7.2 EICR Classification Coding: Code C2 (Potentially Dangerous)
Key Takeaways
Code C2 is defined under BS 7671 Regulation 653.2 and Electrical Safety First Best Practice Guide 4 as 'Potentially dangerous. Urgent remedial action required.'
The defining criterion for Code C2 is the 'single-fault condition': the installation is safe during undisturbed normal operation, but will expose occupants to immediate danger upon the occurrence of a single secondary fault or foreseeable event.
Examples of C2 include no effective earthing, missing required bonding to extraneous-conductive-parts, failure to meet the applicable ADS disconnection time, and missing 30 mA RCD protection for mobile equipment reasonably expected to be used outdoors.
Inadequately supported wiring is C2 where premature collapse in fire would hinder evacuation or firefighting. Regulation 521.10.202 applies throughout the installation; classification depends on the resulting risk, not simply the presence of plastic clips.
Any single Code C2 observation automatically mandates an overall 'UNSATISFACTORY' assessment on the EICR, requiring the duty holder to commission urgent remedial rectification.
7.2 EICR Classification Coding: Code C2 (Potentially Dangerous)
Core Regulatory Benchmark: BS 7671 Regulation 653.2 and Electrical Safety First Best Practice Guide 4 define Code C2 as: 'Potentially dangerous. Urgent remedial action required.' While not presenting an immediate risk of shock or fire at the instant of inspection, a Code C2 defect signifies that the installation's protective safeguards have been compromised, such that a single foreseeable fault will create imminent, severe danger.
In electrotechnical condition reporting under the EAL Level 3 Inspection and Testing qualification framework (specifically Unit QCRB/001 and Unit QCR/001), mastering the distinction between Code C1 and Code C2 is the single most critical evaluative skill. Misclassifying a C1 as a C2 leaves occupants exposed to active lethal hazards without immediate intervention, while over-coding a C3 as a C2 imposes unwarranted financial and legal burdens on the duty holder.
The Concept of the Single Fault Condition
The bedrock engineering principle underlying Code C2 is the single-fault condition (failure of basic protection or failure of fault protection):
+---------------------------------------------------------------------------------------------------+
| THE CODE C2 SINGLE-FAULT THRESHOLD |
+---------------------------------------------------------------------------------------------------+
| NORMAL RESTING STATE (Undisturbed) -----> SINGLE FORESEEABLE EVENT / FAULT |
| - Enclosure closed; basic insulation - Insulation breaks down inside Class I metal |
| intact. kettle, motor, or luminaire, OR |
| - No person actively shocked right now. - DNO PEN conductor breaks on PME supply, OR |
| - NO IMMEDIATE DANGER. - Fire occurs in building corridor. |
| |
| CONSEQUENCE OF COMPROMISED SAFEGUARD: |
| - Earth path absent -> Metalwork stays at 230 V |
| - Zs too high -> Protective device fails to trip |
| - Plastic clips melt -> Cables collapse & trap |
| - POTENTIALLY DANGEROUS -> CODE C2! |
+---------------------------------------------------------------------------------------------------+
Under BS 7671 Chapter 41, safety against electric shock relies on the coordination of Basic Protection (preventing direct contact with live parts) and Fault Protection (preventing dangerous touch voltages on exposed conductive parts during an earth fault via Automatic Disconnection of Supply, ADS).
When fault protection is absent, severely impaired, or uncoordinated, the installation sits in a latent, primed state of hazard. The moment an everyday electrical appliance suffers internal insulation degradation, or a utility neutral is disrupted, the lack of fault protection transforms the latent condition into an active, lethal touch voltage (). Because single electrical insulation faults are normal, statistically predictable occurrences over the lifetime of an installation, compromised fault protection represents an unacceptable risk requiring urgent remedial action.
Comprehensive Real-World Code C2 Defects
Inspectors must apply rigorous technical benchmarks when identifying Code C2 conditions across electrical infrastructure:
Code C2 Defect Classification Matrix
| Defect / Non-Compliance | Relevant BS 7671 Regulation | Technical Engineering Justification |
|---|---|---|
| Absence of a reliable supply earth connection (main earthing conductor disconnected, absent, or severed) | Reg 411.3.1.1 / 542.1 | Automatic Disconnection of Supply (ADS) cannot function. In the event of an earth fault on any Class I equipment, the exposed metalwork remains permanently energized at line voltage. |
| Missing required main protective bonding to an extraneous-conductive-part entering the building | Reg 411.3.1.2 / 544.1 | A pipe that can introduce earth potential requires effective bonding. Missing bonding permits dangerous potential differences under fault conditions. Bonding reduces differences within the installation; it does not hold all PME metalwork at true-earth potential during an open PEN. |
| Earth fault protection cannot disconnect within the applicable required time | Reg 411.3.2 / applicable device data | Check the governing device, circuit and earthing system, including temperature correction. An excessive overcurrent-device loop value is not automatically C2 where effective RCD fault protection satisfies the applicable requirements. |
| Inadequate wiring support where premature collapse in fire would hinder evacuation or firefighting | Reg 521.10.202 | Loss of support can leave cables across escape or firefighting routes, creating an entanglement hazard. Adequate fire-resistant retention is needed for the system. |
| Socket-outlets supplying mobile equipment outdoors without 30 mA RCD protection | Reg 411.3.3 | Equipment used outdoors (lawn mowers, pressure washers, power tools) carries an extreme probability of severed flexes and direct human contact with wet earth. Failure to provide 30 mA RCD additional protection creates severe shock/electrocution risk. |
| Damaged enclosure leaving intact basic-insulated cores accessible and vulnerable to damage | Basic and mechanical protection | Foreseeable abrasion or impact could expose live metal, creating potential danger: C2. If hazardous live metal is already accessible, assess C1 instead. A hole size alone does not establish either code. |
| Inadequate overload protection for a conductor’s current-carrying capacity | Reg 433.1.1 | Verify and , with any applicable special conditions. An oversized protective device can permit damaging overheating under sustained overload, creating potential fire danger. |
| Absence of Circuit Protective Conductor (CPC) on circuits supplying Class I metal luminaires or switches | Reg 411.3.1.1 | Class I metal light fittings without an earth connection will become energized at 230 V upon a single internal wiring fault. Occupants operating the switch or touching the fitting face direct shock. |
| RCD failing to operate when tested at rated residual current () where relied upon for fault protection (e.g. TT earthing system) | Reg 411.5.2 | On a TT system, the earth electrode resistance () is too high for overcurrent devices to operate on earth faults. If the RCD fails to trip, fault protection is completely absent. |
Deep Dive: Earth Fault Loop Impedance () & Disconnection Failure
One of the most frequent examination scenarios in EAL Level 3 testing involves the evaluation of measured values against maximum permitted values in BS 7671 Tables 41.2, 41.3, and 41.4.
Temperature Correction and the Governing Protective Device
Chapter 41 loop limits must be compared with results on a consistent temperature basis. For cold conductors, Appendix 3 gives the simplified sufficient check:
For a Type B 32 A circuit-breaker with a tabulated maximum of , this gives . Do not apply the factor again to a reference value already adjusted for measurement temperature. Exceeding the simplified figure calls for assessment using the applicable temperature-adjusted limit and device data; it does not by itself prove that ADS fails. Identify the required time for the actual circuit and earthing arrangement.
- Without RCD fault protection: For the TN socket circuit considered here, the applicable maximum is and the required disconnection time is 0.4 s. A measured already exceeds that limit. At nominal voltage: This is about , within the Type B magnetic tolerance band of –. The device might trip magnetically, but the guaranteed operating current used for the tabulated limit is . The measurement does not establish the required protection; do not predict a definite thermal-only trip or a precise delay. With failure against the applicable protection criteria established, classify C2.
- With RCD fault protection: Regulation 411.4.204 permits Table 41.5 to be applied on TN systems. Its 30 mA value is , derived from the 50 V basis. A circuit is not C2 merely because it exceeds the MCB loop limit if effective RCD fault protection satisfies the governing requirements. Verify protective-conductor continuity, correct RCD selection and operation, and overcurrent/short-circuit protection; a high loop reading can still indicate a real connection defect.
HIGH MEASURED Zs
|
v
Check result, circuit, required time, device and temperature basis.
|
+--> Applicable overcurrent-device protection meets the time?
| Yes: no C2 solely for failing a simplified 0.8 screen.
|
+--> Effective RCD fault protection meets its requirements?
| Yes: assess continuity and other protection/connection defects.
|
+--> Required fault protection is not effective: C2, urgent action.
Regulation 521.10.202: Premature Collapse in Fire
Introduced in the 18th Edition of BS 7671 and reinforced in BS 7671:2018+A4:2026, Regulation 521.10.202 states:
'Wiring systems shall be supported such that they will not be liable to premature collapse in the event of fire.'
This regulation applies across the entire installation, not merely designated escape routes. Historically, non-metallic cable clips, plastic wall plugs, and plastic mini-trunking were standard installation methods. In multiple tragic fire events (notably the Shirley Towers fire in Southampton and Harrow Court in Stevenage), firefighters navigating smoke-logged premises became entangled in fallen overhead electrical cables, leading to line-of-duty fatalities.
EICR Classification Criteria for Regulation 521.10.202:
- Code C2 (Potentially Dangerous): Cables clipped to surfaces, suspended above false ceilings, or running along corridors and doorways supported exclusively by plastic clips, plastic trunking, or plastic ties where falling cables would block escape routes or trap firefighters.
- Rectification: Provide sufficient fire-resistant retention with suitable clips, bands, ties or other supports and anchors for the substrate. Select spacing for cable weight, route, load and the support manufacturer’s instructions; there is no universal 300–400 mm fixing interval. Other supports may remain where adequate fire retention is provided.
Impact on Overall EICR Assessment & Duty Holder Obligations
Like Code C1, the presence of one or more Code C2 observations automatically results in an overall 'UNSATISFACTORY' assessment on the Electrical Installation Condition Report.
Statutory Duties Depend on the Setting
An EICR outcome does not create one UK-wide 28-day repair rule. C1 needs immediate action and C2 urgent action appropriate to the danger. Workplace duty holders must comply with EAWR; the risk governs the response.
For a specified tenancy covered by England’s private and social rented-sector regulations, Regulation 3(4) applies where the report indicates an actual or potential breach of the electrical safety duty and requires investigative or remedial work. A qualified person must carry it out within 28 days of the inspection and testing, or the shorter period specified. This can include investigation despite an A4 technically satisfactory report. Obtain the qualified person’s written confirmation, and supply it with the original report to existing tenants and the local housing authority within 28 days of completion. An EIC or Minor Works certificate is appropriate where the work requires it; the statutory confirmation is not limited to those certificate types.
Comparison: Code C1 vs Code C2 Response Protocols
| Attribute | Code C1 (Danger Present) | Code C2 (Potentially Dangerous) |
|---|---|---|
| Current State | Actively dangerous right now | Potentially dangerous (requires secondary fault) |
| Action Urgency | Immediate remedial action required | Urgent remedial action required |
| Notification | Immediately notify the person ordering the work and confirm the danger in writing | Clearly report the observation and need for urgent action |
| Circuit Isolation | Seek client permission to isolate/lock off immediately | Advise duty holder to schedule urgent repairs without delay |
| EICR Outcome | UNSATISFACTORY | UNSATISFACTORY |
| Legal Context | Immediate danger requires action under the applicable safety duties | Potential danger requires urgent action under the applicable safety duties; the code alone is not a statutory-compliance certificate |
Worked Practical Case Studies: Code C2 in Practice
Case Study 1: Missing Main Protective Bonding to Gas Service
- Scenario: An inspector performs an EICR on a PME domestic installation. The incoming metallic gas pipe is confirmed to be an extraneous-conductive-part, but no effective main protective bonding exists. The main earthing connection is sound. Bonding is required under Regulation 411.3.1.2.
- Analysis: Missing required bonding permits a dangerous potential difference between the extraneous pipe and electrical exposed-conductive-parts under fault conditions. Bonding limits that difference within the equipotential zone; it does not guarantee that PME-connected parts remain at true-earth potential during an open-PEN event. The observed missing safeguard creates potential danger rather than proving present danger.
- Classification: Code C2 (Potentially dangerous. Urgent remedial action required.)
- Procedure: Record C2 in Section K, identify the missing required bonding and advise urgent repair. Determine the conductor size from the applicable Regulation 544.1 requirements and, for PME, Table 54.8 and the distributor’s conditions, rather than assuming 10 mm² in every case. Declare the overall condition UNSATISFACTORY.
Case Study 2: Measured Exceeding Maximum Limit Without RCD
- Scenario: During testing of a 32 A radial socket circuit wired in 4.0 mm² / 1.5 mm² PVC cable protected by a 32 A Type B MCB on a TN-S supply, measured at the furthest socket is . The maximum permitted in BS 7671 Table 41.3 is . The circuit has no RCD protection.
- Analysis: At nominal voltage the estimated current is , below the guaranteed magnetic operating current used for the tabulated limit. Since this lies within the Type B tolerance band, a magnetic trip is possible, but protection within 0.4 s has not been established against the applicable limit. Do not assert a definite thermal delay from that calculation.
- Classification: Code C2 (Potentially dangerous. Urgent remedial action required.)
- Procedure: The inspector documents the defect as Code C2 on the EICR, explains that the required 0.4 s disconnection has not been established and fault protection needs correction, and issues an UNSATISFACTORY overall condition assessment.
During periodic testing of a 32 A Type B MCB final ring circuit on a TN-C-S supply, the measured earth fault loop impedance (Zs) is recorded as 1.95 Ω. The maximum permitted Zs in BS 7671 Table 41.3 is 1.37 Ω, and the circuit has no RCD protection. How must this observation be classified on the EICR?
Code C1 (Danger Present), because the circuit breaker will trip immediately upon load connection.
Code C2 (Potentially Dangerous), because the measured result does not satisfy the applicable fault-protection limit for the required 0.4 s disconnection time.
Code C3 (Improvement Recommended), because the circuit operates satisfactorily under normal load conditions and MCB overload protection remains intact.
Code FI (Further Investigation Is Advised), because the inspector must dismantle all socket-outlets along the ring to find where the resistance originated.
Which of the following physical installation conditions represents a Code C2 (Potentially Dangerous) defect rather than a Code C1 or Code C3?
Missing required main protective bonding to a gas service confirmed to be an extraneous-conductive-part on a PME installation.
Absence of SPDs in an existing installation where their addition is recommended under the applicable BPG 4 C3 criteria.
Exposed live copper busbar prongs inside a consumer unit due to a missing blanking plate.
An undamaged plastic domestic consumer unit installed under a wooden staircase in 2012.
An EICR finds one corridor lighting circuit supported solely by plastic clips. Premature collapse in fire would leave cables across the evacuation and firefighting route, creating an entanglement hazard (Regulation 521.10.202). All other circuits are sound. What is the overall outcome?
The overall assessment is declared 'Satisfactory' because 95% of circuits comply with BS 7671.
The overall assessment is declared 'Satisfactory with Advisory Notes' because fire safety falls under the Regulatory Reform (Fire Safety) Order rather than BS 7671.
The overall assessment is declared 'UNSATISFACTORY' because a single Code C2 observation mandates an overall unsatisfactory condition.
The overall assessment is deferred under Code FI until the local Fire and Rescue Service inspects the premises.
During periodic testing of an installation with a TT earthing system, the main 100 mA time-delayed RCD providing fault protection fails to trip when tested at rated residual current (1x IΔn). Earth electrode resistance (RA) is measured as 42 Ω. How must this observation be classified?
Code C1 (Danger Present), because the earth electrode is energized continuously at mains voltage.
Code C2 (Potentially Dangerous), because the RCD relied upon for TT fault protection has failed and the required automatic disconnection is not effective.
Code C3 (Improvement Recommended), because the installation functioned correctly prior to the test.
Code FI (Further Investigation Is Advised), because the inspector must excavate the earth rod to investigate soil resistivity.