17.2 Electrical Systems, Motors, Generators, Instrumentation and SCADA

Key Takeaways

  • Ohm's law is volts = amps × ohms; three-phase power in kW ≈ 1.732 × volts × amps × power factor ÷ 1,000.

  • Motor nameplates list horsepower, voltage, full-load amps, speed, service factor and insulation class; overloads protect against sustained overcurrent, and breakers or fuses against short circuits.

  • Magnetic flowmeters need a conductive liquid and a full pipe; transit-time ultrasonic meters suit clean water, and Doppler meters need particles or bubbles.

  • A 4-20 mA signal maps the instrument range linearly from 4 mA (zero) to 20 mA (full scale); a reading near 0 mA usually means a broken loop.

  • Standby generators need regular exercise under load, fuel quality checks and automatic transfer switch testing.

Last updated: October 2026

Electrical Fundamentals

QuantityUnitRelationship
Voltage (E or V)voltsElectrical pressure
Current (I)amperesFlow of charge
Resistance (R)ohmsOpposition to flow
Ohm's lawV = I × R
Single-phase powerwattsW = V × I × power factor
Three-phase powerkilowattskW = 1.732 × V × I × PF ÷ 1,000
Horsepower1 hp = 0.746 kW

Example. A 460-volt three-phase motor draws 50 amps at a 0.85 power factor.

kW = 1.732 × 460 × 50 × 0.85 ÷ 1,000 ≈ 33.9 kW, or about 45 hp of electrical input.

Motors and Motor Control

Most plant motors are three-phase induction motors. Read the nameplate:

  • horsepower, voltage and frequency;
  • full-load amps (FLA) and rated speed (rpm);
  • service factor (a 1.15 SF motor tolerates 15 percent overload briefly, at the cost of shorter life);
  • insulation class and enclosure type (for example TEFC, or explosion-proof for classified areas).

Motor control:

  • Across-the-line starters apply full voltage and draw high inrush current, often about 6 times FLA. Soft starters and VFDs ramp the voltage up gradually.
  • Overload relays trip on sustained current above the setting, protecting windings from heat. Circuit breakers and fuses protect against short circuits.
  • A motor control center (MCC) groups starters, breakers and controls. Only qualified persons work inside energized MCC buckets, under NFPA 70E rules.

Common electrical problems:

SymptomPossible cause
Overload trips repeatedlyMechanical binding, clogged impeller, wrong overload setting, low voltage, phase imbalance
Motor hums but will not startSingle-phasing (lost one phase), locked rotor
Motor runs hotOverload, poor ventilation, voltage imbalance, too many starts
Low insulation resistance on a megger testMoisture or aging insulation; dry or rewind before failure

Variable frequency drives (VFDs) change motor speed by changing frequency. They save energy (affinity laws), soften starts and allow pacing to level or pressure. They also produce heat and harmonics, need clean cool enclosures, and can cause bearing currents in motors without proper grounding.

Standby Power

  • Generators for treatment plants and critical lift and booster stations must start automatically through an automatic transfer switch (ATS).
  • Exercise them regularly; weekly is common. Run them under real or load-bank load periodically so diesel engines do not "wet stack."
  • Check fuel level and quality (water, microbial growth), batteries, coolant, block heaters and alarms.
  • Test the ATS by simulating a utility outage. Keep connection points and receptacles ready for portable generators at smaller stations.

Flow Measurement

MeterPrincipleStrengths and limits
Magnetic (magmeter)Voltage induced as a conductive liquid moves through a magnetic fieldNo obstruction or headloss; needs conductive liquid and a full pipe; good for sludge
Ultrasonic transit-timeDifference in sound travel time with and against flowClean liquids; clamp-on versions available
Ultrasonic DopplerFrequency shift from particles or bubblesNeeds suspended solids or bubbles; poor in very clean water
Venturi or orifice (differential pressure)Pressure drop through a restrictionProven; needs clean taps and straight pipe runs
Propeller and turbineRotating elementClean water only; wears
Parshall flume or weirOpen-channel head converted to flowMust stay free-flowing and clean; level sensor accuracy matters

Level, Pressure and Analyzers

  • Level: ultrasonic and radar (non-contact), submersible pressure transducers, bubblers and floats. Floats often serve as independent high and low alarms.
  • Pressure transmitters for discharge headers, filters and distribution monitoring.
  • Analyzers: chlorine (amperometric or colorimetric), pH, turbidity, dissolved oxygen (optical or membrane), ORP, ammonia and nitrate. Each needs routine calibration against lab results and cleaning on schedule. A drifting analyzer controlling a chemical feed is a compliance risk.

The 4-20 mA Signal

Most analog instruments send a 4-20 mA signal proportional to the measured value:

Value=Range minimum+mA−416×Span\text{Value} = \text{Range minimum} + \frac{\text{mA} - 4}{16} \times \text{Span}

Example. A wet well level transmitter is ranged 0-20 ft and reads 12 mA.

Level = 0 + (12 − 4) ÷ 16 × 20 = 10 ft

The live zero at 4 mA lets the system tell a true zero from a fault. A signal near 0 mA means a broken wire or failed instrument.

SCADA

Supervisory control and data acquisition (SCADA) links field instruments and PLCs (programmable logic controllers) or RTUs (remote terminal units) to operator workstations through an HMI (human-machine interface) over radio, cellular, fiber or leased lines.

  • Functions: alarms, trends, remote control, historical data for reports.
  • Good practice: test alarms and callout systems, document setpoint changes, keep backups of PLC programs, and keep manual operating procedures ready for SCADA outages.
  • Cybersecurity is covered in the security and management section. SCADA should never be reachable from the open internet without strong protections.

Worked Example: Wire-to-Water Efficiency

A pump delivers 1,000 gpm against 100 ft of total dynamic head while its motor draws 26.0 kW.

  • Water horsepower = (1,000 × 100) ÷ 3,960 ≈ 25.3 hp
  • Electrical input = 26.0 kW ÷ 0.746 ≈ 34.9 hp
  • Wire-to-water efficiency ≈ 25.3 ÷ 34.9 ≈ 72 percent

Trend this number over time. A falling efficiency at the same flow and head points to impeller wear, a worn wear ring, clogging or motor problems, and helps justify a rebuild before failure.

Test Your Knowledge

A level transmitter ranged 0 to 30 ft sends a 16 mA signal. What level does it indicate?

A

22.5 ft

B

12 ft

C

16 ft

D

24.5 ft

Test Your Knowledge

Which flowmeter requires a conductive liquid and a full pipe to measure accurately?

A

Magnetic flowmeter

B

Parshall flume

C

Propeller meter in an open channel

D

Ultrasonic level sensor over a weir

Test Your Knowledge

A three-phase 480-volt pump motor draws 30 amps at a power factor of 0.88. About how many kilowatts is it using?

A

12.7 kW

B

25.3 kW

C

21.9 kW

D

38.0 kW

Sections you finish are checked off in the contents.