15.2 Transformer Connections & Special Transformers
Key Takeaways
- Standard three-phase transformer connections (Y-Y, Y-Δ, Δ-Y, Δ-Δ) establish fundamental voltage and current relationships, with Y-Δ and Δ-Y configurations producing a 30° phase shift between HV and LV line voltages.
- The Open-Delta (V-V) connection utilizes two single-phase transformers to deliver three-phase power at 57.7% of the capacity of a full Δ-Δ bank (1.732 S₁) with an active utility capability factor of 86.6%.
- Scott-T (T-T) connections transform three-phase power into two-phase power (or vice versa) using a main transformer tapped at 50% and a teaser transformer tapped at (√3)/2 ≈ 86.6% of full winding turn count.
- Autotransformers transfer power via both inductive and conductive mechanisms, providing higher efficiency, smaller physical footprint, and lower percentage impedance according to S_auto = S_two-winding / (1 - K).
- Grounding transformers, such as zig-zag (interconnected star) units, create a stable artificial neutral point on ungrounded 3-wire systems to facilitate zero-sequence fault current return paths for protective relaying.
15.2 Transformer Connections & Special Transformers
Standard Three-Phase Bank Configurations
Three-phase power transformation can be accomplished using either a single 3-phase transformer unit or three identical single-phase transformers connected in a 3-phase bank. The four primary three-phase winding configurations are Star-Star (Y-Y), Delta-Delta ($\Delta$-$\Delta$), Star-Delta (Y-$\Delta$), and Delta-Star ($\Delta$-Y).
THREE-PHASE WINDING CONNECTIONS & LINE/PHASE RELATIONS
STAR (Y) CONNECTION DELTA (Δ) CONNECTION
Phase A Phase A
│ ┌─┐
█ Winding ███│ Winding
│ ███│
Neutral├──────┐ Phase B│ └─┐Phase C
│ │ ┌─────┼───┼─────┐
█ █ │ ███ │ ███
│ │ │ ███ │ ███
Phase B Phase C └─────┼───┘ │
└─────────┘
V_Line = √3 · V_Phase V_Line = V_Phase
I_Line = I_Phase I_Line = √3 · I_Phase
Summary of Voltage, Current & Phase Relationships
| Winding Connection | Line-to-Phase Voltage | Line-to-Phase Current | Neutral Availability | Primary/Secondary Phase Shift |
|---|---|---|---|---|
| Star-Star (Y-Y) | $V_L = \sqrt{3} V_P$ | $I_L = I_P$ | Yes (4-wire system) | $0^\circ$ (or $180^\circ$) |
| Delta-Delta ($\Delta$-$\Delta$) | $V_L = V_P$ | $I_L = \sqrt{3} I_P$ | No (3-wire system) | $0^\circ$ (or $180^\circ$) |
| Star-Delta (Y-$\Delta$) | $V_{L1} = \sqrt{3} V_{P1}, V_{L2} = V_{P2}$ | $I_{L1} = I_{P1}, I_{L2} = \sqrt{3} I_{P2}$ | Primary side only | $\pm 30^\circ$ phase shift |
| Delta-Star ($\Delta$-Y) | $V_{L1} = V_{P1}, V_{L2} = \sqrt{3} V_{P2}$ | $I_{L1} = \sqrt{3} I_{P1}, I_{L2} = I_{P2}$ | Secondary side only | $\pm 30^\circ$ phase shift |
Technical Features of Bank Configurations
- Star-Star (Y-Y):
- Requires minimum insulation per phase ($V_P = V_L / \sqrt{3}$), making it economical for extra-high voltage (EHV) systems.
- Disadvantage: Oscillating neutral phenomenon and severe 3rd harmonic voltage distortion under unbalanced loads unless neutrals are grounded or a tertiary delta winding is added.
- Delta-Delta ($\Delta$-$\Delta$):
- Excellent for high-current, lower-voltage applications. Traps 3rd harmonic currents within the closed delta loop, preventing voltage distortion.
- Can continue operating at reduced capacity in Open-Delta (V-V) if one single-phase unit breaks down.
- Star-Delta (Y-$\Delta$):
- Standard choice for step-down high-voltage transmission substations. The primary Y neutral can be grounded to stabilize line voltages against lightning surges.
- Delta-Star ($\Delta$-Y):
- Standard choice for step-up generation substations and commercial distribution systems ($400/230\text{ V}$ or $480/277\text{ V}$). The secondary Y neutral provides a 4-wire service to supply both 3-phase motor loads and single-phase lighting/receptacle loads.
Vector Groups & Standard $30^\circ$ Phase Shift
According to IEEE/ANSI standards, in Y-$\Delta$ and $\Delta$-Y transformers, high-voltage line voltage leads low-voltage line voltage by $30^\circ$ for positive phase sequence ($A-B-C$). In European IEC notation, vector groups such as Dy11 ($30^\circ$ lead) and Dy1 ($30^\circ$ lag) designate phase displacements on a 12-hour clock dial ($11 \times 30^\circ = 330^\circ \equiv +30^\circ$).
Open-Delta (V-V) Connection Analysis
When one single-phase transformer in a 3-phase $\Delta$-$\Delta$ bank is removed due to failure or maintenance, the remaining two single-phase transformers can continue delivering balanced 3-phase power in an Open-Delta (V-V) connection.
OPEN-DELTA (V-V) TRANSFORMER BANK TOPOLOGY
Phase A ───────────────┐
│
──┴──
T1 │ │ Primary Winding
──┬──
Phase B ───────────────┼───┐
│ │
──┴── │
T2 │ │ Primary Winding
──┬── │
Phase C ───────────────┴───┘ (Third transformer T3 removed!)
Derivation of V-V Bank Rating & Utility Factor
Let $S_1 = V_P I_P$ be the kVA rating of one single-phase transformer. In a full $\Delta$-$\Delta$ bank of three units, the total capacity is:
In the Open-Delta (V-V) bank, line current $I_L$ cannot exceed the rated phase current $I_P$ of an individual transformer winding ($I_L = I_P$). The total 3-phase apparent power delivered by the two transformers is:
1. Open-Delta Bank Capacity Ratio:
The Open-Delta bank delivers 57.7% of the full 3-phase $\Delta$-$\Delta$ rating.
2. Utility Capability Factor (Operating Efficiency of Installed Units):
The two installed transformers can only be loaded up to 86.6% of their combined rating ($2 S_1$) without thermal overload.
Transformer Power Factor in V-V Bank
When an Open-Delta bank supplies a balanced 3-phase load operating at power factor $\cos \phi$, the individual phase currents in the two transformers are shifted by $30^\circ$ relative to their phase voltages. Consequently, the operating power factors of the two individual transformers are unequal:
- Even if the load operates at unity power factor ($\cos \phi = 1.0$), both transformers operate at $\cos 30^\circ = 0.866$ power factor (one leading, one lagging).
- If the load power factor drops to $0.50$ lagging ($\phi = 60^\circ$), transformer T2 operates at $\cos(60^\circ + 30^\circ) = \cos 90^\circ = 0$ power factor, delivering zero active power while transformer T1 supplies the entire active load power!
Scott-T (T-T) Winding Connection
The Scott-T (or T-T) connection converts a 3-phase system into a 2-phase system (or vice versa) using two special single-phase transformers: the Main Transformer and the Teaser Transformer.
SCOTT-T (T-T) TRANSFORMER VECTOR SCHEMATIC
Phase A (Apex)
│
│ Teaser Transformer (Tapped at 86.6% = √3/2)
│
▼
Phase B ───────█████─────── Phase C
▲ ▲
└───── 50% Tap ─────┘
Main Transformer
Winding Specifications & Vector Derivations
- Main Transformer: Connected across lines B and C of the 3-phase system ($V_{BC} = V_L$). The primary winding has $N_p$ turns and features a precise 50% center tap.
- Teaser Transformer: Connected between line phase A and the 50% center tap of the main transformer.
From the 3-phase equilateral voltage triangle, the altitude from phase A to the midpoint of line B-C is:
To achieve equal primary voltage per turn and balanced orthogonal two-phase secondary voltages ($90^\circ$ phase shift), the primary winding of the teaser transformer must be tapped at $\frac{\sqrt{3}}{2} \approx 86.6%$ of total main turns ($N_{\text{teaser}} = 0.866 N_p$).
Autotransformers: Conductive vs. Inductive Power Transfer
An autotransformer is a single-winding transformer in which a portion of the same continuous winding is common to both the high-voltage (HV) and low-voltage (LV) circuits.
AUTOTRANSFORMER VOLTAGE AND CURRENT FLOW
I_H ───► ┌───────────┐ Common Winding Portion
V_H (Input) │ Primary │ (Series Winding N_se)
└─────┬─────┘
──────────────────────────────┼───────────► I_L (Output)
│
┌─────┴─────┐ Common Winding (N_c)
│ Secondary │ Current = I_L - I_H
└─────┬─────┘
──────────────────────────────┴───────────► Neutral
Transformation Ratio ($K$)
Let $V_H$ be the higher terminal voltage and $V_L$ be the lower terminal voltage. The autotransformer ratio is defined as:
Apparent Power Capacity Advantage
When a standard two-winding transformer of rating $S_{\text{two-winding}}$ is reconnected as an autotransformer, its effective output kVA capacity increases dramatically according to:
Division of Transferred Power
Power transferred from primary to secondary side in an autotransformer occurs via two distinct physical mechanisms:
- Inductively Transferred Power ($P_{\text{ind}}$) (via magnetic flux coupling through core):
- Conductively Transferred Power ($P_{\text{cond}}$) (via direct electrical connection):
Quantitative Advantages & Isolation Hazard
- Copper Saving: $\frac{\text{Weight of copper in auto}}{\text{Weight of copper in 2-winding}} = 1 - K$.
- Higher Efficiency: Internal $I^2 R$ losses decrease because only a fraction $(1-K)$ of power is transformed inductively.
- Lower Percentage Impedance: Results in superior voltage regulation, but increases available short-circuit fault current ($I_{\text{sc}} = I_{\text{rated}} / Z_{\text{pu}}$).
- FATAL ISOLATION HAZARD: Primary and secondary circuits are electrically tied together. A break in the common winding exposes low-voltage load equipment to full high-voltage potentials, requiring solid neutral grounding.
Voltage Tap Changers
To compensate for line voltage drops caused by varying load currents along power distribution feeders, transformers are equipped with tap changers on their high-voltage windings (where current is lower, minimizing arc erosion).
- No-Load Tap Changers (NLTC / Off-Circuit Tap Changers): Tap setting can only be manually adjusted while the transformer is completely de-energized. Typically provides $\pm 2.5%$ and $\pm 5.0%$ voltage adjustments.
- On-Load Tap Changers (OLTC): Adjusts tap positions dynamically while carrying full load current. Employs selector switches and diverter switches with transition resistors or reactors to prevent breaking load current or short-circuiting adjacent tap turns during tap transitions.
Grounding Transformers (Zig-Zag Connection)
Utility distribution systems fed by $\Delta$-connected transformer secondaries lack a physical neutral conductor. To establish a stable neutral point on an ungrounded 3-phase 3-wire network, a Grounding Transformer is installed.
ZIG-ZAG (INTERCONNECTED STAR) GROUNDING TRANSFORMER
Phase A Phase B Phase C
│ │ │
███ a1 ███ b1 ███ c1
│ │ │
███ c2 ███ a2 ███ b2
└───────────────────┼───────────────────┘
│
▼ Ground Neutral (N)
Operating Principle of Zig-Zag (Interconnected Star) Winding
- Each phase limb contains two equal winding sections wound in opposite directions on different core limbs ($a_1, c_2; b_1, a_2; c_1, b_2$).
- Normal Balanced Conditions (Positive/Negative Sequence): Equal opposing currents in each limb cancel magnetizing flux, presenting extremely high magnetizing impedance and drawing negligible no-load current.
- Ground Fault Conditions (Zero Sequence $I_0$): Zero-sequence fault currents flow in phase through all three lines simultaneously. The opposing winding arrangement allows zero-sequence current to pass through with very low impedance, providing a safe path to ground and enabling protective relays to clear phase-to-ground faults.
Two identical 50 kVA single-phase transformers are connected in an Open-Delta (V-V) bank to supply a balanced three-phase load. What is the maximum continuous 3-phase kVA capacity that this V-V bank can deliver without thermal overloading?
A standard 100 kVA, 2000/200 V two-winding distribution transformer is reconnected as a step-up autotransformer to step up voltage from 2000 V to 2200 V. What is the maximum kVA output rating of the resulting autotransformer connection?
In a Scott-T (T-T) transformer bank used to convert a balanced 3-phase power supply into a 2-phase system, at what precise percentage turn tap must the teaser transformer primary winding be tapped relative to the main transformer?