2.4 Electrical Units, Formulas & Conversions

Key Takeaways

  • Electrical units follow strict derived relationships: Potential in Volts (V = J/C), Current in Amperes (A = C/s), Resistance in Ohms (Ω = V/A), Power in Watts (W = J/s), Energy in Joules or Kilowatt-hours (1 kWh = 3,412 BTU = 3.6 MJ), Capacitance in Farads (F), and Inductance in Henrys (H).
  • Power and thermal conversion constants bridge mechanical and HVAC loads to electrical parameters: 1 Horsepower (HP) = 746 Watts; 1 Kilowatt (kW) = 3,412 BTU/hr; and 1 Ton of Air Conditioning = 12,000 BTU/hr = 3.517 kW (3,517 W).
  • Conductor cross-sectional area is measured in Circular Mils (cmil = d², where d is conductor diameter in mils and 1 mil = 0.001 inch), with large conductors rated in kcmil (thousands of circular mils).
  • Conductor voltage drop is calculated using VD = (2 × K × I × D) / cmil for single-phase circuits and VD = (1.732 × K × I × D) / cmil for three-phase circuits, where K-factor constants at 75°C are 12.9 Ω·cmil/ft for Copper and 21.2 Ω·cmil/ft for Aluminum.
  • National Electrical Code recommendations (NEC 210.19(A) Informational Note No. 4 and NEC 215.2(A)(1)(b) Informational Note No. 2) advise limiting voltage drop to a maximum of 3% on branch circuits or feeders, and no more than 5% total across the entire distribution system from the service disconnecting means to the farthest outlet.
Last updated: August 2026

Electrical Units, Formulas & Conversions

Precise unit conversions, conductor area calculations, and voltage drop evaluations are essential competencies for journeyman electricians. System performance, equipment longevity, and fire safety depend on selecting conductors capable of handling circuit continuous loads while restricting voltage drop within acceptable operating limits. This section provides a comprehensive technical reference for SI electrical units, thermal/mechanical conversions, conductor geometry (circular mils), exact voltage drop calculations, and equipment efficiency formulas.


1. Master Electrical Units & Derived Standards

Every electrical calculation utilizes fundamental units defined by the International System of Units (SI) and derived electromagnetic relationships.

Electrical QuantitySymbolUnit NameUnit SymbolMathematical / Physical Derivation
Electromotive Force (Potential)$E, V$Volt$\text{V}$$1\text{ V} = 1\text{ Joule} / 1\text{ Coulomb} = 1\text{ W} / 1\text{ A}$
Electric Current$I$Ampere$\text{A}$$1\text{ A} = 1\text{ Coulomb} / 1\text{ second} = 6.242 \times 10^{18}\text{ electrons/s}$
Electrical Resistance$R$Ohm$\Omega$$1\ \Omega = 1\text{ Volt} / 1\text{ Ampere}$
Electrical Conductance$G$Siemens (Mho)$\text{S}$$G = 1 / R$; $1\text{ S} = 1\text{ A} / 1\text{ V}$
Electric Power$P$Watt$\text{W}$$1\text{ W} = 1\text{ Joule} / 1\text{ second} = 1\text{ V} \times 1\text{ A}$
Electric Energy / Work$W, E$Joule / kWh$\text{J, kWh}$$1\text{ J} = 1\text{ W}\cdot\text{s}$; $1\text{ kWh} = 3,600,000\text{ J} = 3.6\text{ MJ}$
Electrostatic Capacitance$C$Farad$\text{F}$$1\text{ F} = 1\text{ Coulomb} / 1\text{ Volt}$
Magnetic Inductance$L$Henry$\text{H}$$1\text{ H} = 1\text{ Volt}\cdot\text{second} / 1\text{ Ampere}$
Frequency$f$Hertz$\text{Hz}$$1\text{ Hz} = 1\text{ cycle} / 1\text{ second}$
Electric Charge$Q$Coulomb$\text{C}$$1\text{ C} = 1\text{ Ampere} \times 1\text{ second}$
Magnetic Flux$\Phi$Weber$\text{Wb}$$1\text{ Wb} = 1\text{ Volt}\cdot\text{second} = 10^8\text{ Maxwells}$
Magnetic Flux Density$B$Tesla$\text{T}$$1\text{ T} = 1\text{ Wb}/\text{m}^2 = 10,000\text{ Gauss}$

2. Power, Mechanical & Thermal Conversions

In commercial and residential trade work, electricians frequently interface with mechanical equipment rated in horsepower (HP) and HVAC/heating equipment rated in British Thermal Units (BTU).

+-----------------------------------------------------------------------------------------+
|                                ESSENTIAL CONVERSION CONSTANTS                           |
|                                                                                         |
|   1. Mechanical Power to Electrical Power:                                              |
|      • 1 Horsepower (HP) = 746 Watts = 0.746 Kilowatts                                  |
|      • Watts = HP × 746                                                                 |
|      • HP = Watts / 746                                                                 |
|                                                                                         |
|   2. Thermal Energy to Electrical Power:                                                |
|      • 1 Kilowatt (kW) = 3,412 BTU/hr                                                   |
|      • 1 Kilowatt-hour (kWh) = 3,412 BTU of thermal heat                                |
|      • Heating Watts = (BTU/hr) / 3.412                                                 |
|                                                                                         |
|   3. Air Conditioning & Refrigeration Capacity:                                         |
|      • 1 Ton of Refrigeration = 12,000 BTU/hr                                           |
|      • 1 Ton of Refrigeration = 12,000 / 3,412 = 3.517 kW = 3,517 Watts                 |
+-----------------------------------------------------------------------------------------+

Conversion Example: Commercial Duct Heater

A commercial building blueprint specifies a supplemental electric duct heater rated at $68,240\text{ BTU/hr}$.

  • Electrical power required in Kilowatts: $P = \frac{68,240\text{ BTU/hr}}{3,412\text{ BTU/kWh}} = 20.0\text{ kW} = 20,000\text{ Watts}$.
  • If operating at $240\text{V}$ single-phase: Current $I = \frac{20,000\text{ W}}{240\text{V}} = 83.33\text{ A}$.

3. Conductor Geometry, Mils & Circular Mils (cmil)

In North American electrical engineering and NEC tables, wire sizes are expressed in American Wire Gauge (AWG) from 18 AWG up to 4/0 AWG, and in kcmil (thousands of circular mils) for conductors $250\text{ kcmil}$ and larger.

+-----------------------------------------------------------------------------------------+
|                              CIRCULAR MIL DEFINITIONS & AREA                            |
|                                                                                         |
|   • 1 Mil = 0.001 inch (one-thousandth of an inch)                                      |
|   • Diameter (d) in Mils = Diameter in inches × 1,000                                   |
|   • Circular Mil Area (cmil) = d²  (where d is diameter in mils)                        |
|                                                                                         |
|   Comparison between Square Mils and Circular Mils:                                     |
|   • Area in Square Mils = (π / 4) × d² ≈ 0.7854 × cmil                                  |
|   • Area in Circular Mils = Area in Square Mils / 0.7854 ≈ 1.2732 × Square Mils         |
+-----------------------------------------------------------------------------------------+

NEC Chapter 9, Table 8 Conductor Properties (Key Copper Standards):

  • 14 AWG: $4,110\text{ cmil}$ (Solid diameter $\approx 64.1\text{ mils}$)
  • 12 AWG: $6,530\text{ cmil}$ (Solid diameter $\approx 80.8\text{ mils}$)
  • 10 AWG: $10,380\text{ cmil}$ (Solid diameter $\approx 101.9\text{ mils}$)
  • 8 AWG: $16,510\text{ cmil}$
  • 6 AWG: $26,240\text{ cmil}$
  • 4 AWG: $41,740\text{ cmil}$
  • 3 AWG: $52,620\text{ cmil}$
  • 2 AWG: $66,360\text{ cmil}$
  • 1 AWG: $83,690\text{ cmil}$
  • 1/0 AWG: $105,600\text{ cmil}$
  • 2/0 AWG: $133,100\text{ cmil}$
  • 3/0 AWG: $167,800\text{ cmil}$
  • 4/0 AWG: $211,600\text{ cmil}$
  • $250\text{ kcmil}$: $250,000\text{ cmil}$
  • $500\text{ kcmil}$: $500,000\text{ cmil}$

Rectangular Copper Busbar Calculation:

A copper switchboard busbar measures $1/4\text{ inch} \times 2\text{ inches}$ in cross-section.

  • Convert dimensions to mils: $0.250\text{ in} = 250\text{ mils}$; $2.000\text{ in} = 2,000\text{ mils}$.
  • Area in square mils: $A_{\text{sq mils}} = 250 \times 2,000 = 500,000\text{ sq mils}$.
  • Convert square mils to circular mils: $\text{cmil} = \frac{500,000}{0.7854} = 636,618\text{ cmil} \approx 636.6\text{ kcmil}$.

4. Comprehensive Voltage Drop Calculations & NEC Guidelines

When electrical current travels through a circuit conductor, the internal resistance of the wire creates an unavoidable voltage drop ($I \times R$). If conductors are undersized or circuit runs are excessively long, the reduced operating voltage causes motor overheating, contactor chattering, dim lighting, and electronic device failure.

+-----------------------------------------------------------------------------------------+
|                                 VOLTAGE DROP FORMULAS                                   |
|                                                                                         |
|   1. Single-Phase Voltage Drop:      VD = ( 2 × K × I × D ) / cmil                      |
|                                                                                         |
|   2. Three-Phase Voltage Drop:       VD = ( √3 × K × I × D ) / cmil                     |
|                                         = ( 1.732 × K × I × D ) / cmil                  |
|                                                                                         |
|   3. Sizing Conductor Area (cmil):                                                      |
|      • Single-Phase:                 cmil = ( 2 × K × I × D ) / VD_allowable            |
|      • Three-Phase:                  cmil = ( 1.732 × K × I × D ) / VD_allowable        |
|                                                                                         |
|   Where:                                                                                |
|   • K = Specific Conductor Resistance at 75°C:                                          |
|         - Copper (Cu):   K = 12.9 Ω·cmil/ft                                             |
|         - Aluminum (Al): K = 21.2 Ω·cmil/ft                                             |
|   • I = Load Current in Amperes                                                         |
|   • D = One-Way Circuit Distance in Feet                                                |
|   • cmil = Conductor Cross-Sectional Area in Circular Mils (NEC Ch 9, Table 8)          |
|   • Factor '2' in single-phase accounts for out-and-back conductor loop                  |
|   • Factor '√3' (1.732) in three-phase accounts for 120° vector phase relationship      |
+-----------------------------------------------------------------------------------------+

National Electrical Code Voltage Drop Standards (Informational Notes):

  • NEC 210.19(A) Informational Note No. 4 (Branch Circuits): Recommends that branch circuit conductors be sized to limit voltage drop to no more than $3%$ of nominal circuit voltage at the farthest outlet supplying power, heating, or lighting loads.
  • NEC 215.2(A)(1)(b) Informational Note No. 2 (Feeders): Recommends that feeder conductors be sized to limit voltage drop to no more than $3%$.
  • Total Combined System Limit: The maximum total combined voltage drop on both the feeder and the branch circuit combined should not exceed $5%$ from the service disconnecting means to the final load outlet.

Maximum Allowable Voltage Drops by System Voltage:

  • $120\text{V}$ Circuit: $3% = 3.60\text{V}$; $5% = 6.00\text{V}$
  • $208\text{V}$ Circuit: $3% = 6.24\text{V}$; $5% = 10.40\text{V}$
  • $240\text{V}$ Circuit: $3% = 7.20\text{V}$; $5% = 12.00\text{V}$
  • $277\text{V}$ Circuit: $3% = 8.31\text{V}$; $5% = 13.85\text{V}$
  • $480\text{V}$ Circuit: $3% = 14.40\text{V}$; $5% = 24.00\text{V}$

Step-by-Step Worked Problems:

Problem 1: Evaluating Single-Phase Voltage Drop & Upsizing

A $120\text{V}$, single-phase parking lot lighting branch circuit carries a continuous load of $16\text{ A}$ copper conductors over a one-way distance of $175\text{ feet}$ using $12\text{ AWG}$ THHN copper ($6,530\text{ cmil}$).

  1. Calculate Actual Voltage Drop: VD=2×K×I×Dcmil=2×12.9×16 A×175 ft6,530 cmil=72,2406,530=11.06V\text{VD} = \frac{2 \times K \times I \times D}{\text{cmil}} = \frac{2 \times 12.9 \times 16\text{ A} \times 175\text{ ft}}{6,530\text{ cmil}} = \frac{72,240}{6,530} = 11.06\text{V}
  2. Calculate Percentage Drop: %VD=(11.06V120V)×100%=9.22%(Fails 3% limit of 3.60V)\%\text{VD} = \left(\frac{11.06\text{V}}{120\text{V}}\right) \times 100\% = 9.22\% \quad (\text{Fails 3\% limit of 3.60V})
  3. Calculate Minimum Circular Mils to Meet 3% Limit ($3.60\text{V}$ max drop): cmilrequired=2×12.9×16×1753.60V=72,2403.60=20,066.67 cmil\text{cmil}_{\text{required}} = \frac{2 \times 12.9 \times 16 \times 175}{3.60\text{V}} = \frac{72,240}{3.60} = 20,066.67\text{ cmil}
  4. Select Conductor from NEC Chapter 9, Table 8:
    • $8\text{ AWG} = 16,510\text{ cmil}$ (Too small)
    • $6\text{ AWG} = 26,240\text{ cmil}$ (Complies; actual drop with $6\text{ AWG} = 2.75\text{V} = 2.29%$).

Problem 2: Sizing Three-Phase Feeder for Voltage Drop

A $480\text{V}$, 3-phase commercial building feeder supplies an industrial rooftop chiller drawing $75\text{ A}$ over a one-way distance of $350\text{ feet}$ using copper conductors. Sizing for a maximum $3%$ voltage drop ($14.40\text{V}$ maximum allowable drop):

  1. Calculate Required Circular Mil Area: cmil=1.732×K×I×DVDallowable=1.732×12.9×75 A×350 ft14.40V=586,48214.40=40,727.9 cmil\text{cmil} = \frac{1.732 \times K \times I \times D}{\text{VD}_{\text{allowable}}} = \frac{1.732 \times 12.9 \times 75\text{ A} \times 350\text{ ft}}{14.40\text{V}} = \frac{586,482}{14.40} = 40,727.9\text{ cmil}
  2. Select Conductor from NEC Chapter 9, Table 8:
    • $6\text{ AWG} = 26,240\text{ cmil}$ (Too small)
    • $4\text{ AWG} = 41,740\text{ cmil}$ (Properly sized to comply with $3%$ threshold).

5. Electrical Equipment Efficiency Formulas

Efficiency ($\eta$) measures how effectively electrical equipment converts electrical input power into useful mechanical or thermal output power without wasting energy as heat.

+-----------------------------------------------------------------------------------------+
|                                 EQUIPMENT EFFICIENCY FORMULAS                           |
|                                                                                         |
|   1. Efficiency (η) = ( Power Output / Power Input ) × 100%                             |
|                     = ( Watts_Out / Watts_In ) × 100%                                   |
|                                                                                         |
|   2. Input Power (Watts_In) = Watts_Out / η                                             |
|                                                                                         |
|   3. Single-Phase Motor Input Current:                                                  |
|      I = ( HP × 746 ) / ( Voltage × PF × η )                                            |
|                                                                                         |
|   4. Three-Phase Motor Input Current:                                                   |
|      I = ( HP × 746 ) / ( √3 × Voltage × PF × η )                                       |
+-----------------------------------------------------------------------------------------+

Motor Efficiency Worked Example:

A $15\text{ HP}$, $230\text{V}$, single-phase motor has an efficiency rating of $86%$ ($0.86$) and operates at a power factor of $0.88$.

  1. Mechanical Output Power: $P_{\text{out}} = 15\text{ HP} \times 746\text{ W/HP} = 11,190\text{ Watts}$.
  2. Electrical Input Power: $P_{\text{in}} = \frac{11,190\text{ W}}{0.86} = 13,011.63\text{ Watts}$.
  3. Full-Load Current Drawn: I=13,011.63 W230V×0.88=13,011.63202.4=64.29 AmperesI = \frac{13,011.63\text{ W}}{230\text{V} \times 0.88} = \frac{13,011.63}{202.4} = 64.29\text{ Amperes}
Loading diagram...
Conductor Voltage Drop & Sizing Decision Workflow
Test Your Knowledge

A 120V single-phase circuit supplies a 15A load over a one-way distance of 125 feet using 12 AWG copper conductors (6,530 cmil, K = 12.9). What is the total voltage drop on this circuit, and does it comply with the NEC recommended 3% branch circuit limit?

A
B
C
D
Test Your Knowledge

A 25 HP, 460V, three-phase motor has an efficiency rating of 89.5% and operates at a power factor of 0.84. What is the full-load operating current drawn by the motor?

A
B
C
D
Test Your Knowledge

A solid rectangular copper busbar measures 3/8 inch by 1.5 inches in cross-section. What is the cross-sectional area of this busbar expressed in circular mils (cmil)?

A
B
C
D
Test Your Knowledge

A commercial electric heating package for a central air handling unit is rated to produce 102,360 BTU/hr of thermal output. What is the electrical power rating of this heater in Kilowatts (kW)?

A
B
C
D