12.3 Distribution Storage: Types, Sizing & Turnover
Key Takeaways
- Storage Facilities is a named sub-topic in the Distribution System Design and Hydraulics category of the SWRCB distribution exam.
- Total storage is the sum of operating or equalization storage, fire storage, and emergency storage.
- An elevated tank or a ground tank at elevation floats on the system and sets the hydraulic grade line; a ground-level tank at grade requires a booster pump station to serve the system.
- Water level in feet converts to pressure by multiplying by 0.433, so a tank with 60 feet of water depth develops about 26 psi at its base.
- Long detention time in storage causes loss of disinfectant residual, disinfection byproduct formation, nitrification in chloraminated systems, and temperature stratification.
What Storage Buys
| Component | Purpose | Typical sizing basis |
|---|---|---|
| Operating (equalization) storage | Absorbs the difference between a steady source or plant output and a fluctuating demand | Often 15 to 25 percent of maximum day demand |
| Fire storage | Supplies fire flow at the required rate and duration | Required fire flow x duration, per the fire authority |
| Emergency storage | Covers source outage, power failure, main break, earthquake | Often 1 day of average demand or a policy-set duration |
Worked example. MDD is 3.0 MGD; fire flow is 3,000 gpm for 3 hours; emergency policy is one average day at 1.6 MGD. Operating at 20 percent of MDD = 0.20 x 3,000,000 = 600,000 gal Fire = 3,000 x 180 = 540,000 gal Emergency = 1,600,000 gal Total = 2,740,000 gallons
Storage Types and Hydraulic Position
| Type | Position | How it serves the system |
|---|---|---|
| Elevated tank (legged or composite) | Bowl above the service area | Floats on the system - sets the hydraulic grade line directly; supplies flow by gravity during outages |
| Standpipe | Tall ground-supported cylinder | Only the volume above the service area elevation is useful storage; the rest is supporting volume |
| Ground-level reservoir at elevation (hilltop tank) | On high ground | Floats on the system; the California norm where terrain allows |
| Ground-level reservoir at grade / clearwell | At plant grade | Does not float; requires a booster pump station to deliver to the system |
| Buried or partially buried reservoir | Below grade | Requires pumping; subject to the 22 CCR 64585 subsurface requirements including 50-foot separation from sanitary sewers and groundwater monitoring |
| Hydropneumatic (pressure) tank | At grade | Small systems; air cushion maintains pressure between pump cycles; very little usable storage |
Level and Pressure
Example: a hilltop tank with an overflow elevation of 640 ft, currently 8 ft below overflow, serving a home at elevation 465 ft. Water surface = 640 - 8 = 632 ft. Difference = 632 - 465 = 167 ft. Static pressure = 167 x 0.433 = 72.3 psi
A tank that floats on the system is a pressure-setting device. Every foot the level drops removes 0.433 psi from every customer in the zone. That is why level, not volume, is the operational control variable.
Control Valves
- Altitude valve - closes to prevent overflow when the tank reaches a set level; a two-way altitude valve also allows the tank to feed back into the system on demand.
- Level transmitters - pressure transducer, ultrasonic, radar, or float; feed SCADA and the pump control logic.
- Overflow - must terminate with a screened, downturned outlet and a proper air gap, and may never be directly connected to a sewer or storm drain.
- Drain and washout - sized to empty the tank for inspection, also air-gapped.
Turnover: The Water Quality Problem
Storage is the place in a distribution system with the longest detention time, and long detention causes four predictable problems:
- Loss of disinfectant residual - decay is continuous and accelerates with temperature
- Disinfection byproduct formation - free chlorine plus organic precursors plus time equals TTHM and HAA5, and Stage 2 evaluates each monitoring site on its own LRAA
- Nitrification in chloraminated systems - the warm, low-residual, low-velocity interior of a tank is the ideal nitrifier habitat
- Thermal stratification - a tall tank in summer develops a warm surface layer that never mixes with the cold bottom, so a nominally "turned over" tank may be exchanging only the top few feet
Managing Turnover
- Cycle through a wider level band. A tank operated between 90 and 95 percent full exchanges 5 percent of its volume per cycle. Widening the band to 70-95 percent exchanges five times as much.
- Separate inlet and outlet, arranged to minimize short-circuiting - a design requirement for new reservoirs under 22 CCR 64585. Where a common inlet/outlet pipe exists, the incoming water tends to leave immediately and a large volume never exchanges.
- Active mixing systems - submersible mixers or nozzle systems that break stratification.
- Seasonal deep cycling - deliberately drawing a problem tank far down during low-demand periods, with residual and turbidity monitoring during recovery.
- Booster disinfection at the tank outlet where residual cannot be maintained by turnover alone.
- Right-size the storage. Storage sized for a growth projection that never happened is a permanent water quality liability.
[!TIP] Water age is not the same as detention time. A tank with a 3-day theoretical detention time and a common inlet/outlet may have a well-mixed 20 percent and an 80 percent that is weeks old. Tracer studies, temperature profiling at multiple depths, and residual profiles at multiple depths are how operators find out which one they have.
Inspection and Maintenance
| Item | Frequency | What to look for |
|---|---|---|
| Vents and screens | Routine (monthly to quarterly) | Corrosion-resistant screen intact, typically 24-mesh; no gaps, no bird or insect entry |
| Hatches | Routine | Gasketed, overlapping, locked, raised curb with a downturned lip |
| Overflow | Routine | Screened, downturned, flap or duckbill intact, air gap present, no sewer connection |
| Exterior coating and cathodic protection | Annual | Rust, blistering, anode condition |
| Interior inspection | Every 3-5 years typically | Coating failure, sediment depth, corrosion, structural condition - by diver or ROV, or after draining |
| Level instrumentation | Routine | Verify against a physical measurement; a failed level transmitter can overflow a tank or run a zone dry |
| Security | Routine | Fencing, locks, intrusion alarms, ladder guards |
Any reservoir taken out of service for repair or inspection must be disinfected and sampled under AWWA C652-02 before return to service, and if coliform is detected the reservoir must be resampled with results submitted to the State Board for review and approval.
A hilltop reservoir has an overflow elevation of 720 feet and is currently 12 feet below overflow. What is the static pressure at a service connection at elevation 540 feet?
A chloraminated system is losing residual and detecting nitrite in one storage tank that is operated between 88 and 94 percent full. What is the most direct corrective action?
Which storage configuration does NOT float on the distribution system and therefore requires a booster pump station to serve customers?