12.3 The 0.8 Temperature Correction Rule & Maximum Permitted Zs

Key Takeaways

  • Conductor resistance increases with temperature; tests performed at ambient room temperatures (~20°C) with cold conductors must be corrected before comparison against BS 7671 maximum permitted Zs values calculated for maximum operating temperatures (70°C).

  • BS 7671 incorporates a voltage factor Cmin = 0.95 into loop impedance formulas to account for supply voltage drop under network fault conditions (230 V × 0.95 = 218.5 V).

  • The 0.8 quick screen compares the measured loop with 0.8 of the applicable operating-temperature limit. Its exact algebraic inverse is measured Zs×1.25≤table limit. A component-temperature calculation is a different assessment, not an equivalent ×1.20 rule.

  • For 230 V TN systems, Table 41.1 normally requires 0.4 s for final circuits up to 63 A with socket-outlets and up to 32 A supplying only fixed equipment. The usual limit for other circuits, including distribution circuits, is 5 s, subject to the applicable conditions.

  • Where the quick screen is exceeded, check the actual protective measure, valid limit/source and measurement conditions. A supported detailed temperature assessment may establish compliance; the simple screen alone is not the final verdict.

Last updated: November 2026

12.3 The 0.8 Temperature Correction Rule & Maximum Permitted Zs

Core Testing Principle: The maximum permitted ZsZ_s values tabulated in BS 7671 assume that cable conductors are operating at their maximum permitted operating temperature (70∘C70^\circ\text{C} for standard thermoplastic PVC). However, initial verification and periodic testing are performed on de-energised or lightly loaded cables at ambient room temperature (typically ∼20∘C\sim 20^\circ\text{C}). For a quick conservative assessment, compare ambient measurements with 80% (0.8) of the applicable operating-temperature limit. A supported detailed assessment may be used where the simple screen is exceeded.


The Physics of Conductor Temperature & Resistance

Copper is a metallic conductor possessing a positive temperature coefficient of resistance (α\alpha). As conductor temperature increases, thermal vibrations of copper atoms within the crystal lattice impede electron flow, increasing electrical resistance:

Rθ=R20[1+α(θ−20)]R_{\theta} = R_{20} [1 + \alpha (\theta - 20)]

Where:

  • RθR_{\theta} = Conductor resistance at operating temperature θ\theta (∘C^\circ\text{C}).
  • R20R_{20} = Conductor resistance at standard reference ambient temperature (20∘C20^\circ\text{C}).
  • α\alpha = Temperature coefficient of copper at 20∘C20^\circ\text{C} (0.004/∘C0.004 / ^\circ\text{C} or 1/254.51 / 254.5).

Resistance Ratio fromAmbient to Full Load

For a standard70 °C thermoplastic cable,70 °C is the usual maximum continuous conductor temperature, not the inevitable temperature at every design load. Substituting this into the formula:

R70R20=1+[0.004×(70−20)]=1+[0.004×50]=1+0.20=1.20\frac{R_{70}}{R_{20}} = 1 + [0.004 \times (70 - 20)] = 1 + [0.004 \times 50] = 1 + 0.20 = 1.20

This proves that a copper cable conductor operating at its maximum design temperature (70∘C70^\circ\text{C}) has 20%20\% higher resistance than when cold at 20∘C20^\circ\text{C}.

  COPPER CONDUCTOR RESISTANCE: APPROXIMATE 20 °C TO 70 °C CHANGE
  At 20 °C: R20  ── temperature increase ──> At 70 °C: about 1.20 × R20

  This factor applies to the conductor resistance in the stated model.
  The complete fault-loop change also depends on the source and other components.

The Voltage Factor CminC_{\text{min}} (BS 7671 Appendix 3)

Under BS 7671, maximum earth fault loop impedance values are derived from Ohm's law:

Zs≤U0×CminIaZ_s \le \frac{U_0 \times C_{\text{min}}}{I_a}

Where:

  • U0U_0: Nominal line-to-earth AC voltage (230 V230\text{ V}).
  • CminC_{\text{min}}: Minimum voltage factor;0.95 for the usual LV supply in accordance with ESQCR.
  • IaI_a: The current causing automatic disconnection within the specified time (use the time required for the actual circuit and protective measure).

Why Cmin=0.95C_{\text{min}} = 0.95 is Mandatory

Although UK nominal voltage is declared at 230 V230\text{ V}, national supply regulations permit a lower tolerance of −6%-6\% (216.2 V216.2\text{ V}). Furthermore, when a massive short-circuit or earth fault occurs, the surge of current causes a temporary voltage drop across distribution transformers and service lines. To ensure the protective device operates even during severe grid voltage depression, BS 7671 scales the effective supply voltage down by 5%5\%:

U0×Cmin=230 V×0.95=218.5 VU_0 \times C_{\text{min}} = 230\text{ V} \times 0.95 = 218.5\text{ V}


Applying the 0.8 Screen

Appendix 3 provides the familiar measured-impedance assessment:

Zs(measured)≤0.8 Zs(table)Z_{s(\text{measured})}\le0.8\,Z_{s(\text{table})}

Its algebraically equivalent form is:

1.25 Zs(measured)≤Zs(table)1.25\,Z_{s(\text{measured})}\le Z_{s(\text{table})}

This conservative screen allows for conductor resistance increasing with load temperature. Use 1.25 when algebraically reversing the 0.8 screen. The approximate 20-to-70 °C copper resistance factor 1.20 applies to that conductor resistance under those assumptions; a detailed assessment separately treats the source and internal circuit components.


Maximum Permitted ZsZ_s Reference Tables (0.4 s Disconnection, 230 V)

Inspectors reference the following core values from BS 7671 Tables 41.2, 41.3, and 41.4, compared alongside their 80% quick-screen measured limits:

Type B Circuit Breakers (BS EN 60898 / BS EN 61009)

Tripping current Ia=5×InI_a = 5 \times I_n (Instantaneous magnetic trip between 3×In3 \times I_n and 5×In5 \times I_n)

Rating (InI_n)Disconnection Current (IaI_a)BS 7671 Max ZsZ_s (70∘C70^\circ\text{C})GN3 80% Max Measured ZsZ_s (20∘C20^\circ\text{C})
6 A30 A7.28 Ω5.83 Ω
10 A50 A4.37 Ω3.50 Ω
16 A80 A2.73 Ω2.19 Ω
20 A100 A2.19 Ω1.75 Ω
25 A125 A1.75 Ω1.40 Ω
32 A160 A1.37 Ω1.10 Ω
40 A200 A1.09 Ω0.88 Ω
50 A250 A0.87 Ω0.70 Ω

Type C Circuit Breakers (BS EN 60898 / BS EN 61009)

Tripping current Ia=10×InI_a = 10 \times I_n (Instantaneous magnetic trip between 5×In5 \times I_n and 10×In10 \times I_n)

Rating (InI_n)Disconnection Current (IaI_a)BS 7671 Max ZsZ_s (70∘C70^\circ\text{C})GN3 80% Max Measured ZsZ_s (20∘C20^\circ\text{C})
6 A60 A3.64 Ω2.92 Ω
10 A100 A2.19 Ω1.75 Ω
16 A160 A1.37 Ω1.10 Ω
20 A200 A1.09 Ω0.88 Ω
32 A320 A0.68 Ω0.55 Ω

Type D Circuit Breakers (BS EN 60898 / BS EN 61009)

Tripping current Ia=20×InI_a = 20 \times I_n (Instantaneous magnetic trip between 10×In10 \times I_n and 20×In20 \times I_n)

Rating (InI_n)Disconnection Current (IaI_a)BS 7671 Max ZsZ_s (70∘C70^\circ\text{C})GN3 80% Max Measured ZsZ_s (20∘C20^\circ\text{C})
6 A120 A1.82 Ω1.46 Ω
10 A200 A1.09 Ω0.88 Ω
16 A320 A0.68 Ω0.55 Ω
20 A400 A0.55 Ω0.44 Ω
32 A640 A0.34 Ω0.28 Ω

Fuses: Use the Correct Characteristic and Time

Identify the actual fuse standard, system and rating. BS 88-2 systems E/G and BS 88-3 system C have different characteristics; BS 88-3 is not simply a generic service-fuse label. Use the applicable current edition's table or manufacturer time/current data for the required disconnection time.

Read the current IaI_a that ensures operation within that time, then apply:

Zs(max⁡)=U0Cmin⁡IaZ_{s(\max)}=\frac{U_0C_{\min}}{I_a}

For example, if the applicable characteristic establishes Ia=100AI_a=100 A for the required time on a 230 V supply, the operating-temperature limit is 230×0.95/100=2.185Ω230\times0.95/100=2.185 Ω. This is a calculation example, not a rating assigned to an unspecified fuse. Apply the appropriate measured-temperature assessment and record the source of the actual limit.


Action When Measured ZsZ_s Sits in the "Grey Zone" (Between 80% and 100%)

What must an inspector do if a measured ZsZ_s value exceeds the 80% rule-of-thumb limit, but is less than the 100% BS 7671 table limit? (e.g. For a 32 A Type B MCB, table limit is 1.37 Ω1.37\ \Omega, 80% limit is 1.10 Ω1.10\ \Omega, and measured reading is 1.22 Ω1.22\ \Omega).

  QUICK SCREEN                         FURTHER ASSESSMENT
  Measured ≤0.8 × applicable limit      Screen exceeded
  Meets this conservative loop check   Check valid measurement, limit/source,
  Continue the remaining verification  protective measure and detailed assessment

A reading above the screen is not automatically a C2 observation. Identify whether fault protection relies on the overcurrent device or an RCD, and use the appropriate limit. Where temperature is material, apply a supported component calculation or the relevant published correction method; do not assume the external source warms to the final-circuit conductor temperature.

The Detailed Temperature Correction Formula

To establish whether the circuit complies when in the grey zone, adjust the measured internal conductor continuity (R1+R2)(R_1 + R_2) using this approximate copper-resistance model, consistent with α≈0.004/°C at 20 °C:

(R1+R2)corrected=(R1+R2)measured×[230+θmax230+θtest](R_1 + R_2)_{\text{corrected}} = (R_1 + R_2)_{\text{measured}} \times \left[ \frac{230 + \theta_{\text{max}}}{230 + \theta_{\text{test}}} \right]

Where:

  • θmax\theta_{\text{max}} = Maximum permitted conductor temperature under normal service (70∘C70^\circ\text{C} for 70°C thermoplastic PVC).
  • θtest\theta_{\text{test}} = Ambient temperature at the time of testing (e.g. 15∘C15^\circ\text{C}).

Worked Example: Grey Zone Resolution

A 32 A Type B MCB on a radial socket circuit has a measured Ze=0.30 ΩZ_e = 0.30\ \Omega and a measured (R1+R2)=0.88 Ω(R_1 + R_2) = 0.88\ \Omega taken at an ambient room temperature of 10∘C10^\circ\text{C}:

  1. Calculate Cold ZsZ_s: Zs=0.30+0.88=1.18 ΩZ_s = 0.30 + 0.88 = 1.18\ \Omega.
  2. Compare Against Rule of Thumb: 80% limit for 32 A Type B MCB is 1.10 Ω1.10\ \Omega. The measured 1.18 Ω1.18\ \Omega fails the 80% test (1.18>1.10 Ω1.18 > 1.10\ \Omega), but is below the 100% limit (1.37 Ω1.37\ \Omega).
  3. Apply Detailed Calculation: (R1+R2)70=0.88×[230+70230+10]=0.88×[300240]=0.88×1.25=1.10 Ω(R_1 + R_2)_{70} = 0.88 \times \left[ \frac{230 + 70}{230 + 10} \right] = 0.88 \times \left[ \frac{300}{240} \right] = 0.88 \times 1.25 = 1.10\ \Omega
  4. Calculate Final Hot ZsZ_s: For this example, assume the source contribution remains 0.30 Ω and reactance is negligible; add it to the corrected internal resistance: Zs(corrected)=Ze+(R1+R2)70=0.30+1.10=1.40 ΩZ_{s(\text{corrected})} = Z_e + (R_1 + R_2)_{70} = 0.30 + 1.10 = 1.40\ \Omega
  5. Verdict: Under these stated assumptions, 1.40 Ω exceeds the 1.37 Ω limit for relying on this B32 overcurrent characteristic. Assess an appropriate design remedy or verified RCD fault-protection arrangement; an RCBO substitution alone is not a complete acceptance check. Confirm the other protective requirements and record the basis of the result.
Test Your Knowledge

What is the maximum permitted earth fault loop impedance (Zs) at operating temperature under BS 7671 Table 41.3 for a 32 A Type B miniature circuit breaker (MCB) protecting a 230 V final circuit requiring a 0.4-second disconnection time?

A

1.10 Ω

B

1.37 Ω

C

2.73 Ω

D

0.68 Ω

Test Your Knowledge

Why does BS 7671 incorporate a voltage factor Cmin of 0.95 into maximum permitted earth fault loop impedance calculations?

A

To account for potential calibration drift in digital loop impedance test instruments

B

To allow for the resistance increase caused by skin effect in large copper busbars

C

To account for potential supply voltage drop below nominal 230 V under network fault conditions

D

To adjust for power factor variations in highly inductive single-phase motors

Test Your Knowledge

A C20 final circuit has a measured ambient Zs of1.05 Ω. The applicable operating-temperature limit is1.09 Ω and its quick-screen measured limit is0.88 Ω. What is the correct initial assessment?

A

It exceeds the quick screen. Check the valid measurement and actual protective measure, then use a supported detailed assessment before declaring compliance or failure.

B

The circuit is an immediate, definitive pass because the measured reading is below 1.09 Ω

C

The circuit must be immediately coded as C1 (Danger Present) on the EICR because it exceeds the 0.87 Ω rule of thumb

D

The test is invalid because Type C circuit breakers are prohibited from protecting 230 V final socket circuits