11.2 Alternating Current, Single-Phase & Three-Phase Systems

Key Takeaways

  • Alternating current in North America reverses at 60 hertz, and the RMS value used in every code calculation is 0.707 times the peak value while the peak is 1.414 times the RMS value.
  • In a three-phase wye system the line voltage equals 1.732 times the phase voltage while line current equals phase current, which is why a 120-volt phase produces a 208-volt line voltage.
  • In a three-phase delta system the line voltage equals the phase voltage while line current equals 1.732 times the phase current.
  • Single-phase apparent power is VA = E x I, and three-phase apparent power is VA = 1.732 x E-line x I-line, so amperage from a three-phase VA total is I = VA / (1.732 x E).
  • On a 120/240-volt three-phase four-wire delta system the high leg measures approximately 208 volts to the grounded conductor and must be identified in orange or by tagging, and NEC 408.3(F) fixes its position as phase B in the panelboard.
Last updated: August 2026

11.2 Alternating Current, Single-Phase & Three-Phase Systems

Exam Focus: Frequency and RMS values, wye versus delta relationships, the 1.732 factor, converting between VA and amperes on single- and three-phase systems, and high-leg delta identification.

Every commercial load calculation on this examination ends with a division by either 240 (single-phase) or by 1.732 × line voltage (three-phase). Getting the system type right is worth more points than any single table lookup.


Alternating Current Basics

  • Frequency: North American power alternates at 60 hertz — 60 complete cycles per second, so the current reverses direction 120 times per second.
  • Period: one cycle takes 1/60 second ≈ 16.67 milliseconds.
  • RMS (effective) value: the DC-equivalent heating value. Every voltage and current in the NEC is an RMS value unless stated otherwise.

ERMS=0.707×EPEAKEPEAK=1.414×ERMSE_{RMS} = 0.707 \times E_{PEAK} \qquad E_{PEAK} = 1.414 \times E_{RMS}

A "120-volt" circuit has a peak of about 170 volts, and a "277-volt" circuit peaks near 392 volts. That matters for insulation ratings and for understanding why a 600-volt-rated conductor is used on a 480-volt system.


Single-Phase Systems

SystemDescriptionCommon Use
120 V, 2-wireOne ungrounded conductor and a grounded conductorLighting and receptacle branch circuits
120/240 V, 3-wireTwo ungrounded conductors 180° apart plus a grounded center tapStandard dwelling service

On a 120/240 V system, the two ungrounded conductors are 180 degrees out of phase, which is why the voltage between them is the arithmetic sum, 240 V, and why the neutral of a properly connected multiwire branch circuit carries the difference of the two line currents.

Single-phase: VA=E×II=VAE\text{Single-phase: } VA = E \times I \qquad I = \frac{VA}{E}


Three-Phase Systems and the 1.732 Factor

Three-phase power uses three ungrounded conductors whose voltages are 120 electrical degrees apart. The constant that connects line values to phase values is $\sqrt{3} = 1.732$.

+-------------------------------------------------------------------------+
|                  WYE vs. DELTA — MEMORIZE THIS BOX                      |
|                                                                         |
|   WYE (Y)                              DELTA                            |
|   ------------------------------       ------------------------------   |
|   E_line = 1.732 x E_phase             E_line = E_phase                 |
|   I_line = I_phase                     I_line = 1.732 x I_phase         |
|                                                                         |
|   Has a neutral point; supplies        No neutral unless one corner     |
|   line-to-neutral loads.               or midpoint is grounded.         |
|                                                                         |
|   208Y/120 V, 480Y/277 V               240 V, 480 V, 240/120 high leg   |
+-------------------------------------------------------------------------+

Why 208 Volts?

On a 208Y/120 V system each phase-to-neutral voltage is 120 V. The line-to-line voltage is:

Eline=1.732×120=207.8208 VE_{line} = 1.732 \times 120 = 207.8 \approx 208\ \text{V}

Likewise $1.732 \times 277 = 479.8 \approx 480\ \text{V}$.

[!CAUTION] The two-phases-of-a-wye trap. Two ungrounded conductors of a 208Y/120 V system are 120 degrees apart, not 180. A 240 V single-phase appliance will not work correctly on 208 V, and a resistance heater on 208 V produces only about 75% of its 240 V output, because power varies with the square of voltage: $(208/240)^2 = 0.751$.

Three-Phase Power Formulas

VA=1.732×Eline×IlineIline=VA1.732×ElineVA = 1.732 \times E_{line} \times I_{line} \qquad I_{line} = \frac{VA}{1.732 \times E_{line}}

Worked Example

A 208Y/120 V three-phase feeder carries a calculated load of 45,000 VA.

I=45,0001.732×208=45,000360.3=124.9 AI = \frac{45{,}000}{1.732 \times 208} = \frac{45{,}000}{360.3} = 124.9\ \text{A}

The same 45,000 VA on a 480Y/277 V system draws only:

I=45,0001.732×480=45,000831.4=54.1 AI = \frac{45{,}000}{1.732 \times 480} = \frac{45{,}000}{831.4} = 54.1\ \text{A}

That is the engineering reason commercial buildings distribute at 480 V and transform down: at 2.3 times the voltage, the conductor carries 2.3 times less current.


The High-Leg Delta (120/240 V, 3-Phase, 4-Wire)

A four-wire delta system grounds the midpoint of one transformer winding so that two of the three phases give 120 V to ground for lighting, while all three give 240 V line-to-line for motors.

The third phase — the high leg, also called the wild leg or stinger — measures:

Ehigh leg=1.732×120=208 V to the grounded conductorE_{high\ leg} = 1.732 \times 120 = 208\ \text{V to the grounded conductor}

RuleRequirement
IdentificationThe conductor with the higher voltage to ground must be durably and permanently marked by an outer finish that is orange in color, or by other effective means (tagging) at every point where a connection is made if the grounded conductor is also present
Panelboard position (408.3(F))Where a panelboard is supplied from a 4-wire delta system, the high leg is phase B — the busbar or terminal having the higher voltage to ground is arranged as the B phase

[!IMPORTANT] Never land a 120-volt load on the high leg. A 120 V circuit connected between the high leg and the neutral sees 208 V and will destroy the load. Recognizing the 208 V reading on a 240 V delta system is a classic troubleshooting item.


Quick Reference

NeedSingle-PhaseThree-Phase
Amperes from VA$I = VA / E$$I = VA / (1.732 \times E)$
VA from amperes$VA = E \times I$$VA = 1.732 \times E \times I$
Common line voltages120, 208, 240, 277, 480208, 240, 480
Test Your Knowledge

A three-phase, 208Y/120-volt feeder supplies a calculated load of 36,000 volt-amperes. What is the line current?

A
B
C
D
Test Your Knowledge

In a three-phase wye-connected system, what is the relationship between line voltage and phase voltage?

A
B
C
D
Test Your Knowledge

On a 120/240-volt three-phase four-wire delta system, what voltage will a meter read from the high leg to the grounded conductor, and where must that conductor be arranged in a panelboard?

A
B
C
D
Test Your Knowledge

A resistance heater rated 4,800 watts at 240 volts is connected to a 208-volt supply instead. Approximately what output will it produce?

A
B
C
D