10.2 Nonmetallic Raceways (PVC, RTRC, Liquidtight) & Cable Trays (NEC Articles 352, 356, 392)

Key Takeaways

  • Schedule 80 PVC is required where rigid nonmetallic conduit is exposed to physical damage; Schedule 40 PVC, ENT, and LFNC are not permitted in those locations.
  • NEC 352.44 requires an expansion fitting wherever the calculated length change between securely mounted points is 0.25 inch or more, computed from Table 352.44 at 4.06 inches per 100 feet per 100°F.
  • Listed LFMC may serve as the sole equipment grounding conductor only within the length and overcurrent limits of 250.118(6); beyond 6 feet in the ground return path or above the stated overcurrent rating, a wire-type EGC is required.
  • Single conductors in cable tray must be 1/0 AWG or larger and marked for cable tray use (NEC 392.10(B)(1)).
  • Type FMT is limited to dry locations and lengths not exceeding 6 feet and is not a recognized equipment grounding conductor; surface nonmetallic raceway may not be used above 300 volts between conductors unless it has a metal cover.
Last updated: August 2026

Nonmetallic Raceways (PVC, RTRC, Liquidtight) & Cable Trays (NEC Articles 352, 356, 392)

Nonmetallic raceways and cable tray systems offer superior corrosion resistance, chemical immunity, and lightweight structural support in commercial, industrial, and utility environments. However, nonmetallic materials exhibit high coefficients of thermal expansion and lack the innate conductivity of steel raceways, requiring dedicated equipment grounding conductors (EGCs) and carefully engineered expansion joints. Understanding the specific installation boundaries for Schedule 40 vs Schedule 80 PVC, Reinforced Thermosetting Resin Conduit (RTRC), Liquidtight Flexible Conduit (LFMC/LFNC), and Cable Tray systems is critical for passing the Oklahoma Journeyman Electrician examination.


1. Rigid Polyvinyl Chloride Conduit (PVC - NEC Article 352)

Rigid PVC conduit is the most widely installed underground and corrosive-environment raceway. It is impervious to moisture, acids, alkalis, and soil chemicals.

+---------------------------------------------------------------------------------------------------------+
|                                SCHEDULE 40 VS. SCHEDULE 80 PVC COMPARISON                               |
|                                                                                                         |
|  Feature / Parameter             Schedule 40 PVC (Article 352)         Schedule 80 PVC (Article 352)    |
|  -----------------------------   -----------------------------------   -------------------------------- |
|  Wall Thickness                  Standard wall thickness               Thick heavy-duty wall            |
|  Internal Cross-Sectional Area   Larger internal area                  Smaller internal area (less fill)|
|  Physical Damage Rating          Normal / moderate conditions          SUBJECT TO PHYSICAL DAMAGE       |
|  Emerging from Earth (300.5(D))  Requires protection where exposed     Approved for physical protection |
|  Direct Burial Cover Depth       18 inches (general soil)              18 inches (general soil)         |
|  Underground under Driveways     24 inches (commercial driveways)      24 inches (commercial driveways) |
+---------------------------------------------------------------------------------------------------------+

Schedule 40 vs. Schedule 80 Selection Rules (NEC 352.10(F))

  • Schedule 40 PVC: Permitted underground, direct-buried, encased in concrete, in walls/floors, and exposed in locations not subject to physical damage.
  • Schedule 80 PVC (Physical Damage Requirement): Where conduit is installed in areas subject to physical damage, Schedule 80 PVC is mandatory (NEC 352.10(F)). Examples include conduit emerging from grade on the exterior of commercial buildings, service riser poles, warehouse traffic aisles, and parking garages where vehicles or forklifts operate.
  • Conduit Fill Caution: Because Schedule 80 PVC has a much thicker wall, its inside diameter is significantly smaller than Schedule 40. Always use NEC Chapter 9 Table 4 (Schedule 80 PVC) when calculating conductor fill, as fewer conductors can fit into Schedule 80 than Schedule 40 of the same trade size.

Thermal Expansion & Contraction (NEC 352.44 & Table 352.44)

PVC has a high coefficient of thermal expansion ($3.06 \times 10^{-5}\text{ in./in.}/^\circ\text{F}$). In outdoor environments with seasonal temperature swings, long PVC conduit runs expand and contract dramatically, pulling out of boxes or buckling off walls if expansion joints are omitted.

ΔL=(Length in Feet100)×(ΔT in F100)×4.06 inches\Delta L = \left( \frac{\text{Length in Feet}}{100} \right) \times \left( \frac{\Delta T \text{ in } ^\circ\text{F}}{100} \right) \times 4.06\text{ inches}

+-----------------------------------------------------------------------------+
|                   PVC EXPANSION FITTING TRIGGER RULE                        |
|                            (NEC 352.44)                                     |
|                                                                             |
|   If the total estimated change in length (ΔL) between securely mounted     |
|   boxes or anchor points is 0.25 INCHES (6 mm) OR GREATER, an expansion    |
|   fitting MUST be installed!                                                |
+-----------------------------------------------------------------------------+

Worked Example: Rooftop Solar PVC Expansion Calculation

An electrician installs an 80-foot continuous exposed run of Schedule 40 PVC conduit across an Oklahoma commercial rooftop. The expected winter low is $-10^\circ\text{F}$ and the summer rooftop high is $130^\circ\text{F}$.

  1. Calculate Temperature Differential ($\Delta T$): ΔT=130F(10F)=140F\Delta T = 130^\circ\text{F} - (-10^\circ\text{F}) = 140^\circ\text{F}
  2. Determine Expansion from Table 352.44: From NEC Table 352.44, PVC expands $4.06\text{ inches}$ per $100\text{ ft}$ per $100^\circ\text{F}$ temperature change.
  3. Calculate Total Expansion Length ($\Delta L$): ΔL=(80 ft100)×(140F100)×4.06 in.=0.80×1.40×4.06=4.55 inches\Delta L = \left(\frac{80\text{ ft}}{100}\right) \times \left(\frac{140^\circ\text{F}}{100}\right) \times 4.06\text{ in.} = 0.80 \times 1.40 \times 4.06 = 4.55\text{ inches}
  4. Conclusion: Since $4.55\text{ inches} \ge 0.25\text{ inches}$, an expansion fitting is required. A listed expansion fitting providing at least 5 inches of travel (or two smaller fittings) must be installed.

Support Spacing for PVC Conduit (NEC Table 352.30)

Conduit Trade SizeMaximum Support Spacing
1/2 in. through 1 in.3 feet (900 mm)
1-1/4 in. through 2 in.5 feet (1.5 m)
2-1/2 in. through 3 in.6 feet (1.8 m)
3-1/2 in. through 5 in.7 feet (2.1 m)
6 in.8 feet (2.4 m)

Note: PVC conduit must also be securely fastened within 3 feet (900 mm) of each box, cabinet, or termination fitting.


2. Reinforced Thermosetting Resin Conduit (RTRC / Fiberglass - NEC Article 355)

Reinforced Thermosetting Resin Conduit (RTRC), commonly known as fiberglass conduit, is an engineered nonmetallic raceway manufactured from wound fiberglass filaments impregnated with thermosetting epoxy resin.

+-----------------------------------------------------------------------------+
|                        RTRC CLASSIFICATIONS (NEC 355)                       |
|                                                                             |
|   [Type RTRC-AG (Above Ground)]     - Standard wall for exposed/concealed   |
|   [Type RTRC-BG (Below Ground)]     - Thinner wall for direct burial/duct   |
|   [Type RTRC-XW (eXtra-Wall)]       - Heavy-wall listed for SEVERE PHYSICAL |
|                                       DAMAGE & Class I, Div 2 locations     |
+-----------------------------------------------------------------------------+

Key Advantages & Code Applications:

  • Thermal Stability: Coefficient of thermal expansion is significantly lower than PVC ($1.37 \times 10^{-5}\text{ in./in.}/^\circ\text{F}$ — less than half that of PVC).
  • Severe Physical Damage: Type RTRC-XW is specifically listed for installations where subject to severe physical damage (NEC 355.10(F)), such as highway bridges, railway overpasses, wastewater treatment plants, and coastal marine docks.
  • Low Smoke Zero Halogen (LSZH): Unlike PVC (which releases toxic hydrogen chloride gas when burned), RTRC releases non-toxic combustion products, making it ideal for transit tunnels and mining.

3. Flexible Conduits: FMC, LFMC & LFNC

Flexible raceways are designed to isolate vibration at motors, transformers, and HVAC equipment, and to facilitate routing through tight architectural obstructions.

+---------------------------------------------------------------------------------------------------------+
|                           FLEXIBLE RACEWAYS COMPARISON & LIMITATIONS                                    |
|                                                                                                         |
|  Raceway Type       Article   Permitted Environments   Max Support Interval   Securing from Enclosure   |
|  ----------------   -------   ----------------------   --------------------   -----------------------   |
|  FMC (Flex)         348       Dry only (indoor)        4.5 feet (1.4 m)       Within 12 in. (300 mm)    |
|  LFMC (Sealtite)    350       Wet / outdoor / oily     4.5 feet (1.4 m)       Within 12 in. (300 mm)    |
|  LFNC (Nonmetallic) 356       Wet / corrosive / burial 3.0 feet (900 mm)      Within 12 in. (300 mm)    |
+---------------------------------------------------------------------------------------------------------+

Equipment Grounding Limitations for Flexible Conduits (NEC 250.118):

  • FMC (NEC 250.118(5)): Listed FMC is permitted as an equipment grounding conductor ONLY if:
    1. The total length of the ground return path does not exceed 6 feet (1.8 m).
    2. The circuit conductors are protected by overcurrent devices rated at 20 amperes or less.
    3. Listed fittings are used. (If over 20A or > 6 ft, a separate copper EGC must be pulled inside!).
  • LFMC (NEC 250.118(6)): Listed LFMC is permitted as an EGC ONLY if:
    1. Total length does not exceed 6 feet (1.8 m).
    2. Overcurrent protection is rated $\le 20\text{A}$ (for 3/8"–1/2" trade size) or $\le 60\text{A}$ (for 3/4"–1-1/4" trade size).
    3. For runs $> 6\text{ ft}$ or higher overcurrent ratings, a dedicated equipment grounding conductor is mandatory.

Support Exceptions for Flexible Raceways:

  • Luminaire Taps (NEC 348.30(A) Ex. 3 & 350.30(A) Ex. 3): Lengths up to 6 feet (1.8 m) from an outlet box to a luminaire above an accessible drop ceiling are permitted without intermediate supports.
  • Flexibility at Terminals: Lengths up to 3 feet (900 mm) for LFNC or 3 feet for FMC/LFMC are permitted without support where flexibility is required at motor terminals or vibrating equipment.

4. Cable Trays (NEC Article 392)

Cable trays are rigid structural support systems designed to carry insulated conductors, power cables, control cables, and optical fiber cables in commercial and industrial facilities.

+-----------------------------------------------------------------------------+
|                        CABLE TRAY SYSTEM TYPES                              |
|                                                                             |
|   [Ladder Tray]            [Ventilated Trough]       [Solid Bottom Tray]    |
|   Two longitudinal side    Perforated steel/Al base  Solid sheet metal base |
|   rails joined by rungs;   providing partial bottom  providing maximum EMI  |
|   maximum heat dissipation support & ventilation     shielding & drop prot  |
+-----------------------------------------------------------------------------+

Permitted Cable Types (NEC 392.10(A)):

  • Metal-Clad Cable (Type MC)
  • Power and Control Tray Cable (Type TC)
  • Mineral-Insulated Metal-Sheathed Cable (Type MI)
  • Instrumentation Tray Cable (Type ITC)
  • Armored Cable (Type AC)
  • Optical Fiber Cables and Communication Cables

Single-Conductor Cable Rules in Cable Trays (NEC 392.10(B)(1)):

  1. Minimum Conductor Size: Single conductors installed in cable tray must be size 1/0 AWG or larger and marked for cable tray use (marked "CT" or "for CT use"). Conductors smaller than 1/0 AWG are prohibited as single conductors in cable tray (they must be in multiconductor cables).
  2. Single Layer Installation (NEC 392.22(B)(1)): Where single-conductor cables are sizes 1/0 AWG through 4/0 AWG, they must be installed in a single layer in ladder or ventilated trough cable trays.

Metal Cable Trays as Equipment Grounding Conductors (NEC 392.60(B)):

Steel or aluminum cable trays are permitted to be used as Equipment Grounding Conductors (EGCs) provided ALL of the following four conditions are met:

  1. Marking: The cable tray sections and fittings are identified and marked with their minimum cross-sectional area.
  2. Minimum Cross-Sectional Area: The total cross-sectional area of metal meets or exceeds the requirements of NEC Table 392.60(A) based on the largest rating of overcurrent device protecting circuits in the tray.
  3. Bonding Jumpers: All tray joints, expansion splices, and mechanical connections are bonded using listed bonding jumpers sized per NEC 250.102(D) or listed mechanical bonding splice plates.
  4. Qualified Maintenance: In industrial establishments where conditions of maintenance and supervision ensure that only qualified persons service the installation.

5. The Remaining Raceway Articles the PSI Outline Lists

The Raceways and Boxes subject area enumerates 22 sub-topics but carries only 7 scored items, so the Code expects you to recognize each raceway type and know its one defining limitation rather than to master every article. The types not covered above:

RacewayArticleThe limitation that defines it
Type FMT — Flexible Metallic Tubing360Dry locations only, and permitted only in lengths not exceeding 6 feet. Manufactured in trade sizes ½ and ¾ only. Not permitted in hoistways, in storage battery rooms, in hazardous (classified) locations, underground, embedded in concrete or aggregate, or where subject to physical damage. FMT is not an equipment grounding conductor — an EGC must be installed in the tubing.
Surface Metal Raceway386Dry locations only. Not permitted where subject to severe physical damage, where corrosive vapors exist, in hoistways, or in classified locations except as specifically permitted. Where it is a combination raceway with separate compartments for power and signal conductors, the compartments must be identified by stamping, imprinting, or color coding the interior surface.
Surface Nonmetallic Raceway388Dry locations only, and additionally barred from concealed locations, from ambient temperatures above the listing, and from circuits where the voltage exceeds 300 volts between conductors unless the raceway has a metal cover.
Underfloor Raceway390Permitted under the floor surface with defined cover; not permitted where corrosive vapors are present, in hazardous locations except as permitted, or in commercial garages other than for supplying outlets under the floor. Junction boxes must be level with the floor and sealed against water.
Auxiliary Gutter366A wiring supplement, not a distribution raceway: it may not extend more than 30 inches beyond the equipment it supplements except in specific industrial cases, and conductor fill is limited (generally 20 percent, with a 30-conductor current-carrying limit before derating).
Busway368A listed assembly of busbars in a protective housing, supported at defined intervals; totally enclosed busway may be run vertically through floors and horizontally through dry walls with specific firestopping and length conditions.
Metal and Nonmetallic Wireway376 / 378A sheet-metal or nonmetallic trough with a hinged or removable cover: conductor fill is limited to 20 percent of the interior cross-sectional area, and 30 current-carrying conductors is the point at which adjustment factors begin to apply.

[!IMPORTANT] Three numbers from this table earn their keep on exam day. FMT is capped at 6 feet. Surface nonmetallic raceway is barred above 300 volts between conductors unless it has a metal cover. Wireways and auxiliary gutters share the 20 percent fill / 30 current-carrying conductor pair — the same two figures, applied to two different articles.

Loading diagram...
Nonmetallic Raceways & Cable Tray Decision Tree (NEC Articles 350, 352, 355, 356, 392)
Test Your Knowledge

An electrical contractor is installing an exposed raceway along the exterior wall of a commercial warehouse in Tulsa, Oklahoma, where delivery trucks and forklifts operate daily. According to NEC 352.10(F), which nonmetallic raceway method is required?

A
B
C
D
Test Your Knowledge

A continuous 100-foot run of Schedule 40 PVC conduit is installed across a commercial roof deck in Oklahoma City. The temperature differential between the coldest winter night (-10°F) and hottest summer direct-sun roof exposure (140°F) is 150°F. Using NEC Table 352.44 (4.06 inches per 100 ft per 100°F), what is the total calculated thermal expansion length, and is an expansion fitting required?

A
B
C
D
Test Your Knowledge

An electrician connects a 30-horsepower, 480V 3-phase industrial motor using an 8-foot length of 1-inch Liquidtight Flexible Metal Conduit (LFMC). The branch circuit is protected by an 80-ampere inverse-time circuit breaker. Under NEC 250.118(6) and 350.60, what is required regarding equipment grounding?

A
B
C
D
Test Your Knowledge

An industrial facility in Oklahoma is installing single-conductor insulated cables in a ventilated ladder cable tray system. According to NEC 392.10(B)(1), what is the minimum conductor size permitted for single conductors in cable tray installations?

A
B
C
D
Test Your Knowledge

An electrician needs a short flexible connection in a dry mechanical room and reaches for Type FMT (flexible metallic tubing). Which statement about FMT is correct under NEC Article 360?

A
B
C
D