17.2 Electrical Systems, Motors, Generators, Instrumentation and SCADA
Key Takeaways
Ohm's law is volts = amps × ohms; three-phase power in kW ≈ 1.732 × volts × amps × power factor ÷ 1,000.
Motor nameplates list horsepower, voltage, full-load amps, speed, service factor and insulation class; overloads protect against sustained overcurrent, and breakers or fuses against short circuits.
Magnetic flowmeters need a conductive liquid and a full pipe; transit-time ultrasonic meters suit clean water, and Doppler meters need particles or bubbles.
A 4-20 mA signal maps the instrument range linearly from 4 mA (zero) to 20 mA (full scale); a reading near 0 mA usually means a broken loop.
Standby generators need regular exercise under load, fuel quality checks and automatic transfer switch testing.
Electrical Fundamentals
| Quantity | Unit | Relationship |
|---|---|---|
| Voltage (E or V) | volts | Electrical pressure |
| Current (I) | amperes | Flow of charge |
| Resistance (R) | ohms | Opposition to flow |
| Ohm's law | V = I × R | |
| Single-phase power | watts | W = V × I × power factor |
| Three-phase power | kilowatts | kW = 1.732 × V × I × PF ÷ 1,000 |
| Horsepower | 1 hp = 0.746 kW |
Example. A 460-volt three-phase motor draws 50 amps at a 0.85 power factor.
kW = 1.732 × 460 × 50 × 0.85 ÷ 1,000 ≈ 33.9 kW, or about 45 hp of electrical input.
Motors and Motor Control
Most plant motors are three-phase induction motors. Read the nameplate:
- horsepower, voltage and frequency;
- full-load amps (FLA) and rated speed (rpm);
- service factor (a 1.15 SF motor tolerates 15 percent overload briefly, at the cost of shorter life);
- insulation class and enclosure type (for example TEFC, or explosion-proof for classified areas).
Motor control:
- Across-the-line starters apply full voltage and draw high inrush current, often about 6 times FLA. Soft starters and VFDs ramp the voltage up gradually.
- Overload relays trip on sustained current above the setting, protecting windings from heat. Circuit breakers and fuses protect against short circuits.
- A motor control center (MCC) groups starters, breakers and controls. Only qualified persons work inside energized MCC buckets, under NFPA 70E rules.
Common electrical problems:
| Symptom | Possible cause |
|---|---|
| Overload trips repeatedly | Mechanical binding, clogged impeller, wrong overload setting, low voltage, phase imbalance |
| Motor hums but will not start | Single-phasing (lost one phase), locked rotor |
| Motor runs hot | Overload, poor ventilation, voltage imbalance, too many starts |
| Low insulation resistance on a megger test | Moisture or aging insulation; dry or rewind before failure |
Variable frequency drives (VFDs) change motor speed by changing frequency. They save energy (affinity laws), soften starts and allow pacing to level or pressure. They also produce heat and harmonics, need clean cool enclosures, and can cause bearing currents in motors without proper grounding.
Standby Power
- Generators for treatment plants and critical lift and booster stations must start automatically through an automatic transfer switch (ATS).
- Exercise them regularly; weekly is common. Run them under real or load-bank load periodically so diesel engines do not "wet stack."
- Check fuel level and quality (water, microbial growth), batteries, coolant, block heaters and alarms.
- Test the ATS by simulating a utility outage. Keep connection points and receptacles ready for portable generators at smaller stations.
Flow Measurement
| Meter | Principle | Strengths and limits |
|---|---|---|
| Magnetic (magmeter) | Voltage induced as a conductive liquid moves through a magnetic field | No obstruction or headloss; needs conductive liquid and a full pipe; good for sludge |
| Ultrasonic transit-time | Difference in sound travel time with and against flow | Clean liquids; clamp-on versions available |
| Ultrasonic Doppler | Frequency shift from particles or bubbles | Needs suspended solids or bubbles; poor in very clean water |
| Venturi or orifice (differential pressure) | Pressure drop through a restriction | Proven; needs clean taps and straight pipe runs |
| Propeller and turbine | Rotating element | Clean water only; wears |
| Parshall flume or weir | Open-channel head converted to flow | Must stay free-flowing and clean; level sensor accuracy matters |
Level, Pressure and Analyzers
- Level: ultrasonic and radar (non-contact), submersible pressure transducers, bubblers and floats. Floats often serve as independent high and low alarms.
- Pressure transmitters for discharge headers, filters and distribution monitoring.
- Analyzers: chlorine (amperometric or colorimetric), pH, turbidity, dissolved oxygen (optical or membrane), ORP, ammonia and nitrate. Each needs routine calibration against lab results and cleaning on schedule. A drifting analyzer controlling a chemical feed is a compliance risk.
The 4-20 mA Signal
Most analog instruments send a 4-20 mA signal proportional to the measured value:
Example. A wet well level transmitter is ranged 0-20 ft and reads 12 mA.
Level = 0 + (12 − 4) ÷ 16 × 20 = 10 ft
The live zero at 4 mA lets the system tell a true zero from a fault. A signal near 0 mA means a broken wire or failed instrument.
SCADA
Supervisory control and data acquisition (SCADA) links field instruments and PLCs (programmable logic controllers) or RTUs (remote terminal units) to operator workstations through an HMI (human-machine interface) over radio, cellular, fiber or leased lines.
- Functions: alarms, trends, remote control, historical data for reports.
- Good practice: test alarms and callout systems, document setpoint changes, keep backups of PLC programs, and keep manual operating procedures ready for SCADA outages.
- Cybersecurity is covered in the security and management section. SCADA should never be reachable from the open internet without strong protections.
Worked Example: Wire-to-Water Efficiency
A pump delivers 1,000 gpm against 100 ft of total dynamic head while its motor draws 26.0 kW.
- Water horsepower = (1,000 × 100) ÷ 3,960 ≈ 25.3 hp
- Electrical input = 26.0 kW ÷ 0.746 ≈ 34.9 hp
- Wire-to-water efficiency ≈ 25.3 ÷ 34.9 ≈ 72 percent
Trend this number over time. A falling efficiency at the same flow and head points to impeller wear, a worn wear ring, clogging or motor problems, and helps justify a rebuild before failure.
A level transmitter ranged 0 to 30 ft sends a 16 mA signal. What level does it indicate?
22.5 ft
12 ft
16 ft
24.5 ft
Which flowmeter requires a conductive liquid and a full pipe to measure accurately?
Magnetic flowmeter
Parshall flume
Propeller meter in an open channel
Ultrasonic level sensor over a weir
A three-phase 480-volt pump motor draws 30 amps at a power factor of 0.88. About how many kilowatts is it using?
12.7 kW
25.3 kW
21.9 kW
38.0 kW
Sections you finish are checked off in the contents.