11.4 Earth Electrode Resistance Testing

Key Takeaways

  • A TT installation uses a consumer earth electrode connected to its protective earthing system. Bonded metal services can create additional parallel paths; measure the intended electrode arrangement and identify the earthing required for any generating system.

  • 643.7.2 requires earth-electrode resistance measurement where relevant. Fall-of-potential is an established method; other suitable methods include appropriately applied loop or clamp techniques. BS EN 61557-5 specifies earth-resistance test equipment performance.

  • Use adequate spike separation and check the resistance plateau by moving the potential spike. For a suitable simple-electrode 62% method, take comparison readings near 52% and 72% of D and apply the instrument procedure’s acceptance criteria.

  • For TT fault protection by RCD, 411.5.3 requires RA×IΔn≤50 V and the applicable disconnection time. At 30 mA the resistance criterion gives approximately 1667 Ω; actual fault touch voltage can exceed 50 V until disconnection.

  • Earth-electrode resistance should be as low as practicable. Table 41.5 notes that a value above 200 Ω may not be stable; assess seasonal conditions, depth and the required protection rather than treating 200 Ω as a universal automatic failure.

Last updated: November 2026

11.4 Earth Electrode Resistance Testing

Core Testing Principle: A TT installation normally relies on its earth electrode and an RCD for fault protection. Verify the earthing, applicable resistance criterion and required disconnection time together. The criterion does not clamp actual fault touch voltage to 50 V before the protective device operates.


Earth Electrode Systems in TT Installations & Generation

Under BS 7671 Regulation 542.2, acceptable earth electrode configurations include:

  • Earth Rods: Copper-bonded high-tensile steel core rods (typically 15 mm or 16 mm diameter, driven in 1.2 m or 1.5 m extendable sections).
  • Earth Plates & Lattice Mats: Copper plates buried vertically or horizontally in high-resistivity or rocky ground.
  • Earth Tapes & Rings: Bare copper tape (25 mm × 3 mm) buried horizontally in perimeter trenches at depths of 0.5 m to 1.0 m.
  • Foundation Earth Electrodes: Structural metalwork or reinforcement steel bars encased in concrete foundations (BS 7671 Regulation 542.2.2).

The Nature of Earth Resistance

The electrode resistance (RER_E) comprises three physical components. For the TT protection assessment, RAR_A additionally includes the protective-conductor resistance:

  1. Electrode Material & Connection: The metallic resistance of the copper rod, cable lug, and connection clamp (typically negligible, < 0.01 Ω).
  2. Contact Resistance: The interface resistance between the metal surface of the rod and the immediately adjacent soil compacted against it.
  3. Soil Spreading Resistance: The resistance of the concentric hemispherical shells of soil surrounding the rod extending outwards into the earth mass. As distance from the rod increases, the available conducting area grows and the additional resistance of successive soil layers decreases. Most resistance is near the electrode; the simplified resistance-area model has no sharp physical boundary at which soil resistance suddenly becomes zero.
  EARTH ELECTRODE RESISTANCE SHELLS (SPHERE OF INFLUENCE)

               [ Earth Rod Driven into Ground ]
                            │
               ═════════════╪═════════════  Ground Level
                  ( ( ( ( ( │ ) ) ) ) )
                ( ( ( ( ( ( │ ) ) ) ) ) )
               ( ( ( ( ( ( (│ ) ) ) ) ) ) )
               Shell 1    Shell 2    Shell 3
               (High R)  (Medium R)  (Low R ──► Negligible incremental R)
               ◄──────── Sphere of Influence ────────►

Method 1: The 3-Terminal Fall-of-Potential Test (BS EN 61557-5)

The fall-of-potential method is an established way to measure an electrode separately. 643.7.2 requires the relevant measurement; BS EN 61557-5 sets test-equipment requirements rather than prescribing only this arrangement or one spike geometry.

Dedicated Test Instrument Characteristics

Use a suitable earth-resistance tester and its specified leads/connections. Instruments normally use AC at a selected frequency to limit interference and avoid electrode polarisation. Follow the maker's procedure and assess interference or excessive test-spike resistance rather than assuming every tester uses one frequency range.

  FALL-OF-POTENTIAL (3-TERMINAL) TEST CONFIGURATION

      Disconnection
      Clamp OPEN
        │
        ▼          P2 Potential Spike               C2 Current Spike
     [  E  ] ─────── (At 61.8% of D) ───────────────── (At Distance D)
     [ Rod ]
        │                    ▲                                ▲
        │                    │                                │
        │ E / C1 / P1        │ P2                             │ C2
     ┌──┴────────────────────┴────────────────────────────────┴──┐
     │           Dedicated Earth Electrode Tester                │
     └───────────────────────────────────────────────────────────┘
     ◄─────────────────────── Distance D (30 m - 50 m) ──────────►

Step-by-Step Testing Procedure

  1. Make disconnection safe: Isolate and secure the installation supplied by the electrode before interrupting its earthing connection. Identify other sources and possible diverted/parallel current; a main switch OFF position alone does not make an earthing or bonding conductor safe to disconnect. Follow the Chapter 2 precautions and stop if safe conditions cannot be established. Separate the electrode from parallel installation paths at the appropriate test link/connection, then connect the tester to the electrode side. Reconnect and verify earthing before restoring supply.
  2. Position the Spikes:
    • Connect instrument terminal EE (or C1/P1C_1/P_1 combined) to the isolated earth electrode.
    • Drive the Current Spike (C2/HC_2 / H) into the ground at a distance DD from the electrode in a straight line (typically 30 to 50 metres).
    • Drive the Potential Spike (P2/SP_2 / S) into the ground along the exact direct line between the earth electrode and C2C_2, at a distance equal to 61.8% of DD (0.618×D0.618 \times D, based on golden ratio electrical field distribution).
  3. Perform the Three-Point Verification:
    • Reading 1 (RnomR_{\text{nom}}): Measure resistance with P2P_2 at the nominal 61.8% position (e.g. 31 m for D=50D = 50 m).
    • Reading 2 (R−10%R_{-10\%}): Relocate spike P2P_2 10% of DD closer to the electrode (51.8%D51.8\% D, e.g. 26 m) and measure.
    • Reading 3 (R+10%R_{+10\%}): Relocate spike P2P_2 10% of DD further towards C2C_2 (71.8%D71.8\% D, e.g. 36 m) and measure.
  4. Evaluate the Resistance Plateau:
    • Compare the three readings using the instrument procedure’s specified tolerance or accuracy calculation. Substantially agreeing readings support a flat part of the resistance curve for that method; this is not a zero-potential point.
    • Record the electrode resistance determined by the procedure, using the mean of substantially agreeing readings where specified. For the TT assessment, RAR_A also includes the protective-conductor resistance to the exposed parts.
    • If the readings continuously rise without a plateau, the distance DD is too short; the resistance area of the electrode overlaps the resistance area of C2C_2. Increase DD to 70 m or 100 m and repeat.
  FALL-OF-POTENTIAL: CHECK FOR A FLAT RESISTANCE REGION

  Measured resistance
       ^                                    /  approaching C2
       |                                   /
  Re   |          ________________________/
       |         /
       |        /   readings around the selected potential-spike position
       |_______/
       +--------------------------------------------------> P2 distance
       Rod        about 52%D   62%D   72%D               C2 at D

  No satisfactory flat region: increase separation and repeat the checks.

Method 2: Earth Fault Loop Tester Method (TT Systems)

Where driving test spikes into the surrounding ground is physically impossible (e.g., dense urban environments, asphalt pavements, multi-storey city centres), BS 7671 Regulation 643.7.2 permits an alternative method: using an Earth Fault Loop Tester.

What the Loop Measurement Includes

The measured TT loop includes the source/line path, the earth return through the source electrode and the consumer electrode, and the relevant protective connection. It is not a pure electrode-resistance measurement. Account for the source contribution: the IET lists 21 Ω as a typical declared TT external value excluding the consumer electrode.

With the outgoing installation isolated and secured, the competent tester can arrange a controlled live test between the supply line and the separately connected electrode conductor, following the instrument instructions. Establish safe conditions before disconnecting that conductor from the MET, exclude parallel paths, and restore/verify earthing before energising the installation. Opening the main switch alone does not remove bonded-pipe paths. With parallel paths excluded and a suitable test arrangement, the measured loop can provide a conservative assessment of the electrode/protective path because it includes additional series impedance. Label and record the actual method and quantity. In this terminology ZeZ_e excludes the consumer electrode; the complete measured loop includes it.


MaximumAcceptable Earth Electrode Resistance Values (RAR_A)

TT earth-loop impedance often makes overcurrent protection alone unable to achieve the required disconnection time. An RCD is therefore normally used. Where an overcurrent device provides fault protection, its actual loop/disconnection requirements must instead be satisfied.

RCD Protection under 411.5.3

For the RCD arrangement, verify the required disconnection time and:

RA×IΔn≤50 VR_A\times I_{\Delta n}\le50\text{ V} RA≤50 VIΔnR_A\le\frac{50\text{ V}}{I_{\Delta n}}

Here RAR_A includes the electrode and protective-conductor resistance to the exposed-conductive-parts, and IΔnI_{\Delta n} is the rated residual operating current in amperes. This is the BS 7671 criterion; it does not guarantee a maximum actual fault touch voltage of 50 V. The exposed parts can rise to a much higher potential until the protective device disconnects. Apply any relevant special-location requirements as well.

Values from the Resistance Criterion

Rated residual current50 V/IΔn50\text{ V}/I_{\Delta n}Additional assessment
30 mA (0.03 A)Approximately 1667 ΩRequired disconnection, electrode stability and other applicable protection
100 mA (0.10 A)500 ΩRequired disconnection and stability; select time delay only where appropriate
300 mA (0.30 A)Approximately 167 ΩRequired disconnection and stability; do not select solely for fire protection
500 mA (0.50 A)100 ΩRequired disconnection and stability; lower limits may apply elsewhere

Stability: The 200 Ω Note

Table 41.5 says electrode resistance should be as low as practicable and a value above 200 Ω may not be stable. Soil drying and freezing must not raise the resistance above the required value. A single acceptable measurement in damp conditions does not establish year-round suitability.

Assess electrode depth, soil/seasonal conditions, connections and the applicable protection. A value above 200 Ω prompts that assessment; it is not automatically declared unsafe by a universal 200 Ω pass/fail rule. Nor does BS 7671 impose a universal ideal 100 Ω target for every TT installation.

Improving an Unsuitable Electrode Arrangement

Where assessment shows inadequate resistance or stability, options include a deeper electrode, additional suitably spaced rods, or a different electrode/backfill arrangement suited to the ground and corrosion conditions. Extra rods close together have overlapping resistance areas and give less improvement than well-separated rods. Select a suitable arrangement, obtain necessary permissions, check buried services and retest against the actual protection and stability requirements.

Test Your Knowledge

What approximate resistance limit follows from RA×IΔn≤50 V for a TT circuit protected by a 30 mA RCD, before the additional disconnection/stability assessment?

A

200 Ω

B

1667 Ω

C

500 Ω

D

100 Ω

Test Your Knowledge

In the simplified 62% fall-of-potential method for a suitable electrode arrangement, approximately where is the nominal potential spike placed along distance D from the electrode to the current spike?

A

61.8% of distance D

B

50.0% of distance D

C

25.0% of distance D

D

85.0% of distance D

Test Your Knowledge

Above what electrode-resistance value does the note to Table 41.5 warn that the value may not be stable?

A

50 Ω

B

500 Ω

C

1667 Ω

D

200 Ω