11.1 Scoping Accessible, Type A, and Type B Units (IBC 1108)

Key Takeaways

  • Units required to be Type A may be built as Accessible units, and units required to be Type B may be built as Accessible or Type A units (IBC 1108.2).

  • Group R-1 and R-2 non-apartment uses (dormitories, boarding houses) provide Accessible units per Table 1108.6.1.1, which separates units with and without roll-in showers.

  • R-2 apartment houses, monasteries and convents with more than 20 units provide Type A units for at least 2 percent, counted across all R-2 units on the site.

  • In I-1, I-2, R-1, R-2, R-3 and R-4 structures with four or more units intended as residences, every such unit is a Type B unit unless 1108.7 reduces the count.

  • Without elevator service, only ground-floor (accessible entrance) story units must be Type B; site impracticality, multistory units and flood hazard areas can reduce Type A and B counts.

Last updated: October 2026

11.1 Scoping Accessible, Type A, and Type B Units (IBC 1108)

Three Unit Types in the IBC

UnitStandardIntended levelTypical use
Accessible unitA117.1 Section 1102Fully accessible at occupancyHotels, dormitories, nursing homes, hospitals, assisted living
Type A unitA117.1 Section 1103Accessible with some adaptable features (removable base cabinets, reinforcement)Apartments: 2% of units in larger R-2 sites
Type B unitA117.1 Section 1104Basic usability, consistent with the Fair Housing Accessibility GuidelinesEvery unit in most residential structures with four or more units

IBC 1108.2: units required to be Type A may be designed as Accessible units; units required to be Type B may be designed as Accessible or Type A units. A higher type always satisfies a lower requirement.

Accessible spaces (1108.3): Rooms and spaces available to the general public or to residents and serving Accessible, Type A or Type B units are accessible, including toilet and bathing rooms, kitchens, living and dining areas and exterior spaces such as patios, terraces and balconies (exceptions: stories exempted by 1108.4, recreational facilities per 1111.2, and impervious Type B decks or balconies up to 4 in. below the interior floor).

Accessible route (1108.4): At least one accessible route connects accessible entrances with the primary entrance of each Accessible, Type A and Type B unit and with the spaces serving them. Exceptions include site conditions outside the owner's control (a vehicular route with complying parking may substitute), I-3 and R-2 buildings where the required units and all common and public areas are on an accessible route, R-1 multistory units with an accessible level meeting Accessible-unit criteria, and stories exempted under 1108.7.

Group I Scoping (1108.5)

FacilityAccessible unitsType B units
I-1 Condition 14%, not less than oneEvery unit in structures with four or more residential units
I-1 Condition 210%, not less than oneSame
I-2 nursing homes50% of each type, not less than oneSame
I-2 general hospitals, psychiatric and detoxification10%, not less than oneSame
I-2 rehabilitation (mobility)100%-
I-33% of sleeping units, not less than one per classification level, plus one per special-purpose cell type-

In I-1 and I-2 facilities, a portion of the Accessible units (50% or 90% as listed) may use assisted-toileting water closets (IBC 1110.2.2) and assisted-bathing roll-in showers (1110.2.3) instead of the standard A117.1 fixtures.

Group R Scoping (1108.6)

R-1 (hotels, motels, transient boarding houses)

Accessible units per Table 1108.6.1.1, dispersed among classes of units:

Total unitsWithout roll-in showersWith roll-in showersTotal Accessible units
1 to 25101
26 to 50202
51 to 75314
76 to 100415
101 to 150527
151 to 200628
201 to 3007310
301 to 4008412
401 to 5009413
501 to 1,0002% of total1% of total3% of total
Over 1,00020, plus 1 per 100 over 1,00010, plus 1 per 100 over 1,00030, plus 2 per 100 over 1,000

On a multiple-building site, structures with more than 50 units are counted individually; structures with 50 or fewer units are counted together. The 2024 IBC adds exceptions where every unit has showers and none has a bathtub. Every R-1 unit intended to be occupied as a residence in a structure with four or more such units is a Type B unit. Small owner-occupied R-1 buildings with five or fewer units are exempt from Chapter 11 (1103.2.11).

R-2

R-2 typeRequirement
Live/work units (1108.6.2.1)Nonresidential portion accessible; residential portion Type B where four or more live/work units
Apartment houses, monasteries and convents (1108.6.2.2)More than 20 units: at least 2%, not less than one, Type A units, counting all R-2 units on the site (existing structures do not count) and dispersed; every unit in structures with four or more units is Type B
Other R-2 (dormitories, fraternities, sororities, congregate living, boarding houses) (1108.6.2.3)Accessible units per Table 1108.6.1.1; Type B in structures with four or more units; bedrooms count as sleeping units

R-3 and R-4

  • R-3 with four or more units intended as residences in a single structure: all Type B. The 2024 IBC also requires Accessible units per Table 1108.6.1.1 in transient R-3 congregate living facilities and boarding houses.
  • R-4 Condition 1: at least one Accessible sleeping unit; Condition 2: at least two; Type B in structures with four or more sleeping units.

Reducing Type A and Type B Counts (1108.7)

SectionRule
1108.7.1 No elevatorOnly units on stories described in 1108.7.1.1 and 1108.7.1.2 must be Type A and Type B. At least one story with an accessible exterior entrance has all its units Type B; additional stories qualify where the slope between their entrance and arrival points within 50 ft is 10 percent or less
1108.7.2 Multistory unitsA multistory unit without elevator service need not be Type B; with elevator service to one floor, that floor is the primary entry, complies as Type B and contains the living area, kitchen and toilet if provided
1108.7.3 Elevator to lowest residential story onlyOnly units on that story are Type B
1108.7.4 Site impracticalityOn multiple nonelevator buildings, the Type B count may drop to the percentage of the site with pre-development grades under 10 percent, but not below 20 percent, with additional conditions
1108.7.5 Flood hazard areasType A and B not required in nonelevator buildings where the required floor elevation is more than 30 in. above, and more than 10 percent slope from, arrival points within 50 ft

Worked Example

A new four-story R-2 apartment building with an elevator has 96 units; a second 24-unit building without an elevator stands on the same site.

  • Type A: the site has 120 R-2 units (more than 20), so 2% = 2.4, giving 3 Type A units, dispersed among unit types (and among the buildings where units qualify).
  • Type B, elevator building: all 96 units (any not Type A) are Type B.
  • Type B, nonelevator building: only units on the story with the accessible entrance (and any other qualifying story under 1108.7.1.2) must be Type B.
Test Your Knowledge

A new 180-room hotel (Group R-1) is being reviewed. How many Accessible units with roll-in showers does IBC Table 1108.6.1.1 require, and how many Accessible units in total?

A

2 with roll-in showers; 8 total

B

1 with roll-in showers; 6 total

C

2 with roll-in showers; 7 total

D

3 with roll-in showers; 10 total

Test Your Knowledge

A new apartment complex has three R-2 buildings with a total of 150 dwelling units on one site. How many Type A units does IBC 1108.6.2.2.1 require?

A

2

B

3

C

4

D

8

Test Your Knowledge

In a new Group I-2 nursing home, what portion of the sleeping units must be Accessible units under IBC 1108.5.2.1?

A

10 percent, the same rate as general-purpose hospitals

B

4 percent, the rate used for Group I-1 Condition 1

C

100 percent, as in rehabilitation facilities

D

50 percent, but not less than one, of each type