PracticeVideosBlogFlashcards

4.2 Three-Phase Relationships and Real, Apparent, and Reactive Power

Key Takeaways

  • In a star (Y) system the line voltage is √3 times the phase voltage (400 V / 230 V) while line current equals phase current; in a delta (Δ) system line voltage equals phase voltage while line current is √3 times phase current.

  • Three-phase power formulas: P = √3 × VL × IL × cos φ (kW), Q = √3 × VL × IL × sin φ (kVAr), S = √3 × VL × IL (kVA); single-phase: P = V × I × cos φ.

  • The power triangle links real, reactive, and apparent power: S² = P² + Q², with power factor cos φ = P / S.

  • A 400 V, 2 kW, 3-phase motor at 0.8 power factor draws a running current of 2000 / (√3 × 400 × 0.8) = 3.61 A, and 6–8 times that (≈22–29 A) when started direct-on-line.

  • Cables are sized for running current, not starting current, because DOL inrush is momentary; protective devices are selected to ride through the inrush without tripping.

Last updated: August 2026

4.2 Three-Phase Relationships and Real, Apparent, and Reactive Power

Quick Summary: Three-phase questions are guaranteed marks in Sections C and D. Fix the √3 relationships (star: VL=3 VphV_L = \sqrt{3}\, V_{ph}; delta: IL=3 IphI_L = \sqrt{3}\, I_{ph}), the √3 power formulas, and the power triangle (S2=P2+Q2S^2 = P^2 + Q^2, cos⁡ϕ=P/S\cos\phi = P/S) in memory, and every motor-current, maximum-demand, and cable-sizing calculation in this guide becomes mechanical.


1. Star (Y) and Delta (Δ) Relationships

QuantityStar (Y) ConnectionDelta (Δ) Connection
Line vs phase voltageVL=3 VphV_L = \sqrt{3}\, V_{ph} (400 V = √3 × 230 V)VL=VphV_L = V_{ph}
Line vs phase currentIL=IphI_L = I_{ph}IL=3 IphI_L = \sqrt{3}\, I_{ph}
Typical useDistribution with neutral (3-phase 4-wire), motor star startingMotor windings in run mode, balanced 3-wire loads

Singapore's 400 V / 230 V system is exactly this star relationship: each phase-to-neutral voltage is 230 V, and 3×230=400 V\sqrt{3} \times 230 = 400\text{ V} between any two lines.

2. Single-Phase and Three-Phase Power Formulas

  • Single-phase: P=V×I×cos⁡ϕP = V \times I \times \cos\phi; S=V×IS = V \times I.
  • Three-phase (star or delta, using line values):
P=3×VL×IL×cos⁡ϕS=3×VL×ILIL=P3 VLcos⁡ϕP = \sqrt{3} \times V_L \times I_L \times \cos\phi \qquad S = \sqrt{3} \times V_L \times I_L \qquad I_L = \frac{P}{\sqrt{3}\, V_L \cos\phi}

Sanity check: 45 kVA at 400 V gives IL=45,000/(3×400)=64.95 AI_L = 45{,}000 / (\sqrt{3} \times 400) = 64.95\text{ A} — the Electrician licence ceiling expressed in current terms (Chapter 1).

3. Real, Apparent, and Reactive Power — The Power Triangle

  • Real (active) power PP (kW): does useful work (heat, torque, light).
  • Reactive power QQ (kVAr): sustains magnetic fields in motors and transformers; oscillates between source and load without doing useful work.
  • Apparent power SS (kVA): the vector sum that the supply and cables must actually carry.
S2=P2+Q2cos⁡ϕ=PStan⁡ϕ=QPS^2 = P^2 + Q^2 \qquad \cos\phi = \frac{P}{S} \qquad \tan\phi = \frac{Q}{P}

Cables, breakers, and transformers are thermally limited by current, hence by SS — two loads with equal kW but different power factors draw different currents. This is why the licence scope is defined in kVA, not kW.

4. Worked Motor Calculations (EMA Sample-Question Style)

Question (from EMA's published sample list): for a 3-phase 400 V, 2 kW motor with power factor 0.8, find (a) the running current, (b) the direct-on-line starting current, and (c) whether the cable is sized for starting or running current.

(a) Running current:

Irun=P3×VL×cos⁡ϕ=2,0001.732×400×0.8=2,000554.3=3.61 AI_{run} = \frac{P}{\sqrt{3} \times V_L \times \cos\phi} = \frac{2{,}000}{1.732 \times 400 \times 0.8} = \frac{2{,}000}{554.3} = 3.61\text{ A}

(b) DOL starting current: induction motors draw 6–8 × full-load current at standstill (Chapter 3.2):

Istart≈6×3.61≈21.7 A  to  8×3.61≈28.9 AI_{start} \approx 6 \times 3.61 \approx 21.7\text{ A} \;\text{to}\; 8 \times 3.61 \approx 28.9\text{ A}

(c) Cable sizing basis: the cable is sized for the running current (with correction factors), not the starting current — the inrush lasts only seconds, and the protective device is chosen (Type C/D curve or a suitable fuse) to withstand it without tripping. The overload relay, set at 1.0×IFLC1.0 \times I_{FLC} (or 0.58×IFLC0.58 \times I_{FLC} inside a star-delta loop), protects the motor thermally during run.

Efficiency variant: if the 2 kW is shaft (output) power with efficiency η=0.85\eta = 0.85, first convert to input: Pin=2,000/0.85=2,353 WP_{in} = 2{,}000 / 0.85 = 2{,}353\text{ W}, then Irun=2,353/554.3=4.25 AI_{run} = 2{,}353 / 554.3 = 4.25\text{ A}. Read whether the question gives output or input power — EMA long questions mark the distinction.

5. Per-Phase Analysis and Metering

For unbalanced loads, compute each phase separately: per-phase Pph=Vph×Iph×cos⁡ϕ=230×Iph×cos⁡ϕP_{ph} = V_{ph} \times I_{ph} \times \cos\phi = 230 \times I_{ph} \times \cos\phi, then sum the three phases. Metering follows the same structure: whole-current kWh meters connect directly for small loads, while CT-operated meters (e.g., 100/5 A) step down larger currents — the SLD must show the arrangement of protective devices before and after the meter (Chapter 6.1).

6. Reverse Calculations and Common Three-Phase Traps

Written-test long questions frequently work backwards from current to power. Example: a balanced 3-phase heater bank draws 20 A per line at unity power factor from 400 V. Its real power is P=3×400×20×1.0=13,856 W≈13.9 kWP = \sqrt{3} \times 400 \times 20 \times 1.0 = 13{,}856\text{ W} \approx 13.9\text{ kW}, and its apparent power is S=3×400×20=13.9 kVAS = \sqrt{3} \times 400 \times 20 = 13.9\text{ kVA} (identical because cos⁡ϕ=1\cos\phi = 1).

Traps EMA Examiners Exploit

  1. Forgetting √3 in 3-phase work: using P=VL×ILP = V_L \times I_L instead of 3×VL×IL\sqrt{3} \times V_L \times I_L underestimates power by 42%. If an answer looks 1.73× too small, the √3 was dropped.
  2. Mixing line and phase values in delta loads: a delta motor winding sees the full 400 V, but its winding current is only IL/3I_L/\sqrt{3} — the basis of the 0.58 × FLC overload-relay rule (Chapter 3.2).
  3. Using 230 V with √3: the √3 formulas require the line-to-line voltage (400 V); using 230 V with √3 produces line/phase-confused answers (e.g., 26 kVA instead of 45 kVA).
  4. kW versus kVA confusion: licence scope, breaker thermal duty, and supply capacity are kVA (current-based); appliance nameplates are usually kW. Convert through cos⁡ϕ\cos\phi before comparing them.
Test Your Knowledge

In a star-connected 3-phase 4-wire system, what is the relationship between line voltage and phase voltage?

A

VL=VphV_L = V_{ph}

B

VL=3×VphV_L = \sqrt{3} \times V_{ph}

C

VL=3×VphV_L = 3 \times V_{ph}

D

VL=Vph/3V_L = V_{ph} / \sqrt{3}

Test Your Knowledge

A 400 V 3-phase motor delivers 2 kW shaft power at 0.8 power factor and 85% efficiency. What is the approximate running line current?

A

4.25 A

B

3.61 A

C

2.89 A

D

5.42 A

Test Your Knowledge

A small installation draws 12 kW at 0.75 power factor from a 400 V 3-phase supply. What apparent power must the intake and main cables carry?

A

9 kVA

B

12 kVA

C

16 kVA

D

21 kVA

Sections you finish are checked off in the contents.