in family rooms count toward the occupancy's required fixtures.
| Section | Requirement |
|---|---|
| 1110.2.1.2 Toilet rooms | Only one water closet and only one lavatory; a urinal, a child-height water closet and a child-height lavatory are permitted additions; a family bathing room counts as a family toilet room |
| 1110.2.1.3 Bathing rooms | Only one shower or bathtub, plus one water closet and one lavatory; accessible storage where separate-sex bathing rooms have storage |
| 1110.2.1.4 Location | On an accessible route; not more than one story above or below separate-sex toilet rooms; route from any separate-sex room not more than 500 ft |
| 1110.2.1.5 Prohibited location | In passenger transportation facilities and airports, the route may not pass through security checkpoints |
| 1110.2.1.6 Privacy | Doors securable from within with an "occupied" indicator |
IBC 1112.3 Item 4 requires directional signs at each separate-sex toilet and bathing room indicating the nearest family or assisted-use room.
Adult Changing Stations (2024 IBC 1110.4)
Where provided, adult changing stations are accessible. The 2024 IBC requires at least one:
- In assembly and mercantile occupancies where family or assisted-use toilet or bathing rooms are required by 1110.2.1;
- In Group B educational facilities above 12th grade where an aggregate of 12 or more water closets is required to serve classrooms and lecture halls;
- In Group E where a room used for assembly purposes requires an aggregate of six or more water closets;
- In highway rest stops and service plazas.
The station is in a toilet room with only one water closet and one lavatory (or in a required family room), available whenever the occupancy is occupied, not behind security checkpoints, and not more than two stories and 2,000 ft of travel from users.
Drinking Fountains
Scoping (1110.5 in 2021; 1110.7 in 2024)
Where drinking fountains are provided on an exterior site, on a floor or within a secured area, not fewer than two are provided: one for people who use a wheelchair and one for standing persons. A single fountain with two separate spouts serving both groups may substitute. Where more than the minimum are provided, 50 percent serve wheelchair users and 50 percent standing persons, rounded up or down as long as the total is 100 percent. Children's provisions are permitted where fountains are primarily for children. IBC 1112.3 Item 6 requires directional signs when the two types are not adjacent.
Technical Criteria (A117.1 602)
| Item | Wheelchair fountain (602.2) | Standing fountain (602.3) |
|---|---|---|
| Clear floor space | Forward approach, centered, with knee and toe clearance (children's: parallel approach allowed) | - |
| Spout outlet height | 36 in. maximum (children's 30 in. maximum) | 38 to 43 in. (children's 30 to 43 in.) |
| Spout location | 15 in. minimum from the vertical support and 5 in. maximum from the front edge, including bumpers (children's 3 1/2 in. maximum from the front) | 5 in. maximum from the front edge |
| Water flow | 4 in. minimum high; stream angle 30 degrees maximum within 3 in. of the front, 15 degrees maximum between 3 and 5 in. | Same |
| Operable parts | Comply with 309 | Comply with 309.3 and 309.4 |
| Protruding objects | Both comply with 307 |
Bottle-Filling Stations (1110.6 / 1110.8 and A117.1 602.4)
Where provided, bottle-filling stations are accessible, with a clear floor space for a forward or side approach and hand-operated controls complying with 309 or automatic controls. A filler over the standing fountain need not be accessible if one is also over the wheelchair fountain.
Laundry Equipment (2024 IBC 1110.6 and A117.1 611)
Where provided in spaces required to be accessible, at least one of three or fewer washing machines (or dryers) is accessible, and at least two where more than three are provided. A117.1 611 requires a parallel approach clear floor space (centered on top loaders; offset 24 in. maximum from the door centerline on front loaders); operable parts, including doors, lint screens and detergent compartments, comply with 308 and 309 (obstruction height up to 36 in. allowed); top-loading doors 36 in. maximum high; front-loading openings with the bottom 15 to 36 in. above the floor.
Saunas and Steam Rooms (1110.7 / 1110.9 and A117.1 612)
Where provided, saunas and steam rooms are accessible; where clustered, at least 5 percent, but not less than one of each type in each cluster. A117.1 612 requires a turning space inside, and where seating is provided, at least one bench complying with 903, with doors not swinging into the bench clear floor space (unless the room is for individual use and a 305.3 clear floor space is provided beyond the door swing).
A new Group A-2 restaurant requires an aggregate of seven male and female water closets. What does IBC 1110.2.1 require?
Nothing additional, because restaurants are exempt
One additional wheelchair accessible compartment in each room
An accessible family or assisted-use toilet room
An adult changing station in every toilet room
Under ICC A117.1-2017 Section 602.2.4, where must the spout of a wheelchair-accessible drinking fountain be located?
15 inches minimum from the vertical support and 5 inches maximum from the front edge, including bumpers
3 inches maximum from the front edge with no minimum from the support
12 inches minimum from the vertical support and 3 inches maximum from the front edge
Centered on the fountain basin regardless of depth
How far from a separate-sex toilet room may a required family or assisted-use toilet room be under IBC 1110.2.1.4?
On the same floor and within 200 feet
Within two stories and 2,000 feet
Anywhere in the building, as long as it is on an accessible route
Within one story and 500 feet along an accessible route
Sections you finish are checked off in the contents.