11.3 Power Factor, Efficiency & Transformer Theory

Key Takeaways

  • Power factor is the ratio of true power in watts to apparent power in volt-amperes, and a purely resistive load has a power factor of 1.0 while inductive loads such as motors lag with power factors typically between 0.80 and 0.95.

  • True power P equals apparent power S multiplied by power factor, so amperes for a motor load are calculated from volt-amperes rather than from watts.

  • Transformer voltage, current, and turns follow the relationships Ep/Es = Np/Ns and Ep x Ip = Es x Is, so a step-down in voltage produces a proportional step-up in current.

  • Transformer kVA is the same on both the primary and the secondary, which is why secondary full-load amperes are found by dividing the kVA by the secondary voltage, times 1.732 for three-phase.

  • Efficiency is output power divided by input power expressed as a percent, and the difference is dissipated as core loss and copper loss inside the equipment.

Last updated: August 2026

11.3 Power Factor, Efficiency & Transformer Theory

Exam Focus: True/reactive/apparent power and the power triangle, power factor arithmetic, transformer turns and current ratios, primary and secondary full-load current, and efficiency.

Load calculation questions give you volt-amperes. Nameplate questions often give you watts and a power factor. Knowing how to move between them is what separates a correct feeder size from a wrong one.


Three Kinds of Power

SymbolNameUnitWhat It Is
PTrue (real, active) powerWatts (W)Power actually converted to work or heat
QReactive powerVolt-amperes reactive (VAR)Power exchanged with magnetic or electrostatic fields; does no work but occupies conductor capacity
SApparent powerVolt-amperes (VA)The vector total the conductors and transformer must actually carry
                        THE POWER TRIANGLE
                                  /|
                                /  |
              S (VA)          /    |  Q (VAR)
            Apparent        /      |  Reactive
                          /  angle |
                        /__________|
                           P (W)
                          True Power

              P = S x cos(angle)          PF = P / S
              S = sqrt(P^2 + Q^2)

Power Factor

PF=P (watts)S (volt-amperes)PF = \frac{P\ (\text{watts})}{S\ (\text{volt-amperes})}
Load TypeTypical Power FactorBehavior
Incandescent lamp, resistance heater, electric range1.00Unity — current in phase with voltage
Induction motor at full load0.80 – 0.90Lagging — current lags voltage
Lightly loaded induction motor0.30 – 0.60Strongly lagging; the worst case for utility billing
Capacitor bankLeadingUsed to correct a lagging system

Worked Example

A single-phase 240 V motor draws 20 A at a power factor of 0.85.

  • Apparent power: S=240×20=4,800 VAS = 240 \times 20 = 4{,}800\ \text{VA}
  • True power: P=4,800×0.85=4,080 WP = 4{,}800 \times 0.85 = 4{,}080\ \text{W}

Notice the direction of travel: the conductor and overcurrent device are sized from the 4,800 VA / 20 A, not from the 4,080 W. Sizing from watts would undersize the circuit.

Caution

Do not divide watts by volts for a motor. For any load with a power factor below unity, I=PE×PFI = \dfrac{P}{E \times PF} for single-phase and I=P1.732×E×PFI = \dfrac{P}{1.732 \times E \times PF} for three-phase. On the exam, Article 430 sidesteps this entirely by giving you full-load current directly in Tables 430.248 and 430.250 — use those tables for motor circuit sizing, and reserve the power-factor formula for theory items.


Efficiency

% Efficiency=PoutputPinput×100\%\ \text{Efficiency} = \frac{P_{output}}{P_{input}} \times 100

A motor delivering 10 hp of mechanical output while drawing 8,500 W:

  • Output in watts: 10 hp×746=7,460 W10\ \text{hp} \times 746 = 7{,}460\ \text{W}
  • Efficiency: 7,460/8,500=0.878=87.8%7{,}460 / 8{,}500 = 0.878 = \mathbf{87.8\%}

1 horsepower = 746 watts. Memorize it; it appears in motor questions constantly.


Transformer Theory

A transformer transfers energy between two coils by mutual induction. It changes voltage and current, but not power (apart from losses) and not frequency.

The Three Ratios

EPES=NPNS=ISIP\frac{E_P}{E_S} = \frac{N_P}{N_S} = \frac{I_S}{I_P}

Read carefully: voltage and turns move together, while current moves opposite. A step-down transformer has more primary turns, less secondary voltage, and more secondary current.

EP×IP=ES×IS(ideal, no losses)E_P \times I_P = E_S \times I_S \quad (\text{ideal, no losses})

Worked Example — Turns and Current

A single-phase transformer has 800 primary turns and 100 secondary turns, with 480 V applied to the primary.

  1. Turns ratio: 800:100=8:1800 : 100 = 8 : 1 (step-down)
  2. Secondary voltage: 480/8=60 V480 / 8 = \mathbf{60\ \text{V}}
  3. If the secondary delivers 40 A, primary current is 40/8=5 A40 / 8 = \mathbf{5\ \text{A}}
  4. Check: 480×5=2,400 VA480 \times 5 = 2{,}400\ \text{VA} and 60×40=2,400 VA60 \times 40 = 2{,}400\ \text{VA} ✔

Full-Load Current from kVA

The kVA rating is the same on both sides. Use the voltage of the side you want.

SystemFull-Load Current
Single-phaseI=kVA×1000EI = \dfrac{kVA \times 1000}{E}
Three-phaseI=kVA×10001.732×EI = \dfrac{kVA \times 1000}{1.732 \times E}

Example: a 75 kVA, three-phase transformer with a 208 V secondary.

IS=75,0001.732×208=75,000360.3=208.2 AI_S = \frac{75{,}000}{1.732 \times 208} = \frac{75{,}000}{360.3} = \mathbf{208.2\ \text{A}}

And its 480 V primary:

IP=75,0001.732×480=75,000831.4=90.2 AI_P = \frac{75{,}000}{1.732 \times 480} = \frac{75{,}000}{831.4} = \mathbf{90.2\ \text{A}}

These two numbers feed directly into the Article 450 overcurrent protection rules covered in Chapter 8.

Transformer Losses

  • Core (iron) loss — hysteresis and eddy currents in the steel. Essentially constant whenever the transformer is energized, regardless of load.
  • Copper loss — I2RI^2R in the windings. Varies with the square of the load current.

Because core loss is constant, a lightly loaded transformer is an inefficient transformer, and an energized but unloaded transformer still consumes power.


Quick Reference

RelationshipFormula
Power factorPF=P/SPF = P / S
True power from VAP=S×PFP = S \times PF
Horsepower to watts1 hp=746 W1\ \text{hp} = 746\ \text{W}
EfficiencyPout/Pin×100P_{out} / P_{in} \times 100
Transformer ratioEP/ES=NP/NS=IS/IPE_P/E_S = N_P/N_S = I_S/I_P
3-phase FLA from kVAI=(kVA×1000)/(1.732×E)I = (kVA \times 1000) / (1.732 \times E)
Test Your Knowledge

A single-phase 240-volt motor draws 25 amperes at a power factor of 0.80. What is the true power in watts?

A

6,000 watts

B

4,800 watts

C

7,500 watts

D

3,840 watts

Test Your Knowledge

A single-phase transformer has 1,200 turns on the primary and 200 turns on the secondary. With 480 volts applied to the primary and a 30-ampere secondary load, what are the secondary voltage and the primary current?

A

2,880 volts and 180 amperes

B

480 volts and 30 amperes

C

80 volts and 5 amperes

D

80 volts and 180 amperes

Test Your Knowledge

What is the full-load secondary current of a 45 kVA three-phase transformer with a 208-volt secondary?

A

124.9 amperes

B

216.3 amperes

C

187.5 amperes

D

54.1 amperes

Test Your Knowledge

Which statement correctly describes transformer losses?

A

Core loss varies with the square of the load current while copper loss is constant

B

Both core loss and copper loss are constant regardless of loading

C

Core loss is essentially constant whenever the transformer is energized, while copper loss varies with the square of the load current

D

Neither loss occurs when the secondary is unloaded

Sections you finish are checked off in the contents.