3.1 General Electrical Knowledge
Key Takeaways
Voltage is measured in volts (V or E), current in amperes (A or I), resistance in ohms (Ω or R), and power in watts (W or P); apparent power is in volt-amperes (VA) and equals watts only when power factor is 1.0.
Per NEC 110.5, conductors must be copper, aluminum, or copper-clad aluminum unless the Code provides otherwise; when a rule does not name the material, ampacity tables are based on copper.
Conductor sizes are expressed in American Wire Gauge (AWG) or circular mils per NEC 110.6; larger AWG numbers mean smaller conductors, and sizes above 4/0 AWG are given in kcmil.
A megohmmeter (megger) applies a high DC test voltage to measure insulation resistance in megohms, revealing degraded insulation that a normal ohmmeter cannot detect.
A clamp meter measures AC current by sensing the conductor's magnetic field; clamping around both current-carrying conductors cancels the reading because the opposing fields sum to zero.
Why This Matters on the Exam
The Virginia Journeyman exam blueprint assigns 3 questions to General Electrical Knowledge — small in raw count but foundational. Every branch-circuit calculation, conductor ampacity lookup, and troubleshooting scenario on the rest of the exam assumes you can distinguish volts from amps and read a meter correctly. Get the units wrong and every downstream answer is wrong.
Units and Quantities
Electrical work is governed by four interrelated quantities. Memorize the unit and its symbol; the exam often uses the symbol without spelling it out.
| Quantity | Unit | Symbol | What it measures |
|---|---|---|---|
| Voltage (potential difference) | volt | V (E in formulas) | electrical "pressure" pushing charge |
| Current | ampere | A (I) | flow rate of charge |
| Resistance | ohm | Ω (R) | opposition to current flow |
| Power (real) | watt | W (P) | rate of useful work done |
| Apparent power | volt-ampere | VA | total power delivered by source |
| Reactive power | var | var | power oscillating in reactive elements |
Volt-amperes (VA) differ from watts when a circuit has reactance: W = VA × power factor. Resistive loads (heaters, incandescent lamps) have W ≈ VA; motors and ballasts do not. The NEC lists many equipment ratings in VA (not W) because the source must supply apparent power regardless of PF. A 1500 VA transformer at 0.8 PF delivers only 1200 W of real work.
Conductors and Insulators
A conductor permits current flow with low resistance — copper, aluminum, or copper-clad aluminum. Per NEC 110.5, conductors must be one of these three materials unless the Code provides otherwise; when a rule does not name the material, the sizes given are based on copper. An insulator resists current flow — thermoplastic, rubber, ceramic. Insulation is rated by temperature (60°C, 75°C, 90°C) and environment (moisture-resistant THWN, sunlight-resistant XHHW-2). Conductor ampacity in Table 310.16 depends on both the metal and the insulation temperature rating: a 12 AWG copper THHN is rated 30 A at 90°C column but only 25 A where the 75°C column applies (terminations limit the usable ampacity).
Exam Terminology You Must Know
- Ampacity — current-carrying capacity of a conductor in amperes, from Tables 310.16–310.20 with correction (temperature) and adjustment (conduit fill) factors applied.
- Voltage drop — reduction in voltage along a conductor due to resistance; NEC recommends ≤3% on branch circuits and ≤5% total (feeder + branch) for reasonable efficiency.
- Continuous load — a load expected to run 3 hours or more (Article 100); branch-circuit conductors and overcurrent devices must be sized at 125% of a continuous load.
- Nominal voltage — the named system voltage (120V, 208Y/120V, 480Y/277V); used for equipment voltage ratings per NEC 110.4.
- AWG — American Wire Gauge; conductor size system per NEC 110.6. Larger gauge number = smaller conductor (14 AWG < 10 AWG < 1/0 AWG). Sizes above 4/0 AWG are expressed in kcmil (thousands of circular mils).
Reading Electrical Drawings
The exam references symbols, not photos. Key conventions:
- One-line diagram — a simplified schematic showing the source, disconnects, overcurrent devices, transformers, and loads in a single line per phase.
- Common symbols: a switch is two triangles touching points; a receptacle is an arc with a dot; a luminaire is a circle with an X; the grounded (neutral) conductor is identified by three horizontal dashes or the letter N.
- Panelboard schedules list circuit number, load description, conductor size, OCPD rating, and phase (A/B/C). A balanced panel spreads loads across phases so the neutral carries only the unbalanced current.
Measurement Tools
| Tool | Measures | How to use |
|---|---|---|
| Digital multimeter (DMM) | voltage (V), current (A), resistance (Ω), continuity | select range/function, connect leads across the component (V, Ω) or in series (A) |
| Clamp meter | AC current without breaking the circuit | clamp around one conductor only; clamping both current-carrying conductors cancels the reading |
| Megohmmeter (megger) | insulation resistance in megohms (MΩ) | apply a high DC test voltage (500–1000V) between the conductor and ground; detects degraded insulation a normal ohmmeter cannot |
Safety note: Verify the meter is rated for the installation category (CAT III or CAT IV for service work) and the voltage present. A CAT II meter applied to a CAT III service can fail catastrophically. Always test the meter on a known live source first, then on the de-energized circuit, then on the live source again — the "live-dead-live" check required by NFPA 70E.
Worked Example: Measuring a Receptacle Circuit
A 120V receptacle reads 118.2V under a 14 A load. The one-way run is 100 ft of 12 AWG copper (≈1.93 Ω/1000 ft from Chapter 9, Table 8). Voltage drop is:
Vd = (2 × L × I × R) / 1000 = (2 × 100 × 14 × 1.93) / 1000 ≈ 5.4 V
That is 5.4 / 120 = 4.5% — over the 3% branch-circuit recommendation, so the run needs a larger conductor (10 AWG, ≈1.21 Ω/kft, gives Vd ≈ 3.4 V or 2.8%). This is the exact kind of reasoning the exam tests: measure, calculate, decide.
Which unit measures apparent power in an AC circuit?
watt (W)
volt-ampere (VA)
var
joule (J)
What does a megohmmeter (megger) measure that a standard ohmmeter cannot?
Insulation resistance in megohms using a high DC test voltage
AC current by clamping around a conductor
Real power in watts under load
Conductor temperature rise at rated ampacity
Per NEC 110.5, which three conductor materials are permitted unless the Code provides otherwise?
Copper, silver, and gold
Copper, aluminum, and copper-clad aluminum
Aluminum, steel, and copper-clad aluminum
Copper, copper-clad steel, and aluminum alloy
Sections you finish are checked off in the contents.