6.1 Single-Line Diagram (SLD) Preparation, Symbols, and Standard Layouts

Key Takeaways

  • A Single-Line Diagram (SLD) is a simplified schematic representation of a three-phase or single-phase electrical installation required under Singapore Electricity Regulations and SS 638.
  • Graphical symbols used in Singapore SLDs must comply strictly with IEC 60617 / SS 638 standards to ensure uniformity, clarity, and safety compliance across all Licensed Electrical Worker (LEW) submissions.
  • Every electrical installation connected to the SP Group low-voltage grid (400V 3-phase / 230V single-phase) must feature a clearly demarcated TN-S earthing system and Main Earthing Terminal (MET).
  • A compliant SLD must detail incoming supply ratings, main switchboard (MSB) busbar capacity, protective device ratings, prospective short-circuit current (Ipscc), cable cross-sectional areas, and earthing conductors.
  • Under EMA regulations, an up-to-date, LEW-endorsed copy of the SLD must be permanently framed and displayed adjacent to the main intake switchboard or consumer unit.
Last updated: August 2026

6.1 Single-Line Diagram (SLD) Preparation, Symbols, and Standard Layouts

Quick Summary: In Singapore's electrical power framework, a Single-Line Diagram (SLD) is the fundamental blueprint depicting the electrical architecture of an installation. Governed by SS 638 (Code of Practice for Electrical Installations) and IEC 60617 graphical standards, the SLD illustrates electrical supply intake, protection hierarchy, busbar arrangements, cable specifications, earthing configurations, and outgoing sub-circuits using standard single-line conventions. Every installation supervised by a Licensed Electrical Worker (LEW) must possess a valid, updated SLD endorsed by the LEW and displayed prominently at the main switchboard.


1. Statutory Purpose and Regulatory Role of Single-Line Diagrams

Under the Electricity (Electrical Installations) Regulations and SS 638 Clause 514.9, an up-to-date schematic diagram must be provided for every installation. The SLD serves as the master technical document for initial plan submission to SP Services / SP PowerGrid, regulatory audits by Energy Market Authority (EMA) inspectors, operational switching, fault troubleshooting, and routine annual maintenance.

Primary Technical Functions of the SLD:

  1. Design Verification: Demonstrates to authorities that protective device ratings, breaking capacities, cable current-carrying capacities, and earthing arrangements satisfy SS 638 requirements.
  2. Operational Safety: Enables LEWs, plant engineers, and technicians to execute safe isolation, lock-out/tag-out (LOTO) procedures, and emergency supply disconnections without ambiguity.
  3. Demarcation of Responsibility: Clearly highlights the legal interface between SP PowerGrid's incoming revenue meter / service cables and the consumer's internal electrical installation.
  4. Maintenance & Modification Tracking: Provides a historical baseline record; any physical alteration, circuit expansion, or protection setting modification requires immediate revision and LEW re-endorsement on the SLD.

2. Standard Graphical Symbols per IEC 60617 and SS 638

To eliminate operational misinterpretation, all electrical schematics in Singapore must utilize standardized graphical symbols — in Singapore, SS CP 83 Part 2 (Code of Practice for construction computer-aided design (CAD) – Part 2: CAD symbols, aligned with IEC 60617), which the EMA assessment syllabus and technical interview specifically reference. The table below details the most essential graphical symbols and technical representations prescribed under CP 83 Part 2 / IEC 60617 and SS 638:

Component / DeviceGraphical Representation / Symbol StandardFunctional Role & Technical Specification
Incoming Supply (3-Phase 4-Wire)400V / 230V 3Ph 4W 50Hz (TN-S)Public low-voltage supply delivered by SP PowerGrid (3 phase conductors + neutral + protective earth).
Main Isolator / DisconnectorKnife switch symbol (double break without automatic trip)Provides manual point of isolation; must break all live conductors (4-pole for 3-phase with switched neutral).
Moulded Case Circuit Breaker (MCCB)Rectangular body with thermal-magnetic / electronic trip iconOverload ($I_r$) and short-circuit ($I_{sd}/I_i$) protection for distribution sub-mains ($>63\text{A}$).
Miniature Circuit Breaker (MCB)Toggle switch with magnetic & thermal trip curve markingsFinal circuit overload and short-circuit protection (typically $\le 63\text{A}$, Type B, C, or D curves).
Residual Current Circuit Breaker (RCCB)Circuit breaker symbol with toroidal differential transformer iconEarth leakage protection; trips automatically upon sensing residual differential current ($30\text{mA}$, $100\text{mA}$, or $300\text{mA}$).
Current Transformer (CT)Circle surrounding primary conductor line or double loopSteps down primary phase current to standard $5\text{A}$ secondary rating for metering instruments or protection relays.
kWh Energy MeterSquare box labelled kWh or M with pulse output connectionsRevenue or check meter installed by SP Group or consumer to measure active electrical energy consumption.
Main Earthing Terminal (MET)Heavy horizontal bar with earth symbol connectedCentral connection node linking the main earth conductor, earth electrode, metallic service pipes, and neutral earthing link.
Earth Electrode / Ground RodVertical rod with downward tapering horizontal barsCopper-bonded steel driven into ground to establish low Earth Resistance ($R_e \le 1,\Omega$ or $\le 10,\Omega$).

3. SP Group Supply Characteristics and TN-S Earthing Architecture

Low-voltage consumer installations in Singapore receive standard AC power at $400\text{ V}$ (Phase-to-Phase) for three-phase intake or $230\text{ V}$ (Phase-to-Neutral) for single-phase intake, operating at a frequency of $50\text{ Hz}$.

The Mandatory TN-S Earthing System Layout

Singapore Standard SS 638 strictly dictates the TN-S earthing configuration for all public low-voltage grid connections:

  • T (Terre): Direct connection of the power source neutral point to Earth at SP PowerGrid's transformer substation.
  • N (Neutral): Neutral conductor run as a dedicated, insulated line from the source to consumer loads.
  • S (Separated): Protective Earth (PE) conductor maintained as a completely separate conductor throughout the grid and consumer installation.
Substation Transformer Intake                     Consumer Main Switchboard (MSB)
+-------------------------------+               +---------------------------------+
| L1  --------------------------|---------------+--------> Phase L1 Busbar        |
| L2  --------------------------|---------------+--------> Phase L2 Busbar        |
| L3  --------------------------|---------------+--------> Phase L3 Busbar        |
| N   -----(Substation Earth)---|---------------+--------> Neutral Busbar         |
+-------------------------------+               +---------------------------------+
                                                        |
| PE  ----(Cable Sheath/Armor)--|---------------+-------> Main Earthing Terminal  |
+-------------------------------+               |        (MET)                    |
                                                v                                 |
                                         +-------------+                          |
                                         | Local Earth |                          |
                                         | Electrode   |                          |
                                         +-------------+                          |

In a TN-S system, the consumer's Main Earthing Terminal (MET) is connected directly to the metallic lead sheath or armor of SP PowerGrid's service cable (which provides the low-impedance earth return back to the substation neutral point). In addition, SS 638 mandates the installation of a local supplementary Earth Electrode (copper-bonded steel ground rod) connected to the MET to ensure equipotential safety.


4. Structural Layering and Component Specs of a Main Switchboard (MSB)

A compliant Single-Line Diagram for a low-voltage intake must present installation components in a logical top-to-bottom or left-to-right hierarchy:

A. Incoming Supply Demarcation Layer

  • Service Fuses / Cut-Out: SP Group sealed fuses protecting the incoming service cable.
  • SP kWh Metering: Current Transformer (CT) operated meter chamber or direct-connected meter.
  • Incoming Cable Details: Cable type (e.g., $4\times 1\text{C } 300\text{ mm}^2$ XLPE/PVC/SWA/PVC Cu), length, and method of installation.

B. Main Intake Protection & Isolation Layer

  • Main Circuit Breaker: MCCB or Air Circuit Breaker (ACB) with adjustable nominal rating ($I_n$), overload setting ($I_r$), and short-circuit breaking capacity ($I_{cu}$ in kA). Must match or exceed the prospective short-circuit current ($I_{pscc}$) at the point of supply (typically $25\text{ kA}$ to $40\text{ kA}$ at low-voltage intake switchrooms).
  • Protective Relays: Overcurrent relay (50/51) and Earth Fault relay (51N) connected via protection-class CTs (e.g., Class 5P10).

C. Main Busbar Chamber Layer

  • Busbar Material & Cross-Section: High-conductivity tinned copper busbars rated for continuous full-load current (e.g., $100\text{A}$, $200\text{A}$, $400\text{A}$, $800\text{A}$).
  • Short-Circuit Withstand Rating ($I_{cw}$): The maximum r.m.s. short-circuit current the busbar assembly can withstand mechanically and thermally for a duration of $1\text{ second}$ (e.g., $25\text{ kA for 1 sec}$).

D. Sub-Distribution & Outgoing Circuit Layer

  • Protection Devices: Outgoing MCCBs, MCBs, or RCCBs with specific current ratings ($I_n$), number of poles (1P, 2P, 3P, 4P), and short-circuit ratings ($I_{cn}$ e.g., $6\text{ kA}, 10\text{ kA}$).
  • Cable & Load Designations: For every outgoing feeder, the SLD must specify circuit reference number, load description (e.g., "DB-1st-Floor Power", "Air-Con AHU-1"), connected load in kW/kVA, cable size ($mm^2$), conductor material (Cu), and protective conductor size ($mm^2$).

5. Mandatory SLD Presentation & LEW Endorsement Standards

To achieve statutory compliance under EMA guidelines, every published SLD drawing must adhere to exact documentation standards:

  1. Standardized Title Block: Located in the bottom right corner, containing:
    • Name and physical address of the installation.
    • Name, signature, LEW licence number (Electrician, Electrical Technician, or Professional Engineer), and official stamp of the endorsing LEW.
    • Drawing title, drawing reference number, scale (or "N.T.S." - Not To Scale), and date of preparation/revision.
  2. Mandatory Operating Parameters Marked on Drawing:
    • System Voltage & Phase: $400/230\text{V}$, 3-Phase 4-Wire, $50\text{Hz}$, TN-S system.
    • Prospective Short-Circuit Current ($I_{pscc}$) at intake point (e.g., $25\text{ kA}$).
    • Earthing Resistance value ($R_e$) measured at the Earth Electrode.
    • Rating and settings of main protective devices ($I_n$, $I_r$, $I_{sd}$, $I_{\Delta n}$).
  3. Framed Display Requirement: Under SS 638, a clear, durable, framed print of the latest LEW-endorsed SLD must be permanently mounted inside or immediately adjacent to the main intake switchroom, distribution board room, or consumer unit.
Loading diagram...
Standard Low-Voltage 3-Phase Main Switchboard SLD Hierarchy
Test Your Knowledge

Which earthing system arrangement is strictly mandated by SS 638 for all public low-voltage consumer connections supplied by SP PowerGrid in Singapore?

A
B
C
D
Test Your Knowledge

On an SLD for a 400V main switchboard, what does an outgoing MCCB short-circuit rating of Icu = 25 kA represent?

A
B
C
D
Test Your Knowledge

According to SS 638 and EMA regulations, where must a durable, framed copy of the endorsed Single-Line Diagram be placed?

A
B
C
D