12.1 External Earth Fault Loop Impedance (Ze) Measurement
Key Takeaways
External earth fault loop impedance (Ze) comprises the impedance of the electrical path external to the installation: the supply transformer winding, line conductor, and earth return path (protective neutral or earthing conductor).
Safe isolation boundary: opening and locking off the main switch disconnector isolates only the downstream installation; the incoming supply terminals remain live at line-to-earth potential ().
Determine Ze by suitable measurement, enquiry or calculation as appropriate. A live measurement of the supplier earth alone needs parallel installation paths excluded, a justified safe procedure and the supplied installation isolated.
A live Ze test requires the full EAWR 14 justification and precautions. Secure every supply to the outgoing installation, assess diverted current before touching earthing connections, keep the installation isolated during disconnection, and restore/verify earthing before energising.
Typical declared Ze benchmarks for supplies up to 100 A are 0.8 Ω TN-S, 0.35 Ω TN-C-S and 21 Ω TT, subject to the distributor’s actual information. TT Ze excludes the consumer electrode; the loop measured through it also includes that electrode.
12.1 External Earth Fault Loop Impedance (Ze) Measurement
Core Testing Principle: Determine the supply's external earth fault loop impedance, , from suitable information, calculation or measurement. Where a live measurement is necessary, exclude parallel installation paths and apply the full safe-work procedure. A board main switch may leave its incoming terminals live; it does not make an earthing conductor safe to disconnect by itself.
The Physical Composition of the External Loop ()
In electrotechnical engineering, earth fault loop impedance represents the total opposition (resistance and inductive reactance) encountered by a fault current when a negligible-impedance short circuit occurs between a line conductor and earth. The external component, designated , encompasses every conductive element from the originating secondary winding of the regional supply transformer up to the consumer's incoming supply terminals.
SEPARATE TN EXTERNAL LOOP MEASUREMENT (Ze)
┌────────────────────────────────────────────────────────────────────────┐
│ DNO SUBSTATION TRANSFORMER │
│ Secondary Winding (Z_TR) ────► Line Conductor (R1 + X1) │
│ ▲ │ │
│ │ Star Point Ground ▼ Underground / Overhead
│ │ Supply Cable │
│ │ │ │
│ │ ▼ Service Cutout Fuse │
│ │ CONSUMER ORIGIN │
│ │ ┌──────────────────────────────┐ │
│ │ │ Main Switch (LOCKED OFF) │ │
│ │ │ Incoming Terminals (LIVE!) │ │
│ │ │ │ │ │
│ │ Earth Return Path (R2 + X2) │ [ Loop Tester ] │ │
│ │ (Lead Sheath / PEN) │ │ │ │
│ └──────────────────────────────┴──► Disconnected Earthing ────┘ │
│ Conductor (from MET) │
└────────────────────────────────────────────────────────────────────────┘
The Four Physical Components of
- Transformer Secondary Winding (): The internal impedance of the local low-voltage distribution substation transformer winding (typically ). This is predominantly inductive reactance () combined with winding copper resistance ().
- External Line Conductor (): The resistance and inductive reactance of the underground supply mains cable or overhead line spanning from the local distribution substation to the property cutout, including all network tee-joints, service joints, and service terminations.
- Service Cutout & Metering Connections: The internal contact resistance across the DNO service fuse carrier, the HBC fuse link element (BS 1361 / BS 88-3), and the meter tails connecting the cutout to the electricity meter and consumer unit main switch disconnector.
- Supply Earth Return Path (): The path taken by earth fault current returning from the consumer intake back to the transformer star point neutral. The nature of this path depends directly on the system earthing arrangement:
- TN-S System: Current returns via the dedicated metallic lead sheath, aluminium sheath, or steel wire armouring of the incoming underground service cable.
- TN-C-S (PME) System: Current returns along the combined Protective Earthed Neutral (PEN) conductor of the distribution main, which is grounded at multiple points along the distribution route.
- TT system: The external value includes the source and its earth-return contribution, excluding the consumer electrode. The complete fault loop through the installation also includes its electrode and protective connections.
Safe Isolation Boundaries & The Critical Physical Boundary
Before undertaking any work at the intake, the electrical inspector must understand the exact physical boundaries of isolation within a consumer unit or distribution board:
ISOLATION BOUNDARY AT THE CONSUMER UNIT
DNO Supply Cutout (Sealed Fuse)
│
▼ Live unless isolated upstream
Electricity Meter
│
▼ Live unless isolated upstream
┌────────────────────────────────────────────────────────┐
│ CONSUMER UNIT / DISTRIBUTION BOARD │
│ │
│ [ INCOMING TERMINALS ] ◄── LIVE unless isolated upstream │
│ │ │
│ ═════════╧═════════ ◄──── ISOLATION BOUNDARY │
│ MAIN SWITCH DISCONNECTOR (Locked in OFF Position) │
│ ═════════╤═════════ │
│ │ │
│ [ OUTGOING TERMINALS / INTERNAL BUSBARS ] │
│ │ │
│ ▼ ◄── PROVED DEAD & ISOLATED │
│ Final Circuit Overcurrent Protective Devices │
└────────────────────────────────────────────────────────┘
The Incoming vs. Outgoing Reality
- Opening the main switch: This normally disconnects its downstream busbars from that source. Identify and secure every other source, including generation, storage and UPS systems, before treating the test boundary as dead.
- Incoming side: Opening this switch leaves its incoming supply terminals live unless an upstream device has isolated them. The relevant voltages are normally 230 V line-to-earth/neutral and 400 V line-to-line on a three-phase supply.
- Supply isolation: An upstream isolator may be available; establish its ownership, rating and authority for use. Service cutout access requires the relevant distributor/supplier-authorised procedure. Do not remove a sealed fuse or disconnect the supply without that authority and the necessary competence and precautions.
- Safe isolation verification: Prove dead within the actual work boundary using a suitable voltage indicator checked before and after use. Identify and protect against incoming terminals and any other parts that remain live.
- Lock-Off Discipline: The main switch disconnector must be secured in the OFF position using an approved lockout bracket, safety padlock, and warning notice, with the key retained exclusively by the tester. The main switch must remain locked OFF throughout the entire test to ensure the installation circuits stay completely de-energised.
Statutory Authority & Live Testing Safety (EAWR 1989 Regulation 14)
Measuring requires line-to-earth potential () so that the test instrument can circulate test current through the supply transformer and external distribution network. Because the test probes must make direct contact with the incoming live terminals while the installation earthing conductor is disconnected, measurement constitutes live testing on or near uninsulated live conductors.
The Regulation 14 Three-Part Justification
Under Regulation 14 of the Electricity at Work Regulations 1989 (EAWR), work on or near live conductors is strictly prohibited unless three statutory conditions are satisfied concurrently:
Caution
EAWR 14 applies to each proposed live test. Establish that making it dead is unreasonable in all the circumstances, that working live is reasonable, and that suitable precautions prevent injury. Verification is necessary, but a particular live measurement is not automatically justified: suitable distributor information or other permitted methods may avoid it. If the live test is justified, minimise exposed access and keep the outgoing installation securely isolated while its earthing connection is separated.
HSE Guidance Note GS38 Compliance
Select the instrument and leads for the voltage, measurement category and available fault energy. GS38 recommends probe tips no longer than 4 mm, preferably 2 mm or less, with suitable barriers/insulation. Use finger barriers, protected connectors and sound insulated leads. Appropriate current-limiting protection may be integral to the instrument/lead arrangement; do not assume every loop tester must use one universal probe-fuse rating. Follow the maker's approved leads and connections.
PPE and Work-Area Controls
Select insulating and arc-protective equipment from the actual shock/arc risk assessment. Ordinary BS EN 166 eye protection or generic flame-retardant clothing alone does not establish a suitable arc rating. Provide the required face/eye, hand and clothing protection, suitable lighting and clear access. Control entry to the test area so others cannot approach exposed live parts.
The Critical MET Disconnection Requirement
For a separate measurement of the supplier earth-return path, exclude parallel installation paths. Make any disconnection safe first; this does not require or justify disconnecting earthing for every way of determining Ze.
The "Parallel Earth Path Trap"
Where extraneous-conductive-parts are present, main protective bonding connects them to the MET. Metal services or structural paths can link neighbouring installations, creating parallel returns. Identify the actual parts and connections; do not assume every metal pipe is extraneous or every building shares the same services.
With the installation connected to the MET, bonded metalwork can provide additional earth-return paths. The supply line/source portion is shared; it is not a separate parallel branch for every pipe. In a simplified resistive model:
SHARED SOURCE/LINE ── test point ──┬── supplier earth return
├── bonded water path
└── other bonded return path
A low combined reading can conceal a poor supplier earth.
A pipe later replaced by plastic removes that incidental path;
it must not be relied on to make a defective earthing facility safe.
Important
Exclude parallel paths safely: An incidental return can conceal a damaged supply earth. Identify the conductor and all relevant supplies, assess possible diverted current and follow a controlled disconnection procedure. Keep bonding in place unless a separately justified procedure requires otherwise. The separately measured value supports the intended circuit calculations; restore and verify every protective connection before energising or leaving the installation.
Mandatory Safe Working Sequence for Testing
Plan the measurement before exposing the supply terminals. A suitable sequence for a justified separate supplier-earth measurement is:
Plan sources/access → isolate and secure outgoing installation
→ prove dead within boundary and assess diverted-current hazards
→ safely separate earthing connection from parallel paths
→ controlled live measurement using approved connections
→ remove leads and restore/verify earthing
→ covers secured, required checks satisfactory, then restore supply
- Coordinate shutdown: Identify critical services and arrange suitable precautions and consent for interruption.
- Establish the work boundary: Identify every supply, isolate and secure the outgoing installation, and prove dead with a suitable indicator checked before and after use. Protect against the incoming parts that remain live.
- Assess the earthing conductor: Establish safe conditions for handling it, including possible diverted current from the wider network. Main switch OFF alone is insufficient. Stop and seek the appropriate network assistance if safe conditions cannot be established.
- Separate the intended path: Where required for the measurement, safely separate the installation earthing conductor at the appropriate connection/test link to exclude parallel installation paths. Keep the supplied installation isolated throughout.
- Connect the tester: Use a suitable BS EN 61557-3 tester or equivalent performance/safety, in the correct mode and with its approved leads. For a TN supplier-earth measurement, connect line to the supply side and earth to the separated supplier-earthing conductor; connect neutral only as the instrument requires. Use the full live-work precautions. A TT measurement through the consumer electrode includes that electrode and must be identified accordingly.
- Measure and assess: Record the actual value/method, apply the instrument accuracy and stability information and investigate an unexpected result. Remove test leads safely.
- Restore protective connections: Reconnect the earthing conductor, tighten to the specified torque and verify the connection/continuity by an appropriate method. Never energise or leave the installation without its required earthing.
- Restore service: Confirm all required verification and reconnections are satisfactory, secure the covers and restore supply in the planned sequence. Confirm supply polarity before energising outgoing circuits; check the relevant functions afterwards.
DNO Published Maximum Values & System Benchmarks
The IET lists the following typical declared values for supplies up to 100 A. Obtain the distributor information for the actual supply; these are not universal statutory maxima. P28 concerns voltage fluctuations, not this loop-impedance benchmark.
Supply Arrangement Characteristics & Maximum Limits
| Earthing System | Earth Return Path Construction | Typical Maximum Declared | Common Causes of High Readings | Remedial Action If Exceeded |
|---|---|---|---|---|
| TN-S | Separate metallic supply-earth return | 0.80 Ω | Supply route, connections or earthing condition | Assess against actual distributor data and report a suspected supply-earth defect. |
| TN-C-S (PME) | Combined PEN upstream of the separation point | 0.35 Ω | Supply route, connections or PEN condition | Investigate and notify the distributor appropriately; the number alone does not locate a neutral fault. |
| TT | External source/earth-return contribution excluding consumer electrode | 21 Ω | Actual source and return conditions | A loop test through the consumer electrode also includes its resistance; identify the quantity tested. |
Tip
TT assessment: The complete loop measured through the consumer electrode differs from the external value excluding that electrode. Assess the actual electrode/protective path and the relevant RCD/disconnection requirements. Table 41.5 says electrode resistance should be as low as practicable and a value above 200 Ω may not be stable; it does not impose an automatic 200 Ω failure or one required remedy.
Differentiating from Sub-Distribution Impedance ()
Candidates must distinguish between the external loop impedance at the origin () and loop impedance measured at remote distribution boards:
- (origin): External supply-loop impedance determined by an appropriate method. For a separate TN measurement, parallel installation paths are excluded under controlled conditions; for TT, the consumer electrode is excluded from this external definition.
- (Distribution Board): Measured at the incoming terminals of a remote sub-distribution board within the installation. includes plus the resistance of the distribution sub-main line conductor and protective conductor (). Unlike , sub-distribution boards are tested with their local CPCs connected, reflecting any existing parallel structural paths.
Why are parallel installation paths excluded during a justified separate measurement of a TN supplier-earth loop?
To prevent high test currents from tripping downstream Type A and Type B residual current devices (RCDs)
To eliminate parallel earth return paths through bonded metallic pipework and structural steel that would yield an artificially low reading
To protect sensitive microelectronic equipment within the consumer unit from overvoltage transients during the test
To ensure that the test instrument can measure the installation insulation resistance simultaneously
Which typical declared Ze benchmark does the IET list for a usual TN-S supply up to 100 A, subject to the actual distributor information?
0.35 Ω
1.20 Ω
0.80 Ω
21.0 Ω
During a justified separate TN Ze measurement with the earthing conductor separated from the MET, what must happen before restoring the outgoing supply?
Keep every source to the outgoing installation isolated and secured during disconnection, then restore and verify the earthing connection and required checks before energising.
The main switch disconnector must be closed and locked in the ON position to supply 230 V operating power to the downstream final circuits while the earthing conductor remains disconnected
Opening the main switch isolates both incoming and outgoing terminals from the DNO service cutout, eliminating all live working risks
The earthing conductor may be left disconnected until all subsequent circuit loop impedance (Zs) and RCD tests are completed across the entire installation