Cheat sheet

EAL Level 3 Inspection & Testing Cheat Sheet

Practice Questions

Health and Safety

7%of exam

Safe IsolationEAWR 1989GS38 EquipmentLock OffProve Test Prove

Requirements for Inspecting and Testing

21%of exam

Safe Inspection

20%of exam

EICR Classification CodingIP RatingsConcealed CablesAFDD RequirementsSafety Notices

Safe Testing

52%of exam

Quick Facts

Awards
3 related Level 3 EAL awards
600/4337/4
55 Qs, 90 min, pass 62%
603/2625/6
60 Qs, 120 min, pass 61.5%
600/4338/6
Bridging 35Q + QCR/001 exam
Format
Open book, MCQ, GN3 only
Standard
BS 7671 A4:2026, current edition
GN3 edition
10th edition, since 15 Apr
Min age
16 for 4337/4, 18 others
Fees
£47, £50, £89 EAL only

Safe Isolation Sequence

Isolate, lock off, prove, test dead, prove again

Isolate: switch off circuitLock off: retain key or fuseProve: tester on live sourceTest: confirm circuit deadProve again: tester still works

Statutory & Standards

EAWR 1989
Statutory legal duty
Reg 4 EAWR
Prevent danger, reasonably practicable
BS 7671
Non-statutory wiring standard
A4:2026
Current edition, published 15 Apr
A2/A3
Withdrawn 15 Oct 2026
Orange Book
Nickname for A4:2026
IET GN3
Only listed exam reference
HSG85
HSE safe isolation guidance

Safe Isolation

Prove-test-prove
Check indicator before and after
Proving unit
Battery device simulates live supply
Lock off
Retain key, not just switch
Caution notice
Warns, doesn't secure alone
Fuse removal
Alternative to locking device off
GS38 probe
Test lamp or two-pole tester

EIC vs EICR

EIC

  • New work only
  • Certifies BS 7671 compliance
  • No classification codes

EICR

  • Existing installation only
  • Assesses condition safety
  • Uses C1/C2/C3/FI codes

New work vs existing condition

Certificate Picker

  1. New circuit added→EIC(Full new-work certificate)
  2. No new circuit added→MEIWC(Minor works only)
  3. Existing installation condition check→EICR(Condition report only)
  4. Consumer unit replaced→EIC(New CU triggers EIC)
  5. Socket added to circuit→MEIWC(Alteration, no new circuit)
  6. Rented property inspection due→EICR(5-year legal maximum)

Certification Documents

EIC
Certifies new work only
MEIWC
Minor works, no new circuit
EICR
Condition report, existing installation
Schedule of Inspections
Visual, physical checks recorded
Schedule of Test Results
Measured values per circuit
Signatories
Design, construction, inspect and test
Departures
Recorded intended deviations from BS7671

EICR Scope & Notices

Extent
Parts of installation covered
Limitations
Excluded items, reasons, agreed with
Reg 514.12.1
Next inspection date notice
Reg 514.12.2
RCD six-monthly test notice
PRS interval
5 years max, rented homes
GN3 intervals
Guidance only, inspector adjusts

EICR Code Meanings

C1 danger, C2 urgent, C3 improve, FI investigate

C1: immediate danger presentC2: potentially dangerous, urgentC3: improvement recommended, safeFI: further investigation advised

C1 vs C2

C1

  • Danger present now
  • Immediate remedial action
  • e.g. exposed live parts

C2

  • Potentially dangerous fault
  • Urgent remedial action
  • e.g. no effective earthing

Immediate vs urgent action

EICR Code Picker

  1. Exposed live conductor found→C1(Danger present now)
  2. No effective earthing found→C2(Potentially dangerous fault)
  3. Non-dangerous shortfall found→C3(Improvement recommended only)
  4. Suspected but unconfirmed fault→FI(Further investigation advised)
  5. Only C1 or C2 present→Unsatisfactory(Overall EICR outcome)
  6. Only C3 or FI present→Satisfactory(Overall EICR outcome)

Safe Inspection Checks

Reg 642.1
Inspection precedes testing, disconnected
IPXXB/IP2X
General live-parts protection
IPXXD/IP4X
Top surface, higher protection
Cable <50mm deep
Safe zone plus 30mA RCD
Reg 522.6.202
Concealed cable protection rule
Reg 421.1.7
AFDD mandatory, 4 premises types
514.13.1 label
Do Not Remove, earth connection

C3 vs FI

C3

  • Non-dangerous shortfall
  • Improvement recommended only
  • Never makes report unsatisfactory

FI

  • Suspected unconfirmed problem
  • Further investigation advised
  • Also never unsatisfactory alone

Confirmed defect vs unconfirmed suspicion

EICR Classification Coding

C1
Danger present, act immediately
C2
Potentially dangerous, urgent action
C3
Improvement recommended, not dangerous
FI
Further investigation advised
Unsatisfactory
Only C1 or C2 trigger
A4 change
FI dropped 'without delay' wording

Dead Test Order

Continuity -> Ring -> Insulation -> Polarity

Continuity: CPC and bondingRing: r1/rn/r2 checksInsulation: before polarity checkGN3 sets this order

R1+R2 vs R2 Only

R1+R2

  • Link line and CPC
  • Linked at far end
  • Standard method used

R2 only

  • Long wander lead used
  • Ends not linked
  • Impractical far-end access

Linked ends vs wander lead

RCD Test Picker

  1. General non-delay RCD fitted→Test at IΔn(Max 300ms disconnection)
  2. S-type time-delayed RCD fitted→Test at IΔn(130 to 500ms band)
  3. Any RCD type checked→Alternating test current(No x5 test needed)
  4. TT system earth checked→RA x IΔn rule(Must not exceed 50V)
  5. Additional protection required→30mA non-delay RCD(Not an S-type)
  6. RCD function verified onsite→Press integral test button(Confirms RCD still trips)

Continuity Testing

R1+R2
Line plus CPC, linked far end
R2 only
Wander lead, resistance nulled first
r1, rn, r2
Ring conductors, measured separately
Figure-of-eight
Cross-connected ring, socket readings
Spur reading
Reads higher than ring sockets

Zs Formula

Zs equals Ze plus R1+R2

Ze: external loop onlyZs: Ze + R1+R20.8x: temperature correction factorCompare cold reading only

Ze vs Zs

Ze

  • External loop only
  • Earthing conductor disconnected
  • Measured at origin

Zs

  • Total circuit loop
  • Ze plus R1+R2
  • Compared to 0.8x table

External only vs whole circuit

Insulation Resistance

Table 64
Sets minimum IR values
Up to 500V
500V DC test, min 1MΩ
New work extra test
250V DC if equipment connected
SPD caution
Disconnect before 500V DC test
Low reading
Investigate near-minimum results

RCD Disconnection Bands

General 300ms max; S-type 130 to 500ms

General: single test at IΔnS-type: time-delayed, upstream positionTT rule: RA x IΔn 50VNo more x5 test

Type AC vs Type A

Type AC

  • Sinusoidal AC only
  • Fixed equipment only
  • No DC component

Type A

  • AC plus pulsating DC
  • Common with electronics
  • Modern default choice

No DC vs pulsating DC

Earth Loop & Zs

Ze
Origin, earthing conductor disconnected
Zs formula
Ze plus R1+R2
0.8 factor
Compares cold Zs to table
PFC/PSCC
Checks device breaking capacity
TT electrode rule
RA times IΔn under 50V

RCD Testing

IΔn test
Single alternating current check
General RCD
300ms max disconnection time
S-type RCD
130 to 500ms delay band
Type AC
Sinusoidal only, fixed equipment
Type A
Also trips pulsating DC
x5 test
No longer BS 7671 minimum

Disconnection & Polarity

Table 41.1
0.4s TN, 0.2s TT circuits
Distribution circuits
5s TN, 1s TT max
Reg 643.6
Polarity, fuse in line only
Reg 643.9
Phase sequence, three-phase check
Reg 643.10
Functional test, RCD button too

Test Instruments & Diagnosis

BS EN 61557
Test instrument performance standard
GS38 tip
Max 4mm, ideal 2mm
Multimeter fuse
500mA HBC, close to tip
Loop/RCD tester fuse
About 10A rating instead
High-resistance joint
Heat, voltage drop, intermittent fault
Reversed polarity
Line and neutral transposed danger

Common Traps

Amendment scope

A4 2026 is current standard ≠ A2 A3 withdrawn 15 Oct

RCD test count

Only IΔn test required now ≠ x5 test no longer required

Fee vs tuition

EAL fee is qualification only ≠ Centre tuition priced separately

Ze vs Zs scope

Ze excludes circuit conductors ≠ Zs includes R1+R2 total

Continuity method choice

R1+R2 links ends together ≠ R2-only uses wander lead

EIC vs MEIWC scope

EIC covers new circuits ≠ MEIWC covers no new circuit

C1 vs C2 urgency

C1 needs action before leaving ≠ C2 needs action, not immediate

Last Minute

  1. 1.GS38 tip max 4mm; ideal 2mm
  2. 2.RCD test = single check at IΔn
  3. 3.S-type RCD = 130-500ms delay band
  4. 4.Table 41.1: TN 0.4s, TT 0.2s
  5. 5.Distribution circuits: 5s TN, 1s TT
  6. 6.Insulation test = 500V DC, min 1MΩ
  7. 7.EIC = new work; EICR = condition report
  8. 8.C1 or C2 alone = unsatisfactory EICR
  9. 9.Prove-test-prove: check indicator before and after
  10. 10.Secure isolation = lock off, not switch
  11. 11.Inspection precedes testing per Reg 642.1
  12. 12.Compare measured Zs to 0.8x table
  13. 13.AFDD mandatory in 4 premises types
  14. 14.Pre-A4 BS 7671 withdrawn 15 Oct