11.3 Power Factor, Efficiency & Transformer Theory
Key Takeaways
Power factor is the ratio of true power in watts to apparent power in volt-amperes, and a purely resistive load has a power factor of 1.0 while inductive loads such as motors lag with power factors typically between 0.80 and 0.95.
True power P equals apparent power S multiplied by power factor, so amperes for a motor load are calculated from volt-amperes rather than from watts.
Transformer voltage, current, and turns follow the relationships Ep/Es = Np/Ns and Ep x Ip = Es x Is, so a step-down in voltage produces a proportional step-up in current.
Transformer kVA is the same on both the primary and the secondary, which is why secondary full-load amperes are found by dividing the kVA by the secondary voltage, times 1.732 for three-phase.
Efficiency is output power divided by input power expressed as a percent, and the difference is dissipated as core loss and copper loss inside the equipment.
11.3 Power Factor, Efficiency & Transformer Theory
Exam Focus: True/reactive/apparent power and the power triangle, power factor arithmetic, transformer turns and current ratios, primary and secondary full-load current, and efficiency.
Load calculation questions give you volt-amperes. Nameplate questions often give you watts and a power factor. Knowing how to move between them is what separates a correct feeder size from a wrong one.
Three Kinds of Power
| Symbol | Name | Unit | What It Is |
|---|---|---|---|
| P | True (real, active) power | Watts (W) | Power actually converted to work or heat |
| Q | Reactive power | Volt-amperes reactive (VAR) | Power exchanged with magnetic or electrostatic fields; does no work but occupies conductor capacity |
| S | Apparent power | Volt-amperes (VA) | The vector total the conductors and transformer must actually carry |
THE POWER TRIANGLE
/|
/ |
S (VA) / | Q (VAR)
Apparent / | Reactive
/ angle |
/__________|
P (W)
True Power
P = S x cos(angle) PF = P / S
S = sqrt(P^2 + Q^2)
Power Factor
| Load Type | Typical Power Factor | Behavior |
|---|---|---|
| Incandescent lamp, resistance heater, electric range | 1.00 | Unity — current in phase with voltage |
| Induction motor at full load | 0.80 – 0.90 | Lagging — current lags voltage |
| Lightly loaded induction motor | 0.30 – 0.60 | Strongly lagging; the worst case for utility billing |
| Capacitor bank | Leading | Used to correct a lagging system |
Worked Example
A single-phase 240 V motor draws 20 A at a power factor of 0.85.
- Apparent power:
- True power:
Notice the direction of travel: the conductor and overcurrent device are sized from the 4,800 VA / 20 A, not from the 4,080 W. Sizing from watts would undersize the circuit.
Caution
Do not divide watts by volts for a motor. For any load with a power factor below unity, for single-phase and for three-phase. On the exam, Article 430 sidesteps this entirely by giving you full-load current directly in Tables 430.248 and 430.250 — use those tables for motor circuit sizing, and reserve the power-factor formula for theory items.
Efficiency
A motor delivering 10 hp of mechanical output while drawing 8,500 W:
- Output in watts:
- Efficiency:
1 horsepower = 746 watts. Memorize it; it appears in motor questions constantly.
Transformer Theory
A transformer transfers energy between two coils by mutual induction. It changes voltage and current, but not power (apart from losses) and not frequency.
The Three Ratios
Read carefully: voltage and turns move together, while current moves opposite. A step-down transformer has more primary turns, less secondary voltage, and more secondary current.
Worked Example — Turns and Current
A single-phase transformer has 800 primary turns and 100 secondary turns, with 480 V applied to the primary.
- Turns ratio: (step-down)
- Secondary voltage:
- If the secondary delivers 40 A, primary current is
- Check: and ✔
Full-Load Current from kVA
The kVA rating is the same on both sides. Use the voltage of the side you want.
| System | Full-Load Current |
|---|---|
| Single-phase | |
| Three-phase |
Example: a 75 kVA, three-phase transformer with a 208 V secondary.
And its 480 V primary:
These two numbers feed directly into the Article 450 overcurrent protection rules covered in Chapter 8.
Transformer Losses
- Core (iron) loss — hysteresis and eddy currents in the steel. Essentially constant whenever the transformer is energized, regardless of load.
- Copper loss — in the windings. Varies with the square of the load current.
Because core loss is constant, a lightly loaded transformer is an inefficient transformer, and an energized but unloaded transformer still consumes power.
Quick Reference
| Relationship | Formula |
|---|---|
| Power factor | |
| True power from VA | |
| Horsepower to watts | |
| Efficiency | |
| Transformer ratio | |
| 3-phase FLA from kVA |
A single-phase 240-volt motor draws 25 amperes at a power factor of 0.80. What is the true power in watts?
6,000 watts
4,800 watts
7,500 watts
3,840 watts
A single-phase transformer has 1,200 turns on the primary and 200 turns on the secondary. With 480 volts applied to the primary and a 30-ampere secondary load, what are the secondary voltage and the primary current?
2,880 volts and 180 amperes
480 volts and 30 amperes
80 volts and 5 amperes
80 volts and 180 amperes
What is the full-load secondary current of a 45 kVA three-phase transformer with a 208-volt secondary?
124.9 amperes
216.3 amperes
187.5 amperes
54.1 amperes
Which statement correctly describes transformer losses?
Core loss varies with the square of the load current while copper loss is constant
Both core loss and copper loss are constant regardless of loading
Core loss is essentially constant whenever the transformer is energized, while copper loss varies with the square of the load current
Neither loss occurs when the secondary is unloaded
Sections you finish are checked off in the contents.