19.2 Symmetrical Components & Unbalanced Fault Analysis
Key Takeaways
Any set of three unbalanced phasors resolves into positive-, negative- and zero-sequence sets, with Va0 = (Va + Vb + Vc)/3 and the operator a = 1∠120°.
A three-phase balanced fault uses the positive-sequence network only; single line-to-ground connects all three sequence networks in series and gives Ia1 = Ea/(Z1 + Z2 + Z0).
Line-to-line faults connect positive and negative sequence networks in parallel with no zero-sequence involvement, so LL fault current is about 86.6% of the three-phase value.
Zero-sequence current requires a return path: a delta winding traps it and an ungrounded wye blocks it entirely, which is why transformer connection determines ground-fault current.
Faults ranked by typical frequency of occurrence are single line-to-ground (about 70–80%), line-to-line, double line-to-ground, then three-phase (about 5%), which is nevertheless usually the most severe.
19.2 Symmetrical Components & Unbalanced Fault Analysis
Balanced three-phase faults are the easy case and account for only about 5% of real faults. The remaining 95% are unbalanced, and the only practical way to analyse them by hand is Fortescue's method of symmetrical components, a core component of Enhanced TOS topic K, Power System Analysis (PRBEE Resolution No. 40, s. 2024 — 9.00% of the examination, 20 of the 100 Electrical Engineering items).
1. The Symmetrical Component Transformation
Any three unbalanced phasors decompose into three balanced sets:
- Positive sequence (1) — three equal phasors 120° apart in the normal rotation ––; this is the only set present in a healthy balanced system;
- Negative sequence (2) — three equal phasors 120° apart in the reversed rotation ––; it produces a counter-rotating field that heats generator rotors, which is why negative-sequence relays exist;
- Zero sequence (0) — three equal phasors in phase; it can flow only where a neutral or ground return path exists.
The operator satisfies
Synthesis (components to phase quantities):
Analysis (phase quantities to components):
Two consequences are examined repeatedly:
- In a three-wire system (no neutral), , so zero-sequence current is zero by definition;
- In a four-wire system the neutral carries — the neutral current is three times the zero-sequence current, not equal to it.
2. Sequence Networks
Each sequence has its own network with its own impedance.
| Element | |||
|---|---|---|---|
| Synchronous generator | Smallest; typically – | ||
| Transformer | , but path depends on winding connection | ||
| Transmission line | – (ground return path) |
For static equipment — lines, cables, transformers — always, because a static device cannot tell the direction of phase rotation. For rotating machines in general, though is the usual working assumption.
Zero-sequence line impedance is substantially higher than positive sequence because the return path is the earth and any overhead ground wires, enclosing a much larger flux loop.
Transformer Zero-Sequence Connection Rules
This table is the single most examinable item in the topic:
| Connection | Zero-sequence path |
|---|---|
| Grounded wye – grounded wye | Continuous through the transformer |
| Grounded wye – delta | Flows on the wye side, circulates and is trapped in the delta; does not pass through |
| Delta – delta | Blocked on both sides; no external zero-sequence path |
| Ungrounded wye – anything | Blocked; no zero-sequence current at all |
| Grounded wye – delta (as grounding bank) | Provides a deliberate zero-sequence source for ground-fault detection |
A delta winding is a zero-sequence trap: it gives circulating third-harmonic and zero-sequence currents somewhere to go, which is why a delta tertiary is added to large wye-wye autotransformers.
3. Fault Types and Sequence Network Interconnection
| Fault type | Network connection | Fault current expression |
|---|---|---|
| Three-phase (balanced) | Positive sequence only | |
| Single line-to-ground (SLG) | , , in series | , |
| Line-to-line (LL) | , in parallel; no zero sequence | , |
| Double line-to-ground (DLG) | in series with | |
| Open conductor | Series (rather than shunt) network connection | Produces negative-sequence current without high fault current |
Fault-current arithmetic worth memorising: with , the line-to-line fault current is
so an LL fault is always about 86.6% of the three-phase value. A single line-to-ground fault can exceed the three-phase value when , which happens on solidly grounded systems close to a grounded-wye transformer — a genuine engineering result and a favourite examination trap for candidates who assume the three-phase fault is always the worst case.
Faults ranked by frequency of occurrence: SLG 70–80%, LL about 15%, DLG about 10%, and three-phase only about 5%.
4. System Grounding
| Grounding method | Ground-fault current | Transient overvoltage | Typical application |
|---|---|---|---|
| Solidly grounded | Very high | Low | LV distribution, most utility MV |
| Low-resistance grounded | Limited to 100–1000 A | Moderate | Industrial MV systems |
| High-resistance grounded | Limited to about 5–10 A | Moderate | Continuous-process plants |
| Ungrounded | Capacitive only | High (arcing ground fault) | Legacy systems; increasingly avoided |
Neutral grounding impedance appears in the zero-sequence network as — three times, because the total zero-sequence current flows through it. Forgetting the factor of three is the standard error in grounded-neutral fault problems.
Solved Board Exam Examples
Example 1: Resolving Unbalanced Line Currents
A four-wire feeder carries A, A and A. Find the zero-sequence current and the neutral current.
Solution.
Converting to rectangular form: ; ; .
The neutral carries three times this value:
Had the feeder been three-wire with no neutral or ground return, would be forced to zero and no zero-sequence component could exist at all — a useful sanity check on any set of measured currents.
Example 2: Single Line-to-Ground Fault Current
At a bus, pu, pu and pu on a 100 MVA, 13.8 kV base. Find the SLG fault current in amperes and compare it with the three-phase fault.
Solution. For an SLG fault the sequence networks are in series:
The three-phase fault gives pu kA. Because , the ground fault is 28% more severe than the three-phase fault — precisely the case that defeats the "three-phase is always worst" assumption.
Example 3: Line-to-Line Fault Ratio
For a machine with pu, find the ratio of line-to-line fault current to three-phase fault current.
Solution.
For the LL fault, pu, and the faulted phase current is
This √3/2 ratio holds whenever , independent of the actual impedance values.
In a four-wire grounded system, what is the relationship between the neutral current and the zero-sequence current of phase a?
The neutral current equals the zero-sequence current
The neutral current equals three times the zero-sequence current
The neutral current equals one third of the zero-sequence current
The neutral current equals √3 times the zero-sequence current
A grounded-wye to delta transformer feeds a load. What happens to zero-sequence current that flows in the grounded-wye winding?
It passes directly through to the delta side
It circulates within the delta winding and does not appear in the delta-side lines
It is blocked entirely and cannot flow in the wye winding either
It is transformed into negative-sequence current on the delta side
At a particular bus Z1 = Z2 = j0.10 pu and Z0 = j0.30 pu. How does the single line-to-ground fault current compare with the three-phase fault current?
The ground fault current is larger because three sequence currents add
The ground fault current is smaller because the total series impedance is larger
They are exactly equal because Z1 appears in both calculations
The ground fault current is 86.6% of the three-phase value
Sections you finish are checked off in the contents.