PracticeBlogFlashcardsEspañol
All Practice Exams

100+ Free NM Journeyman Electrician Practice Questions

Pass your New Mexico Journeyman Electrician License Exam (EE-98J) exam on the first try — instant access, no signup required.

✓ No registration✓ No credit card✓ No hidden fees✓ Start practicing immediately
~55% Pass Rate
100+ Questions
100% Free
1 / 100
Question 1
Score: 0/0

According to NEC Article 100, what is the definition of a "continuous load"?

A
B
C
D
to track
2026 Statistics

Key Facts: NM Journeyman Electrician Exam

70%

Passing Score

NM Electrical Bureau

80

Questions

PSI exam

EE-98J

Exam Code

NM Electrical Bureau

NEC 2020

Code Edition

NM Electrical Bureau

The New Mexico EE-98J journeyman electrician exam requires 70% to pass on 80 NEC-based questions in 4 hours. New Mexico uses the NEC 2020 edition and designates the journeyman license as EE-98J. The exam is open-book with a bound NEC allowed. NM requires 8,000 hours of apprenticeship experience.

Sample NM Journeyman Electrician Practice Questions

Try these sample questions to test your NM Journeyman Electrician exam readiness. Each question includes a detailed explanation. Start the interactive quiz above for the full 100+ question experience with AI tutoring.

1According to NEC Article 100, what is the definition of a "continuous load"?
A.A load where the maximum current is expected to continue for 3 hours or more
B.A load that operates 24/7
C.A load that exceeds 80% of the circuit rating
D.Any load powered by a dedicated circuit
Explanation: NEC Article 100 defines a continuous load as one where the maximum current is expected to continue for 3 hours or more. This affects conductor and overcurrent device sizing. New Mexico electricians working under NM Electrical Bureau must comply with NEC 2020 requirements.
2Per NEC Article 100, what does "listed" mean?
A.Equipment included in a list published by a qualified testing laboratory that evaluates products
B.Equipment approved by the local inspector
C.Equipment mentioned in the NEC articles
D.Equipment sold by licensed distributors
Explanation: NEC Article 100 defines "listed" as equipment included in a list published by an organization acceptable to the authority having jurisdiction that evaluates products. New Mexico electricians working under NM Electrical Bureau must comply with NEC 2020 requirements.
3Per NEC 110.26(A)(1), what is the minimum working space depth in front of electrical equipment for Condition 1, 0-150V?
A.36 inches (3 feet)
B.30 inches
C.42 inches
D.48 inches
Explanation: NEC Table 110.26(A)(1) requires 36 inches minimum depth for Condition 1 at 0-150V to ground. New Mexico electricians working under NM Electrical Bureau must comply with NEC 2020 requirements.
4Per NEC 110.14(C)(1), what temperature rating governs conductor terminations on equipment rated 100A or less?
A.60°C unless both the conductor and equipment are listed for a higher temperature
B.75°C is the standard for all terminations
C.90°C to maximize conductor ampacity
D.The conductor temperature rating always governs
Explanation: NEC 110.14(C)(1) requires using the 60°C ampacity column for circuits 100A or less, unless both the equipment and conductors are rated and listed for higher temperatures. New Mexico electricians working under NM Electrical Bureau must comply with NEC 2020 requirements.
5Per NEC 110.12, what general requirement applies to all electrical equipment installation?
A.Equipment must be installed in a neat and workmanlike manner
B.Equipment must be painted to match the building
C.All wiring must be concealed
D.Equipment must be labeled with installer information
Explanation: NEC 110.12 requires electrical equipment to be installed in a neat and workmanlike manner. Inspectors use this as a general quality standard. New Mexico electricians working under NM Electrical Bureau must comply with NEC 2020 requirements.
6Per NEC 110.3(B), what obligation exists regarding manufacturer instructions for listed equipment?
A.Listed equipment must be installed and used per its listing and any instructions included in the listing
B.Instructions are suggestions that can be disregarded
C.Only the NEC, not manufacturer instructions, must be followed
D.Instructions only apply during the warranty period
Explanation: NEC 110.3(B) mandates that listed or labeled equipment be installed and used in accordance with its listing instructions, making them enforceable code requirements. New Mexico electricians working under NM Electrical Bureau must comply with NEC 2020 requirements.
7What is the minimum headroom required for working spaces around electrical equipment per NEC 110.26(A)(3)?
A.6 feet 6 inches or the height of the equipment, whichever is greater
B.6 feet
C.7 feet
D.8 feet
Explanation: NEC 110.26(A)(3) requires minimum headroom of 6.5 feet or the height of the equipment, whichever is greater. New Mexico electricians working under NM Electrical Bureau must comply with NEC 2020 requirements.
8Per NEC 110.26(C)(2), when are two entrance doors required for an electrical room?
A.When equipment rated 1,200A or more and over 6 feet wide is installed
B.For any electrical room over 100 sq ft
C.When the room contains more than 3 panels
D.Two doors are never required
Explanation: NEC 110.26(C)(2) requires two entrance doors when equipment rated 1,200A or more is over 6 feet wide. New Mexico electricians working under NM Electrical Bureau must comply with NEC 2020 requirements.
9Per NEC 210.8(A), GFCI protection is required for 125V, 15- and 20-ampere receptacles in which dwelling unit locations?
A.Bathrooms, kitchens, garages, outdoors, crawl spaces, basements, laundry areas, and within 6 feet of sinks
B.Only bathrooms and kitchens
C.Bathrooms, garages, and outdoors only
D.All rooms in the dwelling unit
Explanation: NEC 210.8(A) lists numerous locations requiring GFCI including bathrooms, garages, outdoors, crawl spaces, basements, kitchens, laundry areas, and within 6 feet of sinks. New Mexico electricians working under NM Electrical Bureau must comply with NEC 2020 requirements.
10What is the maximum continuous load on a 20-ampere branch circuit per NEC 210.20(A)?
A.16 amperes (80% of 20A)
B.20 amperes
C.18 amperes
D.15 amperes
Explanation: NEC 210.20(A) requires the branch-circuit overcurrent device rating to be not less than 125% of the continuous load, so the maximum continuous load is 80% of 20A = 16A. New Mexico electricians working under NM Electrical Bureau must comply with NEC 2020 requirements.

About the NM Journeyman Electrician Exam

New Mexico's journeyman electrician exam (EE-98J) is administered by PSI on behalf of the NM Electrical Bureau. The exam tests NEC 2020 knowledge including wiring methods, grounding and bonding, load calculations, motor circuits, and special occupancies relevant to New Mexico installations.

Questions

80 scored questions

Time Limit

4 hours

Passing Score

70%

Exam Fee

$50-$75 (NM Electrical Bureau (PSI))

NM Journeyman Electrician Exam Content Outline

20%

NEC General & Definitions

NEC Article 100 definitions, general requirements, and code navigation

20%

Branch Circuits & Overcurrent Protection

Circuit sizing, conductor ampacity, GFCI/AFCI, and overcurrent devices

20%

Wiring Methods & Materials

Raceways, cable types, conduit fill, box fill, and desert-climate installations

20%

Grounding & Bonding

Article 250 grounding electrode systems, equipment grounding, and bonding

20%

Services, Motors & Special Occupancies

Service entrance, motor circuits, hazardous locations, healthcare, and swimming pools

How to Pass the NM Journeyman Electrician Exam

What You Need to Know

  • Passing score: 70%
  • Exam length: 80 questions
  • Time limit: 4 hours
  • Exam fee: $50-$75

Keys to Passing

  • Complete 500+ practice questions
  • Score 80%+ consistently before scheduling
  • Focus on highest-weighted sections
  • Use our AI tutor for tough concepts

NM Journeyman Electrician Study Tips from Top Performers

1Study NEC 2020 specifically — New Mexico has not adopted the 2023 edition yet
2Master Article 250 grounding and bonding thoroughly — it is the most tested section
3Know dry-climate installation considerations for New Mexico's desert environment
4Practice load calculations for residential and commercial projects using Article 220
5Review swimming pool and spa wiring requirements in Article 680 — common in NM

Frequently Asked Questions

What is the EE-98J designation in New Mexico?

EE-98J is New Mexico's designation for the journeyman electrician license. The 'EE' stands for Electrical Examination, '98' refers to the exam form, and 'J' indicates journeyman level. This is the standard journeyman exam administered by PSI.

What NEC edition does New Mexico use?

New Mexico currently uses the NEC 2020 edition for the journeyman electrician exam. The state has not yet adopted NEC 2023. A bound copy of the NEC 2020 is allowed during the test.

How much does the NM electrician exam cost?

The total cost ranges from $50-$75 including the PSI exam fee and state application fee. License renewal fees are separate. Contact the NM Electrical Bureau for the current fee schedule.

What experience is required in New Mexico?

New Mexico requires 8,000 hours (approximately 4 years) of electrical apprenticeship or equivalent experience under a licensed journeyman or master electrician. Experience must be documented on the state application.