2.3 Conductors (0103)

Key Takeaways

  • Conductor ampacity is read from Table 310.16, but the ampacity usable at a termination is limited by 110.14(C) to the 60°C or 75°C column based on the equipment rating and marking — a 90°C THHN conductor is still sized on the 75°C column at most equipment rated over 100 A.
  • When more than three current-carrying conductors share a raceway, apply the adjustment factors of 310.15(C)(1); when the ambient is not 30°C, apply the correction factors of 310.15(B)(1). Both are applied to the ampacity column matching the conductor insulation, then compared to the 110.14(C) termination limit.
  • Paralleling is permitted for conductors 1/0 AWG and larger under 310.10(G); every conductor of a parallel set must be the same length, material, size, and insulation type, and be terminated in the same manner.
  • Conductor splices and terminations must be made in a box or conduit body (300.15), connections must comply with 110.14(B), and marked torque values must be applied with a calibrated torque tool (110.14(D)).
  • The small-conductor rule in 240.4(D) caps overcurrent protection at 15 A for 14 AWG Cu, 20 A for 12 AWG Cu, and 30 A for 10 AWG Cu, regardless of the higher figures in the 75°C and 90°C columns.
Last updated: August 2026

Conductor Types and Insulation Letter Designations

Conductors are identified by a letter designation that encodes insulation material, temperature rating, and location suitability. Table 310.4(A) is the master list of conductor insulations rated 600 volts, giving each type's trade name, maximum operating temperature, and permitted application. Common types:

LetterTrade NameMax TempTypical Application
THHNHigh heat-resistant thermoplastic nylon90°C dry/dampBranch circuits, general wiring
THWNHeat- and moisture-resistant thermoplastic nylon75°C wet / 90°C dryWet locations, conduit
THWN-2Same as THWN, 90°C wet and dry90°C all locationsGeneral purpose, wet/damp
XHHWCross-linked synthetic polymer (XLPE)75°C wet / 90°C dryDry/wet, industrial
XHHW-2XLPE, 90°C all90°C all locationsGeneral, wet/damp, direct burial
THW / THW-2Thermoplastic, moisture- and heat-resistant75°C / 90°CDry and wet
TWMoisture-resistant thermoplastic60°CDry and wet, general
USE-2Underground service entrance (XLPE)90°CDirect burial, no indoor use

The suffix "-2" means the conductor is rated 90°C in wet locations (not just dry). When the inspector sees THWN-2 or XHHW-2, the 90°C column may be used for derating calculations.

Copper vs. Aluminum

  • Copper (Cu) — lower resistance; smaller size for a given ampacity. Read the copper columns of Table 310.16.
  • Aluminum (Al) and copper-clad aluminum (CCA) — lighter and cheaper for large feeders; read the aluminum/copper-clad aluminum columns of Table 310.16, which run roughly two AWG sizes larger than copper for the same ampacity. Aluminum and copper-clad aluminum 1/0 AWG and larger may be paralleled under 310.10(G), the same threshold as copper.

Ampacity — Table 310.16

Table 310.16 gives allowable ampacities for insulated conductors rated 0–2000 V, not more than 3 current-carrying conductors in a raceway/cable/earth, and an ambient temperature of 30°C. Excerpt (copper):

Size (Cu)60°C75°C90°C
14 AWG15 A20 A25 A
12 AWG20 A25 A30 A
10 AWG30 A35 A40 A
8 AWG40 A50 A55 A
6 AWG55 A65 A75 A
4 AWG70 A85 A95 A
3 AWG85 A100 A115 A
2 AWG95 A115 A130 A
1 AWG110 A130 A150 A
1/0 AWG125 A150 A170 A
2/0 AWG145 A175 A195 A
3/0 AWG165 A200 A225 A
4/0 AWG195 A230 A260 A

The 240.4(D) small-conductor rule caps the overcurrent protection for 14 AWG Cu at 15 A, 12 AWG Cu at 20 A, and 10 AWG Cu at 30 A, regardless of the higher numbers in the 75°C/90°C columns (with exceptions listed in 240.4(G)).

Termination Temperature Limits — 110.14(C)

The conductor's insulation may be rated 90°C, but terminations are limited by 110.14(C):

  • Equipment rated 100 A or less, or marked for conductors 14 AWG through 1 AWG: use the 60°C column unless the equipment is marked 60/75°C, in which case the 75°C column is permitted.
  • Equipment rated over 100 A, or marked for conductors larger than 1 AWG: use the 75°C column unless marked for 90°C.
  • A conductor with higher-rated insulation (e.g., 90°C THHN) may be used, but the ampacity at the termination is taken from the termination-rated column. The 90°C column is the starting point only for derating (correction/adjustment).

The Practical Rule

  • Size the conductor at the termination using 110.14(C) (usually the 75°C column).
  • Size the conductor in the raceway for derating using the 90°C column (if the insulation is 90°C).
  • The smaller of the two is the final ampacity.

Derating (Correction and Adjustment Factors) — 310.15

Table 310.16 is built on two stated conditions: an ambient of 30°C (86°F) and not more than three current-carrying conductors in the raceway, cable, or earth. When the installation departs from either condition, apply the factors printed with Article 310:

  • Ambient temperature correction — Table 310.15(B)(1): multiply the ampacity from the column matching the conductor insulation by the correction factor for the actual ambient. Representative factors (90°C column):
    • 31–35°C: 0.96
    • 36–40°C: 0.91
    • 41–45°C: 0.87
    • 46–50°C: 0.82
  • Adjustment for more than three current-carrying conductors — 310.15(C)(1):
    • 4–6 CCC: 80%
    • 7–9 CCC: 70%
    • 10–20 CCC: 50%
    • 21–30 CCC: 45%

Worked Example

A feeder is run with 6 current-carrying conductors of #2 AWG THHN copper in a single conduit, in a mechanical room where the ambient is 40°C.

  1. Base ampacity from Table 310.16, 90°C column (THHN is 90°C): 130 A.
  2. Ambient correction at 40°C, 90°C column (Table 310.15(B)(1)): 0.91. 130 × 0.91 = 118.3 A.
  3. Adjustment for 6 CCC (310.15(C)(1)): 0.80. 118.3 × 0.80 = 94.6 A.
  4. Termination limit — #2 AWG Cu at 75°C (equipment >100 A, 110.14(C)) = 115 A.
  5. The derated value (94.6 A) is less than the termination limit (115 A), so the derated ampacity governs: ~94 A.

If this conductor served a continuous load, the OCPD would be sized at 125% of the continuous load per 215.3 and must not exceed 94 A.

Conductor Connections, Splices, and Terminal Identification

  • 110.14(B) — Splices: conductor splices and joints must be made with listed splicing devices or by brazing, welding, or soldering with a fusible metal or alloy — and a soldered splice must first be mechanically and electrically secure without the solder, then soldered. Splices must be made in a box or conduit body.
  • 300.15 — Boxes and conduit bodies required: A box or conduit body must be installed at each conductor splice, tap, termination, or junction point, and must remain accessible (314.29).
  • 110.14(D) — Terminal connection torque: where a tightening torque is indicated as a numeric value on equipment or in the installation instructions, it must be applied with a calibrated torque tool (torque wrench, screwdriver, or driver).
  • Terminal identification: Terminals must be marked to indicate the conductor material (Cu/Al/Cu-Al) they are listed for. Aluminum-rated terminals used with aluminum conductors must be listed and installed with antioxidant compound if required.

Paralleling — 310.10(G)

Paralleling means using two or more conductors per phase instead of one large conductor. Under 310.10(G):

  • Allowed for 1/0 AWG and larger copper, aluminum, and copper-clad aluminum.
  • Every conductor of a given parallel set (all the phase A conductors, all the phase B conductors, and so on) must be the same length, same conductor material, same circular-mil area, and same insulation type, and must be terminated in the same manner.
  • Where the parallel sets are run in separate raceways or cables, each raceway or cable must have the same number of conductors and the same electrical characteristics, so that current divides evenly. All conductors of the same circuit — every phase, the neutral, and the equipment grounding conductor — must be in each raceway (300.3(B)); putting all the phase A conductors in one steel conduit is an inductive-heating violation, and it is a classic exam trap.
  • The equipment grounding conductor in each parallel raceway is full-size per Table 250.122 for the circuit overcurrent device, not divided among the raceways.

Paralleling is common on large commercial feeders and services; the inspector verifies that each conductor in a set is identical and that sets are distributed across phases to avoid inductive heating.

Test Your Knowledge

A feeder uses #2 AWG THHN copper conductors (90°C insulation) with 6 current-carrying conductors in one raceway and an ambient temperature of 40°C. Using the 90°C column of Table 310.16, the ampacity is 130 A; the 40°C correction factor is 0.91 and the 4–6 CCC adjustment factor is 0.80. The equipment is rated over 100 A (75°C terminations). What is the final allowable ampacity?

A
B
C
D
Test Your Knowledge

Which of the following is a requirement for paralleling conductors under 310.10(G)?

A
B
C
D
Test Your Knowledge

A #12 AWG THWN-2 copper conductor is protected by a 20 A circuit breaker. Which statement is correct under 240.4(D) and 110.14(C)?

A
B
C
D