PracticeVideosBlogFlashcards

5.3 Touch Voltage, Protective Conductor Sizing, and Main Earthing Terminals

Key Takeaways

  • Touch voltage (Ut) represents the voltage drop across the circuit protective conductor (R2) during an earth fault, defined by Ut = If × R2 = U0 × [R2 / (R1 + R2)].

  • Earth Fault Loop Impedance (Zs = Ze + R1 + R2) must be verified against maximum allowable limits (Zs(max)) in SS 638, incorporating temperature adjustment factors (1.20 for PVC, 1.28 for XLPE).

  • Circuit Protective Conductors (CPCs) are sized either using standard table selection (SS 638 Table 54.7) or calculated via the Adiabatic Equation S = √(I² t) / k.

  • The Main Earthing Terminal (MET) serves as the central earthing junction and must feature a removable link to facilitate earth electrode resistance testing without disturbing building protective bonding.

  • Earthing conductors for domestic supplies up to 45 kVA require a minimum cross-sectional area of 6 mm² copper, while main protective bonding conductors must be at least half the earthing conductor size (min 6 mm², max 25 mm²).

Last updated: August 2026

5.3 Touch Voltage, Protective Conductor Sizing, and Main Earthing Terminals

Quick Summary: Verifying electrical safety under SS 638 requires precise calculation of Touch Voltage (UtU_t) and Earth Fault Loop Impedance (ZsZ_s). The total loop impedance Zs=Ze+(R1+R2)Z_s = Z_e + (R_1 + R_2) must be corrected for conductor operating temperatures and verified against statutory tables. Circuit Protective Conductors (CPCs) are sized either using simplified selection tables or the Adiabatic Equation (S=I2tkS = \frac{\sqrt{I^2 t}}{k}). The Main Earthing Terminal (MET) forms the central grounding node, requiring a removable disconnecting link for earth electrode testing and strict minimum conductor sizing (6 mm26\text{ mm}^2 minimum copper earthing conductor up to 45 kVA45\text{ kVA}).


1. Mathematical Analysis of Touch Voltage (UtU_t)

During a phase-to-earth insulation fault on a Class I appliance, the exposed metallic enclosure becomes energized. The magnitude of potential appearing on the metal enclosure relative to true earth—or relative to adjacent earthed structural metalwork—is termed the Touch Voltage (UtU_t).

          [ TOUCH VOLTAGE DISTRIBUTION IN A PHASE-TO-EARTH FAULT ]

 Substation Transformer              Consumer Distribution Board       Fault Site
 Phase (230V) -------------[ R1 Line Conductor ]------------------> Exposed Metal
                                                                           |
   Ut = Touch Voltage Across Human Body <----------------------------------+
                                                                           |
 MET Busbar <-------------[ R2 Protective Conductor (CPC) ]---------------+ 
     |
     +---[ Ze Supply Earth Return ]---> Transformer Star Point

Touch Voltage Derivation

Let U0U_0 be the nominal phase-to-earth supply voltage (230 V AC230\text{ V AC}), ZeZ_e be external earth fault loop impedance, R1R_1 be phase conductor resistance, and R2R_2 be Circuit Protective Conductor (CPC) resistance. The prospective earth fault current IfI_f is:

If=U0Zs=U0Ze+R1+R2I_f = \frac{U_0}{Z_s} = \frac{U_0}{Z_e + R_1 + R_2}

The touch voltage UtU_t appearing on the faulty appliance casing is the voltage drop across the protective conductor (R2R_2) back to the main equipotential zone:

Ut=If×R2=U0×R2Ze+R1+R2U_t = I_f \times R_2 = U_0 \times \frac{R_2}{Z_e + R_1 + R_2}

Where ZeZ_e is small relative to circuit wiring (common in local distribution boards in TN-S systems), the equation simplifies to:

Ut=U0×R2R1+R2U_t = U_0 \times \frac{R_2}{R_1 + R_2}

Impact of Conductor Sizing Ratio (R1/R2R_1 / R_2)

  • Equal Conductor Sizes (S1=S2  ⟹  R1=R2S_1 = S_2 \implies R_1 = R_2): Ut=230 V×R2R2+R2=230 V×0.5=115 V ACU_t = 230\text{ V} \times \frac{R_2}{R_2 + R_2} = 230\text{ V} \times 0.5 = 115\text{ V AC} Since 115 V AC115\text{ V AC} greatly exceeds the conventional safe limit (UL=50 V ACU_L = 50\text{ V AC}), Automatic Disconnection of Supply (ADS) MUST isolate the circuit within 0.4 s0.4\text{ s} to prevent fatal injury.
  • Oversized Protective Conductor (S2>S1  ⟹  R2<R1S_2 > S_1 \implies R_2 < R_1): If CPC cross-sectional area is increased such that R2=0.25×R1R_2 = 0.25 \times R_1, touch voltage drops to: Ut=230 V×0.251.0+0.25=230 V×0.20=46 V ACU_t = 230\text{ V} \times \frac{0.25}{1.0 + 0.25} = 230\text{ V} \times 0.20 = 46\text{ V AC} Because 46 V AC<50 V AC46\text{ V AC} < 50\text{ V AC}, the touch voltage remains below the dangerous threshold even during the fault duration.

2. Earth Fault Loop Impedance (ZsZ_s) Calculations & Thermal Corrections

To ensure protective devices operate within mandatory disconnection times (0.4 s0.4\text{ s} for final circuits), the total Earth Fault Loop Impedance (ZsZ_s) measured at the furthest point of the circuit must satisfying:

Zs≤Zs(max)Z_s \le Z_{s(\text{max})}

Where Zs(max)Z_{s(\text{max})} is the maximum allowable loop impedance published in SS 638 Tables 41.2, 41.3, and 41.4 for the specific rating and trip curve of the circuit breaker or fuse.

                  [ TOTAL EARTH FAULT LOOP PATH (Zs) ]

+-------------------------------------------------------------------------+
| Zs = Ze (External Supply Loop) + R1 (Phase Cable) + R2 (CPC Conductor)  |
+-------------------------------------------------------------------------+
  [Substation Trans.] -> [Intake Service] -> [Phase Wire R1] -> [Fault Point]
          ^                                                          |
          |                                                          v
  [Substation Earth] <- [Cable Sheath Ze] <- [MET Node] <- [CPC Wire R2]

Temperature Correction Factor Adjustment

Standard cable resistance values (r1+r2r_1 + r_2) provided in technical tables are measured at an ambient temperature of 20∘C20^\circ\text{C}. However, during normal operating conditions or fault carrying states, conductor copper temperatures rise to maximum operating limits (70∘C70^\circ\text{C} for PVC insulation, 90∘C90^\circ\text{C} for XLPE insulation).

Because copper resistance increases with temperature (Rθ=R20[1+α20(θ−20)]R_\theta = R_{20}[1 + \alpha_{20}(\theta - 20)]), SS 638 mandates multiplying ambient measured resistance (R1+R2)20(R_1 + R_2)_{20} by a thermal correction factor:

  • PVC Insulated Cables (70∘C70^\circ\text{C} Max Temp): Temperature Correction Factor = 1.201.20
  • XLPE / Thermosetting Cables (90∘C90^\circ\text{C} Max Temp): Temperature Correction Factor = 1.281.28

Master Loop Impedance Temperature Formula

Zs(fault)=Ze+1.20×(R1+R2)20≤Zs(max)Z_{s(\text{fault})} = Z_e + 1.20 \times (R_1 + R_2)_{20} \le Z_{s(\text{max})}

When performing field testing at ambient 20∘C20^\circ\text{C}, the Licensed Electrical Worker (LEW) must verify that measured ambient loop impedance satisfies the 80% Rule (Zs(measured)≤0.80×Zs(max)Z_{s(\text{measured})} \le 0.80 \times Z_{s(\text{max})}) to account for thermal rise during actual fault conditions.


3. Sizing Circuit Protective Conductors (CPCs)

Under SS 638 Regulation 543.1, Circuit Protective Conductors must be sized using one of two approved methods: Method A (Standard Table Selection) or Method B (The Adiabatic Equation).

Method A: Simplified Selection Table (SS 638 Table 54.7)

When the protective conductor is constructed from the same metal (copper) as the line conductor, minimum CPC cross-sectional area (SpS_p) is selected directly from Table 54.7:

Line Conductor Cross-Sectional Area (SS) [mm2\text{mm}^2]Minimum Cross-Sectional Area of Protective Conductor (SpS_p) [mm2\text{mm}^2]
S≤16 mm2S \le 16\text{ mm}^2Sp=SS_p = S (Equal to Phase Conductor CSA)
16 mm2<S≤35 mm216\text{ mm}^2 < S \le 35\text{ mm}^2Sp=16 mm2S_p = 16\text{ mm}^2
S>35 mm2S > 35\text{ mm}^2Sp=S2S_p = \frac{S}{2} (Half of Phase Conductor CSA)

Method B: The Adiabatic Equation (SS 638 Regulation 543.1.3)

For precise economic engineering design—or where cable materials differ—the CPC cross-sectional area (SS) must not be less than the value calculated by the Adiabatic Equation:

S=I2tkS = \frac{\sqrt{I^2 t}}{k}

Where:

  • SS: Minimum cross-sectional area of protective conductor (mm2\text{mm}^2).
  • II: Prospective earth fault current (rms AC Amperes) for a fault of negligible impedance.
  • tt: Operating disconnection time of the protective device (seconds).
  • kk: Factor taking into account the resistivity, temperature coefficient, and heat capacity of the conductor metal, as well as initial and final conductor temperatures.

Tabulated kk Factors under SS 638 (Tables 54.2 to 54.6)

Conductor Metal & Cable TypeInsulation / Thermal LimitInitial Temp (∘C^\circ\text{C})Final Temp (∘C^\circ\text{C})kk Factor Value
Copper (PVC Insulated Cable)PVC (70∘C70^\circ\text{C})30∘C30^\circ\text{C}160∘C160^\circ\text{C}115115
Copper (XLPE / EPR Cable)XLPE (90∘C90^\circ\text{C})30∘C30^\circ\text{C}250∘C250^\circ\text{C}143143
Copper (Bare Conductor)Uninsulated30∘C30^\circ\text{C}200∘C200^\circ\text{C}159159
Aluminium (PVC Cable)PVC (70∘C70^\circ\text{C})30∘C30^\circ\text{C}160∘C160^\circ\text{C}7676
Steel (Cable Armour / Trunking)Galvanized Steel30∘C30^\circ\text{C}160∘C160^\circ\text{C}5151 (Armour) / 4747 (Conduit)

Worked Step-by-Step Engineering Calculation

  • Scenario: Calculate minimum copper PVC CPC size for a circuit with prospective fault current I=2000 AI = 2000\text{ A}, cleared by an MCB in t=0.10 st = 0.10\text{ s}. Copper PVC k=115k = 115.
  • Step 1: Calculate thermal energy value (I2tI^2 t): I2t=(2000)2×0.10=4,000,000×0.10=400,000 A2sI^2 t = (2000)^2 \times 0.10 = 4,000,000 \times 0.10 = 400,000\text{ A}^2\text{s}
  • Step 2: Calculate square root of thermal energy: I2t=400,000=632.455\sqrt{I^2 t} = \sqrt{400,000} = 632.455
  • Step 3: Apply Adiabatic Equation: S=632.455115=5.50 mm2S = \frac{632.455}{115} = 5.50\text{ mm}^2
  • Step 4: Select commercial cable size: Next standard commercial cable size ≥5.50 mm2\ge 5.50\text{ mm}^2 is 6.0 mm26.0\text{ mm}^2.

4. Main Earthing Terminal (MET) Architecture & Sizing Rules

The Main Earthing Terminal (MET) is the central distribution node where the earthing conductor, main protective bonding conductors, circuit protective conductors, and functional earth conductors are securely interconnected.

                   [ MAIN EARTHING TERMINAL (MET) NODE ]

   SP PowerGrid Cable Sheath / Earth Rod
                  |
                  v
       [ Earthing Conductor ]
                  |
                  v
   +--------------------------------------------------------------+
   |               MAIN EARTHING TERMINAL (MET)                   |
   |  +--------------------------------------------------------+  |
   |  |        REMOVABLE EARTH DISCONNECTING LINK              |  |
   |  +--------------------------------------------------------+  |
   +--------------------------------------------------------------+
        |                         |                        |
        v                         v                        v
 [Main Protective Bonding]   [Circuit Protective]     [Functional Earth]
 (Water/Gas/Steel Pipes)     Conductors (CPCs)       (Clean IT Earth)

Removable Disconnecting Link Requirements

SS 638 mandates that the MET must feature a robust, brass or copper removable disconnecting link. This link can only be unbolted using a tool. It allows the LEW to isolate the earth electrode from the building installation during periodic testing to measure earth electrode resistance (RAR_A) using a 3-pole Earth Resistance Tester without disconnecting active building protective bonding.

Statutory Conductor Sizing Mandates under SS 638

  1. Earthing Conductor (Connecting MET to Earth Electrode / Intake Earth):
    • For domestic premises and small commercial intakes up to 45 kVA45\text{ kVA} (230 V230\text{ V} single-phase or 400 V400\text{ V} three-phase supplies, ≈65 A\approx 65\text{ A} per phase): Minimum 6 mm26\text{ mm}^2 copper.
    • Buried earthing conductors protected against corrosion but NOT mechanically protected: Minimum 16 mm216\text{ mm}^2 copper.
    • Buried earthing conductors NOT protected against corrosion: Minimum 25 mm225\text{ mm}^2 copper.
  2. Main Protective Bonding Conductors (Connecting MET to Extraneous Services):
    • Minimum cross-sectional area: Must not be less than half the required CSA of the earthing conductor of the installation, with a strict minimum of 6 mm26\text{ mm}^2 copper.
    • Maximum capping: Need not exceed 25 mm225\text{ mm}^2 copper regardless of main intake size.
Loading diagram...
Main Earthing Terminal (MET) Infrastructure Layout
Test Your Knowledge

Using the Adiabatic Equation S = √(I² t) / k, calculate the minimum required copper CPC size for a circuit experiencing a prospective earth fault current I = 1500 A cleared in t = 0.10 s, given k = 115.

A

2.5 mm²

B

4.0 mm²

C

6.0 mm²

D

10.0 mm²

Test Your Knowledge

Under SS 638 Table 54.7, what is the minimum cross-sectional area required for a copper Circuit Protective Conductor (CPC) when the copper phase conductor cross-sectional area is 25 mm²?

A

6 mm²

B

10 mm²

C

16 mm²

D

25 mm²

Test Your Knowledge

What is the minimum cross-sectional area specified by SS 638 for a copper earthing conductor in a domestic installation rated up to 45 kVA?

A

2.5 mm²

B

4.0 mm²

C

6.0 mm²

D

16.0 mm²

Sections you finish are checked off in the contents.