4.2 Three-Phase Relationships and Real, Apparent, and Reactive Power
Key Takeaways
In a star (Y) system the line voltage is √3 times the phase voltage (400 V / 230 V) while line current equals phase current; in a delta (Δ) system line voltage equals phase voltage while line current is √3 times phase current.
Three-phase power formulas: P = √3 × VL × IL × cos φ (kW), Q = √3 × VL × IL × sin φ (kVAr), S = √3 × VL × IL (kVA); single-phase: P = V × I × cos φ.
The power triangle links real, reactive, and apparent power: S² = P² + Q², with power factor cos φ = P / S.
A 400 V, 2 kW, 3-phase motor at 0.8 power factor draws a running current of 2000 / (√3 × 400 × 0.8) = 3.61 A, and 6–8 times that (≈22–29 A) when started direct-on-line.
Cables are sized for running current, not starting current, because DOL inrush is momentary; protective devices are selected to ride through the inrush without tripping.
4.2 Three-Phase Relationships and Real, Apparent, and Reactive Power
Quick Summary: Three-phase questions are guaranteed marks in Sections C and D. Fix the √3 relationships (star: ; delta: ), the √3 power formulas, and the power triangle (, ) in memory, and every motor-current, maximum-demand, and cable-sizing calculation in this guide becomes mechanical.
1. Star (Y) and Delta (Δ) Relationships
| Quantity | Star (Y) Connection | Delta (Δ) Connection |
|---|---|---|
| Line vs phase voltage | (400 V = √3 × 230 V) | |
| Line vs phase current | ||
| Typical use | Distribution with neutral (3-phase 4-wire), motor star starting | Motor windings in run mode, balanced 3-wire loads |
Singapore's 400 V / 230 V system is exactly this star relationship: each phase-to-neutral voltage is 230 V, and between any two lines.
2. Single-Phase and Three-Phase Power Formulas
- Single-phase: ; .
- Three-phase (star or delta, using line values):
Sanity check: 45 kVA at 400 V gives — the Electrician licence ceiling expressed in current terms (Chapter 1).
3. Real, Apparent, and Reactive Power — The Power Triangle
- Real (active) power (kW): does useful work (heat, torque, light).
- Reactive power (kVAr): sustains magnetic fields in motors and transformers; oscillates between source and load without doing useful work.
- Apparent power (kVA): the vector sum that the supply and cables must actually carry.
Cables, breakers, and transformers are thermally limited by current, hence by — two loads with equal kW but different power factors draw different currents. This is why the licence scope is defined in kVA, not kW.
4. Worked Motor Calculations (EMA Sample-Question Style)
Question (from EMA's published sample list): for a 3-phase 400 V, 2 kW motor with power factor 0.8, find (a) the running current, (b) the direct-on-line starting current, and (c) whether the cable is sized for starting or running current.
(a) Running current:
(b) DOL starting current: induction motors draw 6–8 × full-load current at standstill (Chapter 3.2):
(c) Cable sizing basis: the cable is sized for the running current (with correction factors), not the starting current — the inrush lasts only seconds, and the protective device is chosen (Type C/D curve or a suitable fuse) to withstand it without tripping. The overload relay, set at (or inside a star-delta loop), protects the motor thermally during run.
Efficiency variant: if the 2 kW is shaft (output) power with efficiency , first convert to input: , then . Read whether the question gives output or input power — EMA long questions mark the distinction.
5. Per-Phase Analysis and Metering
For unbalanced loads, compute each phase separately: per-phase , then sum the three phases. Metering follows the same structure: whole-current kWh meters connect directly for small loads, while CT-operated meters (e.g., 100/5 A) step down larger currents — the SLD must show the arrangement of protective devices before and after the meter (Chapter 6.1).
6. Reverse Calculations and Common Three-Phase Traps
Written-test long questions frequently work backwards from current to power. Example: a balanced 3-phase heater bank draws 20 A per line at unity power factor from 400 V. Its real power is , and its apparent power is (identical because ).
Traps EMA Examiners Exploit
- Forgetting √3 in 3-phase work: using instead of underestimates power by 42%. If an answer looks 1.73× too small, the √3 was dropped.
- Mixing line and phase values in delta loads: a delta motor winding sees the full 400 V, but its winding current is only — the basis of the 0.58 × FLC overload-relay rule (Chapter 3.2).
- Using 230 V with √3: the √3 formulas require the line-to-line voltage (400 V); using 230 V with √3 produces line/phase-confused answers (e.g., 26 kVA instead of 45 kVA).
- kW versus kVA confusion: licence scope, breaker thermal duty, and supply capacity are kVA (current-based); appliance nameplates are usually kW. Convert through before comparing them.
In a star-connected 3-phase 4-wire system, what is the relationship between line voltage and phase voltage?
A 400 V 3-phase motor delivers 2 kW shaft power at 0.8 power factor and 85% efficiency. What is the approximate running line current?
4.25 A
3.61 A
2.89 A
5.42 A
A small installation draws 12 kW at 0.75 power factor from a 400 V 3-phase supply. What apparent power must the intake and main cables carry?
9 kVA
12 kVA
16 kVA
21 kVA
Sections you finish are checked off in the contents.