13.3 Phase Sequence, Voltage Drop & Additional Functional Testing
Key Takeaways
Regulation 643.9 requires phase sequence to be maintained at relevant points in a polyphase installation. Dead inspection of conductor identification can establish this; live phase-rotation testing is used where needed for the equipment and safe commissioning.
Table 4 Ab gives informative voltage-drop guidance from the origin:3% lighting and 5% other uses for a public LV supply,6% and 8% for a private LV supply. Check actual equipment requirements and supply voltage; these are not guaranteed minimum terminal voltages.
Where appropriate, verify voltage drop by calculation or measurement. Use design current, the relevant cable data and operating temperature; a simple measured-resistance calculation also needs its reactance/power-factor assumptions assessed.
Functional testing under Regulation 643.10 mandates operational verification of assemblies, switchgear, controlgear, interlocks, emergency stop controls, and protective devices without relying on computational models.
Functionally test emergency stopping for the intended safe response: Category 0 removes power immediately; Category 1 uses a controlled stop before power removal. Resetting must only permit a deliberate restart, never cause one. Emergency stop is not isolation for maintenance.
13.3 Phase Sequence, Voltage Drop & Additional Functional Testing
Core Testing Principle: Initial verification and periodic inspection extend beyond dead continuity and earth loop impedance to encompass operational integrity. Under BS 7671, three distinct verifications confirm overall system functionality: Regulation 643.9 requires maintained phase sequence at relevant polyphase points;643.11 addresses voltage-drop verification where appropriate; and 643.10 requires functional testing of applicable assemblies, controls and interlocks.
Phase Sequence Testing on Polyphase Systems (Regulation 643.9)
In three-phase electrical distribution systems (400 V line-to-line, 230 V line-to-neutral), three sinusoidal voltage waveforms are generated with an electrical phase displacement of 120° (2π / 3 radians):
BALANCED THREE-PHASE SUPPLY: SAME FREQUENCY,120° DISPLACEMENT
With L1 chosen as reference:
vL1=Vpk sin(ωt) vL2=Vpk sin(ωt−120°) vL3=Vpk sin(ωt−240°)
Maintaining L1/L2/L3 identification preserves this sequence.
A motor’s required physical rotation also depends on its terminals
and the viewing direction specified by its manufacturer.
The Standard Harmonized Sequence
Under BS 7671, the harmonized phase conductors are designated:
- Line 1 (): Brown
- Line 2 (): Black
- Line 3 (): Grey
- Neutral (): Blue
For the stated sequence, the corresponding waveform peaks occur120° apart in the order L1, L2, L3. This alone does not define clockwise shaft rotation for every machine or viewing direction.
Why Reversed Rotation Matters
Interchanging any two lines reverses the rotating field of a directly supplied three-phase induction motor. The driven equipment may then operate incorrectly: a pump may lose performance, a fan may deliver inadequate airflow, or machinery may move in an unintended direction. The actual consequences depend on the design; do not assume a universal impeller failure or time to seizure.
Verification and Commissioning
- Maintain identification: Inspect the L1/L2/L3 connections and identification at relevant points. This can verify phase sequence without unnecessary live testing.
- Live indication where needed: Use a suitable phase-sequence instrument complying with BS EN 61557-7 or providing equivalent performance and safety. Connect the specified leads to the identified lines under a justified safe procedure; do not infer conductor identity from arbitrary lead colours alone.
- Interpret the indication: Compare the displayed sequence with the instrument instructions and intended circuit arrangement. A clockwise instrument indication is not proof of every connected motor’s required shaft direction.
- Check the equipment: Follow manufacturer commissioning instructions for a safe rotation check, including the specified viewing direction and controls. Correct a transposition only after safe isolation, then repeat the affected checks.
Verification of Voltage Drop (BS 7671 Regulation 643.11 & Appendix 4)
Every electrical cable possesses internal resistance and reactance. When load current circulates through circuit conductors, an electrical potential difference develops along the length of the run, reducing the voltage delivered to the terminal equipment.
Why Voltage Drop Matters
Low utilisation voltage can reduce motor starting torque, affect running performance and cause lighting or electronic equipment to malfunction. For the usual fixed-frequency induction-motor approximation, starting torque varies with voltage squared:0.9²=0.81, a19% reduction. Whether that prevents starting depends on the motor and load; it is not an automatic catastrophic outcome.
Table 4 Ab Voltage-Drop Guidance
Regulation 525.1 requires the equipment requirements to be considered. Table 4 Ab in Appendix 4 gives informative values from the installation origin to a load point:
| LV supply | Lighting | Other uses | At 230 V:lighting/other | At 400 V:lighting/other |
|---|---|---|---|---|
| Direct public supply | 3% | 5% | 6.9 V /11.5 V | 12 V /20 V |
| Private LV supply | 6% | 8% | 13.8 V /18.4 V | 24 V /32 V |
These are design guidance, not statutory voltage thresholds. Check the actual equipment tolerance and supply voltage: subtracting 11.5 V from nominal 230 V does not guarantee218.5 V at the load, since the voltage at the origin can already be below 230 V. Private-transformer guidance likewise does not guarantee satisfactory equipment operation.
Methods of Voltage Drop Verification (Regulation 643.11)
Where voltage drop needs verification,643.11 permits calculation or measurement. Use the appropriate method for the circuit and equipment:
Method 1: The Design Calculation Method
In initial verification, because full operational design load is rarely connected at the time of testing, voltage drop can be assessed by calculation using the tabulated millivolt-per-amp-per-metre values from BS 7671 Appendix 4:
Where:
- : Tabulated voltage drop figure for the cable type, cross-sectional area, and installation method (from BS 7671 Tables 4D1B to 4J4B).
- : Circuit design current in amperes (NOT the protective device rating !).
- : Single-way route length of the circuit in metres.
- : Divisor converting millivolts to volts.
Worked Example: A single-phase radial circuit wired in flat twin-and-earth cable with 70°C thermoplastic insulation () supplies a 16 A design load () over a run length of 32 metres: For a public 230 V power circuit, the5%guidance value is 11.5 V. The calculated 9.22 V is within that value. Confirm the selected cable data/temperature basis and actual equipment voltage requirement; this calculation alone does not establish complete circuit compliance.
Method 2: The Direct Measurement / Impedance Method
- Direct Operational Measurement: Measuring the line-to-neutral voltage at the distribution board origin () and simultaneously measuring terminal voltage at the furthest load () while the circuit is operating under full steady-state design load (). The difference represents the actual operating voltage drop ().
- Line-Neutral Impedance Derivation: Measuring the dead continuity resistance of the line conductor plus the neutral conductor to the furthest point using a low-resistance ohmmeter. For a predominantly resistive single-phase circuit, adjust the resistance to the relevant operating temperature before using: This approximation needs refinement where reactance and load power factor are significant. A cold continuity value used without the necessary temperature assessment can understate operating voltage drop.
Functional Testing of Assemblies & Controls (Regulation 643.10)
Under BS 7671 Regulation 643.10, assemblies such as switchgear and controlgear assemblies, drives, controls, and interlocks must be subjected to functional testing to verify that they are correctly mounted, configured, and operate in accordance with relevant equipment standards and design specifications.
THE SCOPE OF FUNCTIONAL TESTING
┌────────────────────────────────────────────────────────────────────────┐
│ 1. SWITCHGEAR & ISOLATORS │
│ • Positive mechanical break, smooth handle action, flag indicators │
│ • Verify provided interlocks against the actual assembly design │
├────────────────────────────────────────────────────────────────────────┤
│ 2. EMERGENCY STOPPING CONTROLS (BS EN ISO 13850 / Reg 537.3.3) │
│ • Actuation initiates the specified safe stop category │
│ • Latching mechanism holds in OFF position; NO AUTOMATIC RESTART! │
├────────────────────────────────────────────────────────────────────────┤
│ 3. AUTOMATION & CONTACTORS │
│ • Motor starters, hold-in coils, thermal overloads, interlocks │
│ • Time clocks, photocells (dusk-to-dawn), PIR occupancy sensors │
├────────────────────────────────────────────────────────────────────────┤
│ 4. INTEGRAL PROTECTIVE DEVICE TEST CONTROLS │
│ • RCD / RCBO push-to-test buttons ('T') │
│ • AFDD manual test facility where provided; follow maker instructions │
└────────────────────────────────────────────────────────────────────────┘
1. Switchgear, Disconnectors & Interlocks
- Switching and isolation function: Operate the applicable devices to verify smooth operation, required pole disconnection and correct position indication for their intended function. Check device suitability and manufacturer instructions; do not assume every switch performs isolation.
- Enclosure interlocks: Where provided, verify the intended door/switch interlock and any controlled override against the assembly instructions. Industrial assemblies do not all use one identical door mechanism. Apply the required barriers and safe-access procedure.
2. Emergency Stopping Controls (BS EN ISO 13850 & Regulation 537.3.3)
Test the installed emergency-stopping system safely against the machine’s intended design and instructions, controlling the hazards created by the test:
[!CRITICAL]
Mandatory Emergency Stop Operational Rules
- Specified safe stop: Category 0 removes power immediately; Category 1 first performs a controlled stop and then removes power. A Category 1 system must not be judged defective merely because it maintains power during controlled deceleration.
- Maintained stop command: Check the actuator’s latching and deliberate manual-reset function in accordance with its design. The stopping command remains effective until properly reset.
- No automatic restart: Resetting must only permit a subsequent deliberate restart; it must not start the machine. Verify the intended restart controls and safe conditions. An emergency stop is not safe electrical isolation for maintenance.
For 230 V final circuits supplied directly from a public LV network, what voltage-drop guidance does BS 7671 Table 4 Ab give for lighting and other uses, subject to actual equipment requirements?
5.0% (11.5 V) for lighting and 3.0% (6.9 V) for socket outlets
4.0% (9.2 V) for lighting and 4.0% (9.2 V) for socket outlets
3.0% (6.9 V) for lighting and 5.0% (11.5 V) for socket outlets
6.0% (13.8 V) for lighting and 8.0% (18.4 V) for socket outlets
Why should the intended phase sequence and safe equipment rotation be confirmed when commissioning a directly supplied three-phase induction-motor pump?
The motor line-to-line supply voltage will increase from 400 V to 690 V, puncturing winding insulation
The motor will draw zero active power and fail to generate any internal magnetic flux
The circuit protective conductor will carry the full motor full-load running current back to the MET
Interchanging two lines reverses the motor’s rotating field and can make the pump run in the wrong direction, impairing performance or damaging equipment depending on its design
When functionally testing an emergency stop control system under BS 7671 Regulation 643.10 and BS EN ISO 13850, which operational sequence is mandatory upon resetting the latched emergency stop pushbutton?
Resetting must only permit a subsequent deliberate restart; it must not itself restart the machinery
The machinery must immediately re-start automatically to resume continuous production without operator intervention
The control circuit must sound an audible evacuation siren for 30 seconds before automatically re-applying power to the motor
The upstream main circuit breaker must automatically trip to the open position to enforce a lockout