5.3 Touch Voltage, Protective Conductor Sizing, and Main Earthing Terminals
Key Takeaways
- Touch voltage (Ut) represents the voltage drop across the circuit protective conductor (R2) during an earth fault, defined by Ut = If × R2 = U0 × [R2 / (R1 + R2)].
- Earth Fault Loop Impedance (Zs = Ze + R1 + R2) must be verified against maximum allowable limits (Zs(max)) in SS 638, incorporating temperature adjustment factors (1.20 for PVC, 1.28 for XLPE).
- Circuit Protective Conductors (CPCs) are sized either using standard table selection (SS 638 Table 54.7) or calculated via the Adiabatic Equation S = √(I² t) / k.
- The Main Earthing Terminal (MET) serves as the central earthing junction and must feature a removable link to facilitate earth electrode resistance testing without disturbing building protective bonding.
- Earthing conductors for domestic supplies up to 45 kVA require a minimum cross-sectional area of 6 mm² copper, while main protective bonding conductors must be at least half the earthing conductor size (min 6 mm², max 25 mm²).
5.3 Touch Voltage, Protective Conductor Sizing, and Main Earthing Terminals
Quick Summary: Verifying electrical safety under SS 638 requires precise calculation of Touch Voltage ($U_t$) and Earth Fault Loop Impedance ($Z_s$). The total loop impedance $Z_s = Z_e + (R_1 + R_2)$ must be corrected for conductor operating temperatures and verified against statutory tables. Circuit Protective Conductors (CPCs) are sized either using simplified selection tables or the Adiabatic Equation ($S = \frac{\sqrt{I^2 t}}{k}$). The Main Earthing Terminal (MET) forms the central grounding node, requiring a removable disconnecting link for earth electrode testing and strict minimum conductor sizing ($6\text{ mm}^2$ minimum copper earthing conductor up to $45\text{ kVA}$).
1. Mathematical Analysis of Touch Voltage ($U_t$)
During a phase-to-earth insulation fault on a Class I appliance, the exposed metallic enclosure becomes energized. The magnitude of potential appearing on the metal enclosure relative to true earth—or relative to adjacent earthed structural metalwork—is termed the Touch Voltage ($U_t$).
[ TOUCH VOLTAGE DISTRIBUTION IN A PHASE-TO-EARTH FAULT ]
Substation Transformer Consumer Distribution Board Fault Site
Phase (230V) -------------[ R1 Line Conductor ]------------------> Exposed Metal
|
Ut = Touch Voltage Across Human Body <----------------------------------+
|
MET Busbar <-------------[ R2 Protective Conductor (CPC) ]---------------+
|
+---[ Ze Supply Earth Return ]---> Transformer Star Point
Touch Voltage Derivation
Let $U_0$ be the nominal phase-to-earth supply voltage ($230\text{ V AC}$), $Z_e$ be external earth fault loop impedance, $R_1$ be phase conductor resistance, and $R_2$ be Circuit Protective Conductor (CPC) resistance. The prospective earth fault current $I_f$ is:
The touch voltage $U_t$ appearing on the faulty appliance casing is the voltage drop across the protective conductor ($R_2$) back to the main equipotential zone:
Where $Z_e$ is small relative to circuit wiring (common in local distribution boards in TN-S systems), the equation simplifies to:
Impact of Conductor Sizing Ratio ($R_1 / R_2$)
- Equal Conductor Sizes ($S_1 = S_2 \implies R_1 = R_2$): Since $115\text{ V AC}$ greatly exceeds the conventional safe limit ($U_L = 50\text{ V AC}$), Automatic Disconnection of Supply (ADS) MUST isolate the circuit within $0.4\text{ s}$ to prevent fatal injury.
- Oversized Protective Conductor ($S_2 > S_1 \implies R_2 < R_1$): If CPC cross-sectional area is increased such that $R_2 = 0.25 \times R_1$, touch voltage drops to: Because $46\text{ V AC} < 50\text{ V AC}$, the touch voltage remains below the dangerous threshold even during the fault duration.
2. Earth Fault Loop Impedance ($Z_s$) Calculations & Thermal Corrections
To ensure protective devices operate within mandatory disconnection times ($0.4\text{ s}$ for final circuits), the total Earth Fault Loop Impedance ($Z_s$) measured at the furthest point of the circuit must satisfying:
Where $Z_{s(\text{max})}$ is the maximum allowable loop impedance published in SS 638 Tables 41.2, 41.3, and 41.4 for the specific rating and trip curve of the circuit breaker or fuse.
[ TOTAL EARTH FAULT LOOP PATH (Zs) ]
+-------------------------------------------------------------------------+
| Zs = Ze (External Supply Loop) + R1 (Phase Cable) + R2 (CPC Conductor) |
+-------------------------------------------------------------------------+
[Substation Trans.] -> [Intake Service] -> [Phase Wire R1] -> [Fault Point]
^ |
| v
[Substation Earth] <- [Cable Sheath Ze] <- [MET Node] <- [CPC Wire R2]
Temperature Correction Factor Adjustment
Standard cable resistance values ($r_1 + r_2$) provided in technical tables are measured at an ambient temperature of $20^\circ\text{C}$. However, during normal operating conditions or fault carrying states, conductor copper temperatures rise to maximum operating limits ($70^\circ\text{C}$ for PVC insulation, $90^\circ\text{C}$ for XLPE insulation).
Because copper resistance increases with temperature ($R_\theta = R_{20}[1 + \alpha_{20}(\theta - 20)]$), SS 638 mandates multiplying ambient measured resistance $(R_1 + R_2)_{20}$ by a thermal correction factor:
- PVC Insulated Cables ($70^\circ\text{C}$ Max Temp): Temperature Correction Factor = $1.20$
- XLPE / Thermosetting Cables ($90^\circ\text{C}$ Max Temp): Temperature Correction Factor = $1.28$
Master Loop Impedance Temperature Formula
When performing field testing at ambient $20^\circ\text{C}$, the Licensed Electrical Worker (LEW) must verify that measured ambient loop impedance satisfies the 80% Rule ($Z_{s(\text{measured})} \le 0.80 \times Z_{s(\text{max})}$) to account for thermal rise during actual fault conditions.
3. Sizing Circuit Protective Conductors (CPCs)
Under SS 638 Regulation 543.1, Circuit Protective Conductors must be sized using one of two approved methods: Method A (Standard Table Selection) or Method B (The Adiabatic Equation).
Method A: Simplified Selection Table (SS 638 Table 54.7)
When the protective conductor is constructed from the same metal (copper) as the line conductor, minimum CPC cross-sectional area ($S_p$) is selected directly from Table 54.7:
| Line Conductor Cross-Sectional Area ($S$) [$ ext{mm}^2$] | Minimum Cross-Sectional Area of Protective Conductor ($S_p$) [$ ext{mm}^2$] |
|---|---|
| $S \le 16\text{ mm}^2$ | $S_p = S$ (Equal to Phase Conductor CSA) |
| $16\text{ mm}^2 < S \le 35\text{ mm}^2$ | $S_p = 16\text{ mm}^2$ |
| $S > 35\text{ mm}^2$ | $S_p = \frac{S}{2}$ (Half of Phase Conductor CSA) |
Method B: The Adiabatic Equation (SS 638 Regulation 543.1.3)
For precise economic engineering design—or where cable materials differ—the CPC cross-sectional area ($S$) must not be less than the value calculated by the Adiabatic Equation:
Where:
- $S$: Minimum cross-sectional area of protective conductor ($ ext{mm}^2$).
- $I$: Prospective earth fault current (rms AC Amperes) for a fault of negligible impedance.
- $t$: Operating disconnection time of the protective device (seconds).
- $k$: Factor taking into account the resistivity, temperature coefficient, and heat capacity of the conductor metal, as well as initial and final conductor temperatures.
Tabulated $k$ Factors under SS 638 (Tables 54.2 to 54.6)
| Conductor Metal & Cable Type | Insulation / Thermal Limit | Initial Temp ($^\circ ext{C}$) | Final Temp ($^\circ ext{C}$) | $k$ Factor Value |
|---|---|---|---|---|
| Copper (PVC Insulated Cable) | PVC ($70^\circ\text{C}$) | $30^\circ\text{C}$ | $160^\circ\text{C}$ | $115$ |
| Copper (XLPE / EPR Cable) | XLPE ($90^\circ\text{C}$) | $30^\circ\text{C}$ | $250^\circ\text{C}$ | $143$ |
| Copper (Bare Conductor) | Uninsulated | $30^\circ\text{C}$ | $200^\circ\text{C}$ | $159$ |
| Aluminium (PVC Cable) | PVC ($70^\circ\text{C}$) | $30^\circ\text{C}$ | $160^\circ\text{C}$ | $76$ |
| Steel (Cable Armour / Trunking) | Galvanized Steel | $30^\circ\text{C}$ | $160^\circ\text{C}$ | $51$ (Armour) / $47$ (Conduit) |
Worked Step-by-Step Engineering Calculation
- Scenario: Calculate minimum copper PVC CPC size for a circuit with prospective fault current $I = 2000\text{ A}$, cleared by an MCB in $t = 0.10\text{ s}$. Copper PVC $k = 115$.
- Step 1: Calculate thermal energy value ($I^2 t$):
- Step 2: Calculate square root of thermal energy:
- Step 3: Apply Adiabatic Equation:
- Step 4: Select commercial cable size: Next standard commercial cable size $\ge 5.50\text{ mm}^2$ is $6.0\text{ mm}^2$.
4. Main Earthing Terminal (MET) Architecture & Sizing Rules
The Main Earthing Terminal (MET) is the central distribution node where the earthing conductor, main protective bonding conductors, circuit protective conductors, and functional earth conductors are securely interconnected.
[ MAIN EARTHING TERMINAL (MET) NODE ]
SP PowerGrid Cable Sheath / Earth Rod
|
v
[ Earthing Conductor ]
|
v
+--------------------------------------------------------------+
| MAIN EARTHING TERMINAL (MET) |
| +--------------------------------------------------------+ |
| | REMOVABLE EARTH DISCONNECTING LINK | |
| +--------------------------------------------------------+ |
+--------------------------------------------------------------+
| | |
v v v
[Main Protective Bonding] [Circuit Protective] [Functional Earth]
(Water/Gas/Steel Pipes) Conductors (CPCs) (Clean IT Earth)
Removable Disconnecting Link Requirements
SS 638 mandates that the MET must feature a robust, brass or copper removable disconnecting link. This link can only be unbolted using a tool. It allows the LEW to isolate the earth electrode from the building installation during periodic testing to measure earth electrode resistance ($R_A$) using a 3-pole Earth Resistance Tester without disconnecting active building protective bonding.
Statutory Conductor Sizing Mandates under SS 638
- Earthing Conductor (Connecting MET to Earth Electrode / Intake Earth):
- For domestic premises and small commercial intakes up to $45\text{ kVA}$ ($230\text{ V}$ single-phase or $400\text{ V}$ three-phase supplies, $\approx 65\text{ A}$ per phase): Minimum $6\text{ mm}^2$ copper.
- Buried earthing conductors protected against corrosion but NOT mechanically protected: Minimum $16\text{ mm}^2$ copper.
- Buried earthing conductors NOT protected against corrosion: Minimum $25\text{ mm}^2$ copper.
- Main Protective Bonding Conductors (Connecting MET to Extraneous Services):
- Minimum cross-sectional area: Must not be less than half the required CSA of the earthing conductor of the installation, with a strict minimum of $6\text{ mm}^2$ copper.
- Maximum capping: Need not exceed $25\text{ mm}^2$ copper regardless of main intake size.
Using the Adiabatic Equation S = √(I² t) / k, calculate the minimum required copper CPC size for a circuit experiencing a prospective earth fault current I = 1500 A cleared in t = 0.10 s, given k = 115.
Under SS 638 Table 54.7, what is the minimum cross-sectional area required for a copper Circuit Protective Conductor (CPC) when the copper phase conductor cross-sectional area is 25 mm²?
What is the minimum cross-sectional area specified by SS 638 for a copper earthing conductor in a domestic installation rated up to 45 kVA?