13.2 Appliances & Fixed Electric Space Heating (NEC Articles 422 & 424)
Key Takeaways
- NEC 422.13 classifies a fixed storage-type water heater with a capacity of 120 gallons or less as a continuous load, so its branch circuit conductors and overcurrent device are sized at 125 percent of the nameplate rating.
- NEC 422.16(B)(2) permits a cord for a waste disposer with a length of 18 to 36 inches, and 422.16(B)(3) permits a cord for a built-in dishwasher or trash compactor with a length of 3 to 4 feet measured from the face of the attachment plug to the plane of the rear of the appliance.
- NEC 422.31(A) permits the branch-circuit overcurrent device to serve as the disconnecting means for a permanently connected appliance rated at not over 300 volt-amperes or 1/8 horsepower, while 422.31(B) requires an appliance rated over 300 volt-amperes to have a disconnect within sight or a branch-circuit switch or breaker capable of being locked in the open position.
- NEC 424.3(B) classifies fixed electric space-heating equipment as a continuous load, requiring branch-circuit conductors and overcurrent protection sized at not less than 125 percent of the total heating load including any motors.
- NEC 424.44(G) requires ground-fault circuit-interrupter protection for personnel for electrically heated floors in bathrooms, kitchens, and in hydromassage bathtub, spa, and hot tub locations.
13.2 Appliances & Fixed Electric Space Heating (NEC Articles 422 & 424)
Exam Focus: 422.10 branch-circuit rating, 422.13 water heater continuous load, 422.16 cord lengths, 422.31/422.33 disconnecting means, 424.3(B) heating as continuous load, 424.44(G) heated floor GFCI, and Article 440 nameplate MCA/MOP.
Appliances is a named subject on the PSI blueprint. The rules divide cleanly into three: how big the circuit must be, how the appliance may be connected, and how it is disconnected for service.
Sizing the Appliance Branch Circuit — Article 422 Part II
| Rule | Requirement |
|---|---|
| 422.10(A) | For an individual branch circuit, the rating must not be less than the marked rating of the appliance, or not less than the marked rating of an appliance having combined heating, motor, and other loads |
| 422.10(B) | For a circuit supplying two or more loads, the rating is determined in accordance with 210.23 |
| 422.11 | Appliances must be protected against overcurrent; a single non-motor-operated appliance rated 13.3 A or more must have branch-circuit protection not exceeding 150% of the marked rating, and where that does not correspond to a standard size, the next higher standard size is permitted |
| 422.12 | Central heating equipment other than fixed electric space heating must be supplied by an individual branch circuit, with permitted exceptions for auxiliary equipment such as a pump, valve, humidifier, or air cleaner directly associated with the heating equipment |
The Two Continuous-Load Classifications
+-------------------------------------------------------------------------+
| APPLIANCES THE CODE CALLS CONTINUOUS LOADS |
| |
| 422.13 Fixed STORAGE-TYPE WATER HEATER, 120 gallons or less |
| --> branch circuit sized at 125% of nameplate rating |
| |
| 424.3(B) FIXED ELECTRIC SPACE-HEATING EQUIPMENT |
| --> conductors and OCPD at 125% of total heating load, |
| including any motors |
| |
| Example: a 4,500 W, 240 V water heater draws 18.75 A. |
| 18.75 x 1.25 = 23.4 A --> 25 A OCPD, 10 AWG copper conductors. |
+-------------------------------------------------------------------------+
[!CAUTION] The 120-gallon threshold is exact. A storage water heater of 120 gallons or less is a continuous load. A larger commercial storage heater is not automatically classified that way by 422.13, though it may still be a continuous load in fact under the Article 100 three-hour definition.
Flexible Cord Connection — NEC 422.16
Cord-and-plug connection is a permitted method for specific appliances, with specific cord lengths that examiners like because they are exact numbers.
| Appliance | Permitted Cord Length | Other Conditions |
|---|---|---|
| Waste (garbage) disposer | 18 in to 36 in | Receptacle located to avoid physical damage to the cord; receptacle accessible; cord identified for the purpose |
| Built-in dishwasher or trash compactor | 3 ft to 4 ft (0.9 m to 1.2 m), measured from the face of the attachment plug to the plane of the rear of the appliance | Receptacle located in the space occupied by the appliance or adjacent to it, accessible, and cord identified for the purpose |
| Range hood | 18 in to 36 in | Receptacle accessible and supplied by an individual branch circuit |
| Household electric range, wall oven, counter-mounted cooking unit | Cord and plug permitted where the connection is accessible from the front by removal of a drawer | Cord identified for the purpose |
Measurement trap: the dishwasher and compactor length is measured to the plane of the rear of the appliance, not to the terminal box. Options that describe the measurement any other way are wrong.
Appliance Disconnecting Means — Article 422 Part III
| Situation | Permitted Disconnect |
|---|---|
| Permanently connected, rated not over 300 VA or 1/8 hp (422.31(A)) | The branch-circuit overcurrent device may serve as the disconnecting means |
| Permanently connected, rated over 300 VA (422.31(B)) | The branch-circuit switch or circuit breaker may serve as the disconnecting means where it is within sight from the appliance or is capable of being locked in the open position; the locking provision must remain in place with or without the lock installed |
| Cord-and-plug connected (422.33) | An accessible separable connector or an accessible plug and receptacle may serve as the disconnecting means |
| Motor-operated appliance rated over 1/8 hp (422.32) | The disconnecting means must comply with the motor rules and be within sight from the appliance, or capable of being locked open |
| Unit switches (422.34) | A unit switch with a marked-off position that disconnects all ungrounded conductors may serve as the disconnecting means where other means are provided, which differ by occupancy type |
Fixed Electric Space Heating — Article 424
| Rule | Requirement |
|---|---|
| 424.3(B) | Fixed electric space-heating equipment is a continuous load; conductors and overcurrent protection at 125% of the total load, including motors |
| 424.4 | Branch circuits for fixed electric space heating are limited to the ratings recognized in Article 210, and the supply circuits must be sized for the total load |
| 424.19 | A disconnecting means must disconnect the heater, motor controller, and supplementary overcurrent devices, and must be within sight or capable of being locked open |
| 424.35 | Heating cables must be marked at each end with the identification, catalog number, and rating in volts and watts, or volts and amperes |
| 424.36 | Heating cables must be installed only in ceilings and floors as permitted, and are not permitted in walls except where a portion runs vertically to reach a ceiling or floor location |
| 424.44(G) | GFCI protection for personnel is required for electrically heated floors in bathrooms, kitchens, and in hydromassage bathtub, spa, and hot tub locations |
Worked Example
A dwelling has 12 kW of baseboard electric heat plus a 5 A blower motor, supplied at 240 V.
- Heating current: $12{,}000 / 240 = 50\ \text{A}$
- Add the motor: $50 + 5 = 55\ \text{A}$
- Apply 424.3(B): $55 \times 1.25 = 68.75\ \text{A}$
- Minimum overcurrent device: 70 A, with conductors of at least 68.75 A ampacity at the applicable terminal temperature column.
Air Conditioning and Refrigeration — Article 440 Nameplate Rules
Hermetic refrigerant motor-compressors do not follow the general motor rules of Article 430. Instead, the equipment nameplate carries two numbers that override the usual calculations:
| Nameplate Value | Meaning | Use |
|---|---|---|
| MCA — Minimum Circuit Ampacity | The minimum conductor ampacity the manufacturer requires | Size the conductors to at least this value |
| MOP or MOCP — Maximum Overcurrent Protective device | The largest permitted branch-circuit short-circuit and ground-fault device | Select an OCPD not exceeding this value |
The MOP commonly exceeds what 240.4(D) would allow for the conductor size, which is one of the specific exemptions listed in 240.4(G). A 14 AWG conductor with an MCA of 14.2 A and an MOP of 25 A is a legitimate installation on a 25 A device — the fuse or breaker is providing short-circuit and ground-fault protection while the compressor's internal overload protects against overload.
2023 reminder: an outdoor condensing unit outlet in a dwelling requires GFCI protection under 210.8(F), and the outdoor emergency disconnect and surge protection rules in Section 10.4 apply to the dwelling service that feeds it.
A 4,500-watt, 240-volt fixed storage-type water heater with a 50-gallon capacity is installed in a dwelling. What minimum branch-circuit rating does NEC 422.13 produce?
What flexible cord length does NEC 422.16(B)(3) permit for a built-in dishwasher, and how is it measured?
A permanently connected 5,000-volt-ampere appliance is installed 40 feet from its panelboard and out of sight of it. What does NEC 422.31(B) require for the disconnecting means?
An air-conditioning condensing unit nameplate lists a minimum circuit ampacity of 14.2 amperes and a maximum overcurrent protective device of 25 amperes. What does Article 440 permit?