Administration and General Regulations
46%of exam
Plumbing Fixtures
14%of exam
Water Supply and Distribution
11%of exam
Sanitary Drainage
11%of exam
Plumbing Vent Requirements
8%of exam
Traps, Interceptors, and Separators
8%of exam
Storm Drainage
2%of exam
Quick Facts
- Exam owner
- International Code Council
- Program
- National Contractor/Trades
- G24-N
- 2018 IPC, 70% passing score
- F24-N
- 2015 IPC, 70% passing score
- T24-N reference
- 2021 International Plumbing Code
- T24-N passing score
- 70% or 75%, by ID
- F24-N Pearson registration ends
- December 1, 2026
- T24-N Pearson registration opens
- December 1, 2026
- Questions
- 100 multiple-choice
- Time
- 4 hours
- Format
- Open-book Pearson VUE CBT
- ICC exam fee
- $120 per exam
- Licensing
- Confirm exam acceptance with jurisdiction
Code Lookup Order
Edition → topic → section → table → footnotes
Installation Lookup
- Code term changes the answer→Chapter 2 definitions(Check exact term first)
- Selecting pipe support spacing→Table 308.5(Material and orientation)
- Selecting underground drainage pipe→Table 702.2(Building drainage and vent)
- Testing plastic DWV→Water test §312.2(Air testing prohibited)
- Hydrotesting potable supply piping→Section 312.5(At least working pressure)
- Calculating required fixture counts→Table 403.1(Start with occupancy classification)
Exam Codes and Editions
- G24-N
- 2018 IPC, 70% passing score
- F24-N
- 2015 IPC, 70% passing scoreRegistration ends December 1, 2026
- T24-N-70%
- 2021 IPC, 70% passing scoreOpens December 1, 2026
- T24-N-75%
- 2021 IPC, 75% passing scoreOpens December 1, 2026
- Exam pacing
- Average 2.4 minutes per question
Plans and Measurements
- Plan view
- Horizontal routing from above
- Riser diagram
- Vertical routing and branch connections
- Drawing legend
- Decode line types and symbols
- Pipe invert
- Inside bottom of pipe
- Developed length
- Along pipe and fitting centerlinesCh. 2
- Slope
- Vertical fall ÷ horizontal run
- 40 ft at ¼ in/ft
- 10 in of fall
- Flood level rim
- Fixture edge where water overflowsCh. 2
Installation and Materials
- Pipe and fitting sizes
- Nominal unless specified§301.5
- Material identification
- Manufacturer marking and required standards§303
- Foundation wall penetration
- Relieving arch or oversized sleeve§305.3
- Buried pipe
- Continuous load-bearing bedding§306
- Cutting and notching
- Check structural safety provisions§307
- Hanger spacing
- Match material and orientationTable 308.5
- Potable pipe materials
- Separate service and distribution tablesTables 605.3–605.4
- Drain and vent materials
- Separate aboveground and underground tablesTables 702.1–702.2
Tests and Inspections
- DWV
- Drain, waste, and vent
- DWV water test head
- 10 ft water head minimum§312.2
- DWV head exception
- Uppermost 10 ft of system§312.2
- Successive DWV water tests
- Overlap preceding section's upper 10 ft
- DWV water test hold
- At least 15 minutes
- DWV air test
- Nonplastic only, 5 psi, ≥15 min§312.3
- Water supply hydrostatic test
- At least working pressure≥15 min, §312.5
- Water supply air test
- Nonplastic only, ≥50 psi, ≥15 min§312.5
- Supply test water
- Use potable source§312.5
- Test pressure ≤10 psi
- Gauge increments ≤0.10 psi§312.1.1
Typical Toilet Clearances
15 side • 21 front • 30 center spacing
Fixture Layout
- Minimum fixture counts
- Occupancy and occupant loadTable 403.1
- Toilet centerline to obstruction
- 15 in typical minimum§405.3.1
- Unpartitioned adjacent toilet centers
- 30 in minimum spacing§405.3.1
- Toilet front clearance
- 21 in typical minimum§405.3.1
- Accessible fixtures
- Check separate accessibility provisions§404
- Accessible children's toilet exception
- 12 in minimum on one side2018/2021 §405.3.1
- Flushed fixtures
- Check tank or flushometer requirements2015 §425, 2018/2021 §415
Water Heater Safety
- T&P relief valve
- Temperature and pressure protection§504.4
- Relief discharge path
- Gravity flow with observable termination§504.6
- Relief discharge outlet
- Full-size, same-room air gap§504.6
- Relief discharge piping
- Dedicated, valve-free, trap-free line§504.6
- Storage tank leakage hazard
- Provide approved pan§504.7
- Bottom-fed heater
- Vacuum relief valve§504.2
- Closed supply to storage heater
- Cold-side expansion control downstream§607.3
Static and Residual Pressure
Static pressure
- Measured with flow stopped
- Building maximum §604.8
Residual pressure
- Available while water flows
- Fixture minimum Table 604.3
Identify the measurement condition
Water Supply Lookup
- Fixture needs minimum flow pressure→Table 604.3(Use pressure under flow)
- Source pressure cannot meet demand→Booster system §604.7(Check §606.5)
- Building static exceeds 80 psi→Regulator with strainer §604.8(Check service-line and riser exception)
- Selecting potable backflow protection→Table 608.1(Match hazard and pressure conditions)
- Check valve feeds storage heater→Expansion control §607.3(2015 specifies expansion tank)
Supply and Pressure
- Fixture supply performance
- Required flow and residual pressureTable 604.3
- Variable street pressure
- Design for minimum available pressure§604.6
- Inadequate fixture flow pressure
- Check booster system requirements§604.7
- Building static pressure above 80 psi
- Approved regulator with strainer§604.8
- Regulated building pressure
- 80 psi static or lowerCheck §604.8 exception
- Quick-closing valve
- Water hammer arrestor§604.9
- Water supply fixture units
- Estimate probable supply demandAppendix E method
- Elevated outlet
- Deduct pressure for elevation rise≈0.433 psi/ft
Backpressure and Backsiphonage
Backpressure
- Downstream pressure overcomes supply
- Check protection for reversed pressure
Backsiphonage
- Supply pressure falls below atmospheric
- Check protection for suction
Match assembly to reversal modes
Backflow Protection
- Cross-connection
- Potential path for potable contamination
- Backsiphonage
- Reversal from supply-side negative pressure
- Backpressure
- Downstream pressure exceeds supply pressure
- Potable outlet air gap
- Clear space above flood rim
- Pressure vacuum breaker
- High/low hazard, backsiphonage onlyTable 608.1
- Double-check assembly
- Low hazard, both reversal modesTable 608.1
- Reduced pressure principle assembly
- High/low hazard, both reversal modesTable 608.1
- Assembly selection
- Check hazard and reversal modeTable 608.1
Fixture Unit Mapping
Supply units feed • Drainage units drain
Building Drain and Building Sewer
Building drain
- Lowest piping collecting interior drainage
- Extends 30 in beyond walls
Building sewer
- Begins where building drain ends
- Conveys discharge to disposal
Locate the junction cleanout
Drainage Lookup
- Sizing sanitary building sewer→Table 710.1(1)(DFUs and pipe slope)
- Sizing fixture branch or stack→Table 710.1(2)(Read applicable load column)
- Sanitary discharge cannot drain by gravity→Check sump and pump §712(Verify gravity route and exceptions)
- Fixture floor below upstream cover→Check backwater valve rule(Next upstream public sewer manhole)
- Draining commercial food-preparation equipment→Indirect waste air gap(Start at §802.1.1)
- Sizing a horizontal storm drain→Table 1106.2(Use flow and slope)
Gravity Drainage
- Drainage fixture units (DFU)
- Relative sanitary discharge loadTable 709.1
- Building drain or sewer sizing
- Sum DFUs, select slope columnTable 710.1(1)
- Fixture branches and stacks
- Use branch or stack columnTable 710.1(2)
- Horizontal drain ≤2½ in
- ¼ in per ft minimumTable 704.1
- Horizontal drain 3–6 in
- ⅛ in per ft baselineTable 704.1
- Horizontal drain ≥8 in
- ¹⁄₁₆ in per ft baselineTable 704.1
- Upstream of grease interceptor
- ¼ in per ft minimum2018/2021 §704.1
- Drain-to-sewer junction cleanout
- At junction or ≤10 ft upstream§708.1.3
- Drainage fitting selection
- Match pattern to flow directionTable 706.3
Air Gap and Air Break
Indirect waste air gap
- Outlet clears receptor flood rim
- ≥2× effective waste opening
Indirect waste air break
- Outlet clears receptor trap seal
- Use where expressly permitted
Use the required receptor separation
Indirect Waste and Pumps
- Commercial food preparation fixtures
- Indirect waste through air gap§802.1.1
- Indirect discharge installation
- Check receptor, trap, and vent2015 §802.2, 2018/2021 §802.3
- Drainage air gap
- ≥2× effective opening above rim
- Drainage air break
- Outlet above receptor trap seal
- Below gravity sewer elevation
- Covered, vented sump with pump§712.1
- Sump pump discharge
- Check valve then accessible shutoff§712.2
- Backwater valve trigger
- Floor below next upstream manholePublic sewer cover elevation
- Backwater valve section
- 2015 §715.1, 2018/2021 §714.1
Horizontal Wet Vent Limits
Two bathroom groups, one floor
Dry Vent and Wet Vent
Dry vent
- Carries air
- Check §905 connections and grade
Wet vent
- Carries drainage and air
- Check §912 fixture groups
Trace drainage before choosing vent
Vent Lookup
- Finding trap-to-vent limit→Table 909.1(Trap size and slope)
- Dry vent joins horizontal drain→Section 905.3(Connect above drain centerline)
- Two bathroom groups share level→Check wet vent §912(Verify fixture and connection limits)
- Considering an air admittance valve→Section 918(Check access and outdoor vent)
- Locating roof vent termination→Section 903(Check jurisdiction-specified roof height)
Vent Layout and Sizing
- Drainage vent
- Admits or releases air
- Trap-to-vent distance
- Measure from weir along drainTable 909.1
- Trap arm at ¼ in/ft
- 1½ in: 6 ft maximumTable 909.1
- Self-siphoning fixtures
- Trap-to-vent developed-length exception§909.1
- Dry vent on horizontal drain
- Connect above drain centerline§905.3
- Dry vent before horizontal offset
- Rise ≥6 in above rimHighest trapped fixture served
- Horizontal wet vent
- Up to two same-floor bathroom groups§912.1
- Vent terminals
- Check openings, roof use, frost§903
- Air admittance valve (AAV)
- Admits air under negative pressure§918
- Systems using air admittance valves
- At least one outdoor stack ventOr outdoor vent stack §918.7
Trap and Grease Interceptor
Fixture trap
- Liquid seal blocks sewer gas
- Check seal depth and protection
Grease interceptor
- Captures grease-bearing waste constituents
- Allow access for service
Identify the function first
Trap and Interceptor Lookup
- Trap seal subject to evaporation→Seal protection §1002.4.1(Check permitted primer or barrier)
- Food-prep fixture drains grease→Grease interceptor or removal device(Check §1003.3.1)
- Repair garage drains oily waste→Oil separator §1003.4(Check covered discharge and exceptions)
- Food waste disposer joins interceptor→Check edition §1003.3.2(2018/2021 prohibit grease interceptor connection)
Trap Seals and Separation
- Fixture trap
- Liquid seal blocks sewer gas§1002
- Typical fixture trap seal
- 2–4 in liquid depth§1002.4
- Special accessible fixture designs
- Deeper trap seals permitted§1002.4
- Emergency floor drain seal
- Protect against seal loss§1002.4.1
- Potable-water trap primer
- Replenishes trap waterASSE 1018
- Barrier-type seal protection
- Limits floor drain seal evaporationASSE 1072
- Grease interceptor
- Retains fats, oils, and grease§1003.3
- Oil separator
- Separates oils from covered discharges§1003.4
- Interceptor service
- Provide access for maintenance§1003
Primary and Secondary Roof Drainage
Primary
- Carries design roof runoff
- Size by design flow
Secondary
- Handles blocked primary drainage
- Separate visible discharge endpoint
Size overflow independently
Roof and Storm Drainage
- Stormwater disposal
- Route to approved disposal§1101.2
- Design rainfall
- 100-year hourly or approved local rate§1106.1
- Vertical wall draining onto roof
- Add half the wall area§1106.4
- Roof drain design flow
- Published flow at ponding head§1105.2
- Horizontal storm pipe sizing
- Match design flow and slopeTable 1106.2
- Required roof drains, entrapment possible
- Provide overflow drain or scupper§1108.1
- Secondary system outlet
- Separate, visible above-grade discharge§1108.2
- Secondary system sizing
- Assume primary flow is zero§1108.3
Common Traps
Code editions
G24-N uses 2018 IPC ≠ F24-N uses 2015 IPC
Book policy
Approved IPC is exam reference ≠ Cheat sheet is pre-exam review
Plastic pipe testing
DWV water test covers plastic ≠ DWV air test excludes plastic
Nonplastic air test pressures
DWV air test 5 psi ≠ Water supply air test ≥50 psi
Reversal targets
Backflow protection safeguards potable supply ≠ Backwater valve stops sewer backup
Sizing inputs
Sanitary drainage uses DFUs ≠ Storm drainage uses runoff flow
Trap seal loss
Venting limits pressure disturbances ≠ Seal protection addresses evaporation
Disposer to grease interceptor
2015 allows connection after solids interception ≠ 2018/2021 prohibit this connection
Two drainage destinations
Stormwater needs approved disposal ≠ Sewage-only sewers exclude stormwater
Last Minute
- 1.Match registration to IPC edition
- 2.Confirm jurisdiction accepts exam ID
- 3.DWV water test hold ≥15 minutes
- 4.Toilet front clearance typically 21 in
- 5.Check regulator above 80 psi static
- 6.Size sanitary drains by fixture units
- 7.Trap-to-vent limits use Table 909.1
- 8.Typical trap seal depth 2–4 in
- 9.Apply table footnotes before choosing
- 10.Keep overflow discharge separate and visible