PracticeVideosBlogFlashcards

20.2 Industrial Motor Control, Logic Circuits & PLC Automation

Key Takeaways

  • Reduced-voltage starting methods restrict induction motor inrush currents during acceleration: Wye-Delta (Y–Δ\text{Y}\text{--}\Delta) starting reduces line current and starting torque to 13\frac{1}{3} (33.3%33.3\%) of Direct-On-Line (DOL) values (Istart, Y=13Istart, ΔI_{\text{start, Y}} = \frac{1}{3} I_{\text{start, }\Delta}, Tstart, Y=13Tstart, ΔT_{\text{start, Y}} = \frac{1}{3} T_{\text{start, }\Delta}).

  • Autotransformer starters (Korndorfer method) utilize voltage taps xx (50%50\%, 65%65\%, or 80%80\%), reducing motor voltage to xVLx V_L, motor starting current to xIDOLx I_{\text{DOL}}, starting torque to x2TDOLx^2 T_{\text{DOL}}, and line starting current to x2IDOLx^2 I_{\text{DOL}}.

  • Variable Frequency Drives (VFDs) control AC motor rotational speed (Ns=120fPN_s = \frac{120 f}{P}) by maintaining a constant Volts-per-Hertz ratio (V/f=constantV/f = \text{constant}) below base frequency, limiting inrush current to 100%–150%100\%\text{--}150\% of rated current while developing full rated torque.

  • Industrial hardwired motor control circuits deploy Start/Stop pushbuttons, seal-in holding contacts, series Thermal Overload Relay (TOR) normally closed contacts, and electrical/mechanical interlocking to prevent simultaneous energization of opposing contactors.

  • Programmable Logic Controllers (PLCs) execute a cyclic 4-stage scan sequence: Input Scan (reading physical sensor inputs into memory), Logic Execution Scan (evaluating Ladder Diagram or Function Block program logic), Output Scan (updating output modules), and System Diagnostics/Overhead.

Last updated: August 2026

20.2 Industrial Motor Control, Logic Circuits & PLC Automation

Industrial motor control systems, magnetic contactors, reduced-voltage starting topologies, and Programmable Logic Controllers (PLCs) form vital practical components of the PRC Registered Electrical Engineer (REE) Licensure Examination. Three-phase induction motors drive the vast majority of industrial loads (pumps, compressors, conveyors, fans). Electrical engineers must design control circuits that safely start, stop, reverse, speed-control, and protect electric motors while complying with Philippine Electrical Code (PEC) guidelines.


1. Industrial Motor Starting Techniques & Performance Comparisons

Direct-On-Line (DOL) starting of large 3-phase induction motors causes massive inrush current (500% to 800%500\% \text{ to } 800\% of full-load current), creating severe line voltage dips that disturb neighboring facility loads. Reduced-voltage starting limits starting current to acceptable utility limits.

Comparison of Motor Starting Methods

Starting MethodMotor Terminal Voltage (VmV_m)Motor Starting Current (ImI_m)Line Starting Current (IlineI_{\text{line}})Starting Torque (TstartT_{\text{start}})Key Applications & Characteristics
Direct-On-Line (DOL)100% (VL)100\% \ (V_L)100% (IDOL)100\% \ (I_{\text{DOL}})100% (IDOL)100\% \ (I_{\text{DOL}})100% (TDOL)100\% \ (T_{\text{DOL}})Small motors (<7.5 kW/10 HP< 7.5\ \text{kW} / 10\ \text{HP}). Simple, maximum starting torque, high current surge.
Wye-Delta (Y–Δ\text{Y}\text{--}\Delta)57.7% (VL3)57.7\% \ \left(\frac{V_L}{\sqrt{3}}\right)33.3% (IDOL3)33.3\% \ \left(\frac{I_{\text{DOL}}}{3}\right)33.3% (IDOL3)33.3\% \ \left(\frac{I_{\text{DOL}}}{3}\right)33.3% (TDOL3)33.3\% \ \left(\frac{T_{\text{DOL}}}{3}\right)Motors started under light/no-load conditions. Requires 6-terminal motor; low cost.
Autotransformer (Korndorfer)x⋅VLx \cdot V_L (x=0.50,0.65,0.80x = 0.50, 0.65, 0.80)x⋅IDOLx \cdot I_{\text{DOL}}x2⋅IDOLx^2 \cdot I_{\text{DOL}}x2⋅TDOLx^2 \cdot T_{\text{DOL}}Large high-inertia industrial drives. Smooth acceleration, Korndorfer transition eliminates current spike.
Primary Resistorx⋅VLx \cdot V_L (x<1.0x < 1.0)x⋅IDOLx \cdot I_{\text{DOL}}x⋅IDOLx \cdot I_{\text{DOL}}x2⋅TDOLx^2 \cdot T_{\text{DOL}}Smooth acceleration; power dissipated as heat in series resistors.
Soft Starter (SCR)Ramped VmV_m (0 to VL0 \text{ to } V_L)200% to 350%200\% \text{ to } 350\% rated200% to 350%200\% \text{ to } 350\% ratedAdjustable rampSolid-state voltage ramping via antiparallel SCRs. Eliminates mechanical shock.
Variable Frequency Drive (VFD)Variable VV (V/f=constV/f = \text{const})100% to 150%100\% \text{ to } 150\% rated100% to 150%100\% \text{ to } 150\% rated100% to 150%100\% \text{ to } 150\% ratedFull speed and torque control. Maximum efficiency, zero line surge.

Mathematical Formulations

Wye-Delta ( Y–Δ\,\text{Y}\text{--}\Delta) Starting:

When connected in Delta (run mode), phase voltage equals line voltage (Vphase,Δ=VLV_{\text{phase},\Delta} = V_L) and line current is Iline,Δ=3Iphase,Δ=3VLZstI_{\text{line},\Delta} = \sqrt{3} I_{\text{phase},\Delta} = \frac{\sqrt{3} V_L}{Z_{\text{st}}}. During Wye starting, phase voltage is Vphase,Y=VL3V_{\text{phase},Y} = \frac{V_L}{\sqrt{3}}, so phase current is Iphase,Y=VL3ZstI_{\text{phase},Y} = \frac{V_L}{\sqrt{3} Z_{\text{st}}}. Line current equals phase current:

Iline,Y=VL3Zst=13(3VLZst)=13Iline,ΔI_{\text{line},Y} = \frac{V_L}{\sqrt{3} Z_{\text{st}}} = \frac{1}{3} \left( \frac{\sqrt{3} V_L}{Z_{\text{st}}} \right) = \frac{1}{3} I_{\text{line},\Delta} Starting Torque: Tstart∝Vphase2  ⟹  Tstart,Y=(13)2Tstart,Δ=13Tstart,Δ\text{Starting Torque: } T_{\text{start}} \propto V_{\text{phase}}^2 \implies T_{\text{start},Y} = \left( \frac{1}{\sqrt{3}} \right)^2 T_{\text{start},\Delta} = \frac{1}{3} T_{\text{start},\Delta}

Autotransformer (Korndorfer) Starting:

For an autotransformer tap ratio xx (where x=0.50,0.65,0.80x = 0.50, 0.65, 0.80):

  • Motor terminal voltage: Vm=xVLV_m = x V_L
  • Motor starting current: Im=xIDOLI_m = x I_{\text{DOL}}
  • Transformer primary line current (by power equality VLIline=VmImV_L I_{\text{line}} = V_m I_m): Iline=x(VmVL)IDOL=x2IDOLI_{\text{line}} = x \left( \frac{V_m}{V_L} \right) I_{\text{DOL}} = x^2 I_{\text{DOL}}
  • Motor starting torque: Tstart=x2TDOLT_{\text{start}} = x^2 T_{\text{DOL}}

2. Hardwired Relay Logic & Motor Control Circuits

Elementary ladder diagrams represent control circuits using standard IEEE/NEMA symbols.

Standard Forward-Reverse Motor Starter Circuit

                  FORWARD / REVERSE MOTOR CONTROL LADDER DIAGRAM

   L1 |---[ STOP ]---+-+---[ F-START ]---+---[ R-NC ]---( F COIL )---+---[ TOR ]---| N
      |              | |                 |                            |
      |              | +---[ F-NO  ]-----+                            |
      |              |                                                |
      |              +-----[ R-START ]---+---[ F-NC ]---( R COIL )----+
      |                |                 |
      |                +---[ R-NO  ]-----+

Essential Control Elements:

  1. Stop Pushbutton: Normally Closed (NC) contact connected in series with the entire control circuit.
  2. Start Pushbutton: Normally Open (NO) momentary contact.
  3. Holding (Seal-In) Contact: NO auxiliary contact of contactor (F-NOF\text{-NO} or R-NOR\text{-NO}) connected in parallel across the Start button to maintain coil energization after button release.
  4. Electrical Interlocking: NC contact of Forward contactor (F-NCF\text{-NC}) wired in series with Reverse coil (RR), and vice versa. Prevents shorting two line phases if both pushbuttons are pressed simultaneously.
  5. Thermal Overload Relay (TOR): NC contact (95–9695\text{--}96) placed in series with contactor coils. Opens automatically when sustained motor overcurrent causes bimetallic strip bending.

3. Programmable Logic Controllers (PLCs)

A Programmable Logic Controller (PLC) is a ruggedized industrial digital computer that continuously monitors input signals from sensors/switches, executes a stored control program, and actuates output devices (contactors, solenoids, indicator lamps).

PLC Hardware Architecture

  • CPU (Central Processing Unit): Microprocessor executing system firmware and user ladder logic.
  • Input Module: Converts field AC/DC signals (24 V DC,120 V AC24\ \text{V DC}, 120\ \text{V AC}) into internal logic voltages using optocouplers for electrical noise isolation.
  • Output Module: Drives field loads via relays, triacs, or solid-state transistors.
  • Power Supply: Converts plant AC voltage into regulated 24 V DC24\ \text{V DC} bus power.

The Four-Stage PLC Scan Cycle

                             PLC SCAN CYCLE REPEAT LOOP

       +-------------------------------------------------------------------+
       |                                                                   |
       v                                                                   |
  +----------+         +---------------+         +-----------+       +-----------+
  | 1. Input | ------> | 2. Logic Exec | ------> | 3. Output | ----> | 4. System |
  |   Scan   |         |   (Program)   |         |   Scan    |       | Overhead  |
  +----------+         +---------------+         +-----------+       +-----------+
  1. Input Scan: CPU reads state of physical input terminals and updates the Input Image Table memory.
  2. Logic Execution Scan: CPU executes ladder rungs sequentially from top to bottom, evaluating conditions using Input Image Table values and updating the Output Image Table.
  3. Output Scan: CPU writes Output Image Table states simultaneously to physical output module terminals.
  4. System Diagnostics / Overhead: Performs self-testing, communication servicing, and watchdog timer reset.

PLC Scan Time (TscanT_{\text{scan}}): Total duration required to complete one full cycle (typically 1 to 20 milliseconds1 \text{ to } 20\ \text{milliseconds}). High-speed events occurring faster than TscanT_{\text{scan}} require hardware interrupt inputs.

IEC 61131-3 Programming Languages

  • Ladder Diagram (LD): Graphical language mimicking hardwired relay logic rungs.
  • Function Block Diagram (FBD): Graphical blocks representing logic functions (AND, OR, TON, PID).
  • Structured Text (ST): High-level block-structured text language (similar to Pascal/C).
  • Instruction List (IL): Low-level assembly-like language.
  • Sequential Function Chart (SFC): Flowchart-based state machine programming.

Standard PLC Timers & Counters

  • Timer On-Delay (TON): Output turns ON after input rung remains continuous for Preset Time (PTPT).
  • Timer Off-Delay (TOF): Output turns OFF after input rung goes false for Preset Time (PTPT).
  • Retentive Timer (RTO): Retains accumulated time (ACCACC) even if input rung turns false; requires explicit Reset (RSTRST) instruction.
  • Count Up (CTU) / Count Down (CTD): Increments/decrements accumulated count on false-to-true rung transitions.

Solved Board Exam Examples

Example 1: Wye-Delta Starter Currents & Torque Calculation

Problem: A 33-phase, 460 V460\ \text{V}, 60 Hz60\ \text{Hz}, 50 HP50\ \text{HP} squirrel-cage induction motor has a rated full-load current of 65 A65\ \text{A} and a Direct-On-Line (DOL) starting current of 420 A420\ \text{A} with a starting torque of 280 N⋅m280\ \text{N}\cdot\text{m}. Calculate: (a) Line starting current under Wye-Delta starting, (b) Motor starting torque under Wye-Delta starting, and (c) Percentage reduction in starting line current compared to DOL.

Solution:

  1. Calculate line starting current under Wye-Delta starting (Istart, YI_{\text{start, Y}}): Istart, Y=13IDOL=420 A3=140.0 AI_{\text{start, Y}} = \frac{1}{3} I_{\text{DOL}} = \frac{420\ \text{A}}{3} = 140.0\ \text{A}
  2. Calculate motor starting torque under Wye-Delta starting (Tstart, YT_{\text{start, Y}}): Tstart, Y=13TDOL=280 N⋅m3=93.33 N⋅mT_{\text{start, Y}} = \frac{1}{3} T_{\text{DOL}} = \frac{280\ \text{N}\cdot\text{m}}{3} = 93.33\ \text{N}\cdot\text{m}
  3. Calculate percentage reduction in line current: %Reduction=(1−13)×100%=66.67%\% \text{Reduction} = \left( 1 - \frac{1}{3} \right) \times 100\% = 66.67\%

Example 2: Autotransformer Starter Tap Calculation

Problem: A 2300 V2300\ \text{V}, 33-phase induction motor draws a DOL starting current of 1,200 A1,200\ \text{A} from the line. The facility distribution system limits starting line current to a maximum of 500 A500\ \text{A}. Determine: (a) The maximum allowable autotransformer voltage tap xx, and (b) The resulting starting torque as a percentage of DOL starting torque.

Solution:

  1. Use autotransformer line current equation (Iline=x2IDOLI_{\text{line}} = x^2 I_{\text{DOL}}): x2IDOL≤500 A  ⟹  x2(1200)=500x^2 I_{\text{DOL}} \le 500\ \text{A} \implies x^2 (1200) = 500 x2=5001200=0.41667  ⟹  x=0.41667=0.6455(64.55%x^2 = \frac{500}{1200} = 0.41667 \implies x = \sqrt{0.41667} = 0.6455 \quad (64.55\%
  2. Select nearest standard lower autotransformer tap: xstandard=0.65(65% tap yields Iline=(0.65)2×1200=507 A)x_{\text{standard}} = 0.65 \quad (65\%\text{ tap yields } I_{\text{line}} = (0.65)^2 \times 1200 = 507\ \text{A}) To strictly respect the 500 A500\ \text{A} limit, select the 50%50\% tap (x=0.50x = 0.50): Iline, 50%=(0.50)2×1200=300 AI_{\text{line, 50\%}} = (0.50)^2 \times 1200 = 300\ \text{A}
  3. Calculate starting torque percentage for 50%50\% tap: Tstart=x2TDOL=(0.50)2TDOL=0.25TDOL(25.0% of DOL torque)T_{\text{start}} = x^2 T_{\text{DOL}} = (0.50)^2 T_{\text{DOL}} = 0.25 T_{\text{DOL}} \quad (25.0\%\text{ of DOL torque})
Loading diagram...
Industrial Motor Starting Topology & PLC Automation Scan Workflow
Motor Line Starting Current (% FLC) and Starting Torque (% FLT) Across Starting Methods
Test Your Knowledge

A 3-phase, 460 V induction motor has a Direct-On-Line starting current of 360 A. If a Wye-Delta starter is installed, what is the line current drawn from the supply during starting?

A

180 A

B

208 A

C

240 A

D

120 A

Test Your Knowledge

An autotransformer motor starter operates on the 65% voltage tap. What starting torque will the motor develop compared to its full-voltage DOL starting torque?

A

42.25%

B

33.3%

C

50.0%

D

65.0%

Test Your Knowledge

In a PLC ladder logic control program, what is the purpose of placing a normally open auxiliary contact of a contactor coil in parallel with a momentary Start pushbutton?

A

To provide electrical interlocking against opposing contactors

B

To provide holding (seal-in) logic that maintains coil power after releasing the button

C

To sense thermal overload fault conditions

D

To delay contactor energization by one scan cycle

Sections you finish are checked off in the contents.