11.2 Alternating Current, Single-Phase & Three-Phase Systems
Key Takeaways
- Alternating current in North America reverses at 60 hertz, and the RMS value used in every code calculation is 0.707 times the peak value while the peak is 1.414 times the RMS value.
- In a three-phase wye system the line voltage equals 1.732 times the phase voltage while line current equals phase current, which is why a 120-volt phase produces a 208-volt line voltage.
- In a three-phase delta system the line voltage equals the phase voltage while line current equals 1.732 times the phase current.
- Single-phase apparent power is VA = E x I, and three-phase apparent power is VA = 1.732 x E-line x I-line, so amperage from a three-phase VA total is I = VA / (1.732 x E).
- On a 120/240-volt three-phase four-wire delta system the high leg measures approximately 208 volts to the grounded conductor and must be identified in orange or by tagging, and NEC 408.3(F) fixes its position as phase B in the panelboard.
11.2 Alternating Current, Single-Phase & Three-Phase Systems
Exam Focus: Frequency and RMS values, wye versus delta relationships, the 1.732 factor, converting between VA and amperes on single- and three-phase systems, and high-leg delta identification.
Every commercial load calculation on this examination ends with a division by either 240 (single-phase) or by 1.732 × line voltage (three-phase). Getting the system type right is worth more points than any single table lookup.
Alternating Current Basics
- Frequency: North American power alternates at 60 hertz — 60 complete cycles per second, so the current reverses direction 120 times per second.
- Period: one cycle takes 1/60 second ≈ 16.67 milliseconds.
- RMS (effective) value: the DC-equivalent heating value. Every voltage and current in the NEC is an RMS value unless stated otherwise.
A "120-volt" circuit has a peak of about 170 volts, and a "277-volt" circuit peaks near 392 volts. That matters for insulation ratings and for understanding why a 600-volt-rated conductor is used on a 480-volt system.
Single-Phase Systems
| System | Description | Common Use |
|---|---|---|
| 120 V, 2-wire | One ungrounded conductor and a grounded conductor | Lighting and receptacle branch circuits |
| 120/240 V, 3-wire | Two ungrounded conductors 180° apart plus a grounded center tap | Standard dwelling service |
On a 120/240 V system, the two ungrounded conductors are 180 degrees out of phase, which is why the voltage between them is the arithmetic sum, 240 V, and why the neutral of a properly connected multiwire branch circuit carries the difference of the two line currents.
Three-Phase Systems and the 1.732 Factor
Three-phase power uses three ungrounded conductors whose voltages are 120 electrical degrees apart. The constant that connects line values to phase values is $\sqrt{3} = 1.732$.
+-------------------------------------------------------------------------+
| WYE vs. DELTA — MEMORIZE THIS BOX |
| |
| WYE (Y) DELTA |
| ------------------------------ ------------------------------ |
| E_line = 1.732 x E_phase E_line = E_phase |
| I_line = I_phase I_line = 1.732 x I_phase |
| |
| Has a neutral point; supplies No neutral unless one corner |
| line-to-neutral loads. or midpoint is grounded. |
| |
| 208Y/120 V, 480Y/277 V 240 V, 480 V, 240/120 high leg |
+-------------------------------------------------------------------------+
Why 208 Volts?
On a 208Y/120 V system each phase-to-neutral voltage is 120 V. The line-to-line voltage is:
Likewise $1.732 \times 277 = 479.8 \approx 480\ \text{V}$.
[!CAUTION] The two-phases-of-a-wye trap. Two ungrounded conductors of a 208Y/120 V system are 120 degrees apart, not 180. A 240 V single-phase appliance will not work correctly on 208 V, and a resistance heater on 208 V produces only about 75% of its 240 V output, because power varies with the square of voltage: $(208/240)^2 = 0.751$.
Three-Phase Power Formulas
Worked Example
A 208Y/120 V three-phase feeder carries a calculated load of 45,000 VA.
The same 45,000 VA on a 480Y/277 V system draws only:
That is the engineering reason commercial buildings distribute at 480 V and transform down: at 2.3 times the voltage, the conductor carries 2.3 times less current.
The High-Leg Delta (120/240 V, 3-Phase, 4-Wire)
A four-wire delta system grounds the midpoint of one transformer winding so that two of the three phases give 120 V to ground for lighting, while all three give 240 V line-to-line for motors.
The third phase — the high leg, also called the wild leg or stinger — measures:
| Rule | Requirement |
|---|---|
| Identification | The conductor with the higher voltage to ground must be durably and permanently marked by an outer finish that is orange in color, or by other effective means (tagging) at every point where a connection is made if the grounded conductor is also present |
| Panelboard position (408.3(F)) | Where a panelboard is supplied from a 4-wire delta system, the high leg is phase B — the busbar or terminal having the higher voltage to ground is arranged as the B phase |
[!IMPORTANT] Never land a 120-volt load on the high leg. A 120 V circuit connected between the high leg and the neutral sees 208 V and will destroy the load. Recognizing the 208 V reading on a 240 V delta system is a classic troubleshooting item.
Quick Reference
| Need | Single-Phase | Three-Phase |
|---|---|---|
| Amperes from VA | $I = VA / E$ | $I = VA / (1.732 \times E)$ |
| VA from amperes | $VA = E \times I$ | $VA = 1.732 \times E \times I$ |
| Common line voltages | 120, 208, 240, 277, 480 | 208, 240, 480 |
A three-phase, 208Y/120-volt feeder supplies a calculated load of 36,000 volt-amperes. What is the line current?
In a three-phase wye-connected system, what is the relationship between line voltage and phase voltage?
On a 120/240-volt three-phase four-wire delta system, what voltage will a meter read from the high leg to the grounded conductor, and where must that conductor be arranged in a panelboard?
A resistance heater rated 4,800 watts at 240 volts is connected to a 208-volt supply instead. Approximately what output will it produce?