12.2 Vertical Conductors, Downspouts & Horizontal Storm Drains

Key Takeaways

  • Vertical conductors and leaders are sized for maximum projected roof area from IPC Table 1106.2; horizontal storm drains, storm sewers and their horizontal branches are sized from Table 1106.3 by slope; semicircular roof gutters are sized from Table 1106.6.
  • IPC Section 1103.1 requires leaders and storm drains connected to a combined sewer to be trapped, either with an individual trap on each conductor branch or a single trap in the main storm drain just before its connection to the combined building sewer or public sewer.
  • IPC Section 1101.3 prohibits draining storm water into sewers intended for sewage only, and Section 1101.8 requires cleanouts in the storm drainage system complying with the sanitary drainage cleanout provisions, with an exception for subsurface drainage systems.
  • IPC Section 1109.1 converts continuous or semicontinuous discharge into equivalent roof area at 96 square feet per gallon per minute, based on a rainfall rate of 1 inch per hour.
  • Increasing horizontal storm drain slope from 1/8 inch per foot to 1/4 inch per foot raises the allowable projected roof area by roughly 41 percent in Table 1106.3.
Last updated: September 2026

12.2 Vertical Conductors, Downspouts & Horizontal Storm Drains

Core Principle: Gravity storm drainage relies on open-channel hydraulic flow in horizontal piping and annular gravity film flow in vertical stacks. Under Chapter 11 of the 2006 International Plumbing Code, sizing is governed by rainfall intensity, surface square footage, and hydraulic gradient (pipe slope). Furthermore, protecting building occupants from hazardous sewer gas when connecting to older combined municipal systems requires specialized trapping and venting configurations.


Terminology & System Anatomy

A licensed plumber must clearly distinguish between four related but distinct components of a building's storm collection network:

                               SYSTEM ANATOMY
                               
               Roof Drain                   Roof Gutter
                   |                             |
                   v                             v
          +-----------------+           +-----------------+
          |    CONDUCTOR    |           |     LEADER      |
          | (Interior Pipe) |           | (Exterior Pipe) |
          +--------+--------+           +--------+--------+
                   |                             |
                   +--------------+--------------+
                                  |
                                  v
                   +------------------------------+
                   |    BUILDING STORM DRAIN      |
                   |  (Inside Building to 5' Out) |
                   +--------------+---------------+
                                  |
                                  v 5 Feet Beyond Building Wall
                   +------------------------------+
                   |    BUILDING STORM SEWER      |
                   |   (5' Beyond Wall to Main)   |
                   +------------------------------+
  1. Conductor: An interior vertical pipe for conveying stormwater from the roof down through the inside of a building.
  2. Leader: An exterior vertical drainage pipe (commonly called a downspout) for conveying stormwater from roof gutters or exterior scuppers down the outside face of a building.
  3. Building Storm Drain: The lowest horizontal piping of a storm drainage system that receives stormwater from conductors and conduits inside the walls of the building and conveys it to the building storm sewer, terminating 5 feet (1,524 mm) outside the inner face of the building wall.
  4. Building Storm Sewer: The exterior piping that receives discharge from the building storm drain 5 feet outside the building wall and conveys it to a public storm sewer, combined sewer, or approved private outfall.

Sizing Vertical Conductors & Leaders (IPC Section 1106.2 and Table 1106.2)

Vertical leaders and conductors carry high-velocity discharge. Water clings to the pipe walls in a cylindrical film surrounding a core of moving air. When conductors are properly sized, they run at approximately 1/3 core capacity, preventing air choking, extreme hydraulic shock, and excessive pressure spikes.

+-------------------------------------------------------------------------+
|         IPC TABLE 1106.2: SIZE OF VERTICAL CONDUCTORS AND LEADERS       |
|               (Maximum Projected Roof Area in Square Feet)              |
+---------------+---------------------------------------------------------+
| Leader        |     Horizontally projected roof area (square feet)      |
| Diameter      |  1 in/hr  |  2 in/hr  |  3 in/hr  |  4 in/hr  | 6 in/hr |
+---------------+-----------+-----------+-----------+-----------+---------+
| 2"            |   2,880   |   1,440   |     960   |     720   |    480  |
| 3"            |   8,800   |   4,400   |   2,930   |   2,200   |  1,470  |
| 4"            |  18,400   |   9,200   |   6,130   |   4,600   |  3,070  |
| 5"            |  34,600   |  17,300   |  11,530   |   8,650   |  5,765  |
| 6"            |  54,000   |  27,000   |  17,995   |  13,500   |  9,000  |
| 8"            | 116,000   |  58,000   |  38,660   |  29,000   | 19,315  |
+---------------+-----------+-----------+-----------+-----------+---------+
| There is NO 2-1/2 inch row in Table 1106.2, and the table is published |
| at whole-number rainfall rates. For Indiana's 2.5 to 3.0 in/hr design  |
| rates, convert the roof area to the 1 in/hr column instead (equivalent |
| area = actual area x rainfall rate) or interpolate between columns.    |
+-----------------------------------------------------------------------+

Rectangular Leaders (Exterior Downspouts)

When architectural downspouts are rectangular rather than round, footnote a to Table 1106.2 governs: the sizes indicated are the diameter of circular piping, and the table applies to piping of other shapes provided the cross-sectional shape fully encloses a circle of the diameter indicated. There is no Section 1106.2.1 in the 2006 IPC. For example, a 3-inch round conductor has a cross-sectional area of:

A=πr2=3.14159×(1.5)2=7.07 sq inA = \pi r^2 = 3.14159 \times (1.5)^2 = 7.07 \text{ sq in}

The footnote test is geometric, not area-based: a 2-inch by 3-inch rectangular downspout cannot fully enclose a 3-inch circle (its short dimension is only 2 inches), so it does not qualify as a 3-inch conductor even though its 6.0 square inches is close to the 7.07 square inches of the round pipe. A 3-inch by 4-inch downspout does enclose a 3-inch circle and qualifies.


Sizing Horizontal Storm Drains & Sewers (IPC Table 1106.3)

Horizontal storm piping operates under gravity flow. Sizing is controlled by the internal pipe diameter and the slope (pitch) of the line. Under the Manning formula, increasing pipe slope accelerates flow velocity, allowing a given pipe diameter to drain a substantially larger roof footprint.

+-------------------------------------------------------------------------+
|      IPC TABLE 1106.3: SIZING OF HORIZONTAL BUILDING STORM DRAINS       |
|               (Maximum Projected Roof Area in Square Feet)              |
+----------+--------------------------------------------------------------+
| Pipe     |  Horizontally projected roof area (square feet) by slope     |
| Diameter |     1/8 in/ft (1% slope)      |     1/4 in/ft (2% slope)     |
| (Inches) | 1 in/hr | 2 in/hr | 3 in/hr | 1 in/hr | 2 in/hr | 3 in/hr  |
+----------+---------+---------+---------+---------+---------+----------+
| 3"       |   3,288 |   1,644 |   1,096 |   4,640 |   2,320 |    1,546 |
| 4"       |   7,520 |   3,760 |   2,506 |  10,600 |   5,300 |    3,533 |
| 5"       |  13,360 |   6,680 |   4,453 |  18,880 |   9,440 |    6,293 |
| 6"       |  21,400 |  10,700 |   7,133 |  30,200 |  15,100 |   10,066 |
| 8"       |  46,000 |  23,000 |  15,330 |  65,200 |  32,600 |   21,733 |
| 10"      |  82,800 |  41,400 |  27,600 | 116,800 |  58,400 |   38,950 |
| 12"      | 133,200 |  66,600 |  44,400 | 188,000 |  94,000 |   62,600 |
+----------+---------+---------+---------+---------+---------+----------+
| Table 1106.3 also carries a 1/2 in/ft (4%) block and a 15-inch row.    |
| It is published at whole-number rainfall rates; for an Indiana design  |
| rate of 2.5 or 2.75 in/hr, convert to the 1 in/hr column or            |
| interpolate between the published columns.                             |
+-----------------------------------------------------------------------+

Slope & Velocity Dynamics

  • Minimum Fall: Section 1106.3 states it plainly: "The minimum slope of horizontal branches shall be one-eighth unit vertical in 12 units horizontal (1-percent slope) unless otherwise approved." That floor applies at every diameter in the table, including 3 inch — there is no separate 1/4-inch-per-foot minimum for 3-inch storm piping.
  • Self-Cleansing Velocity: Horizontal storm drains must maintain a minimum scouring velocity of 2 feet per second (fps) to transport grit, roofing gravel, and sediment to the municipal main without siltation.
  • Steep Pitch Capacity Boost: doubling the slope from 1/8 inch to 1/4 inch per foot raises capacity by about 41 percent, because open-channel flow varies with the square root of the slope. Read it off the table: a 4-inch horizontal storm drain at a 2 in/hr rate goes from 3,760 square feet at 1/8 inch per foot to 5,300 square feet at 1/4 inch per foot.

Combined Sewer Systems vs. Separate Storm Sewers (IPC Sections 1101.3, 1103 and 1108)

Historically, older industrial Indiana cities—including Indianapolis, Fort Wayne, South Bend, Terre Haute, and Evansville—constructed combined sewer systems where domestic sewage and urban runoff co-mingle in a single street sewer. Modern subdivisions and commercial developments, by contrast, utilize separate storm sewer systems.

                   COMBINED SEWER CONNECTION (IPC SECTION 1103.1)
                   
    Roof Conductors / Downspouts
                 |
                 v
    Horizontal Building Storm Drain
                 |
                 |      Fresh air inlet where required by the
                 |      local authority (not an IPC 2006 mandate)
                 |            |
                 v            v
             +---+------------+---+
             |                    |
             |   BUILDING TRAP    |  <-- Trapped Building Storm Sewer
             |    (Full-Size)     |      (Prevents sewer gas from migrating
             |       \____/       |       up into roof drains/downspouts)
             +----------+---------+
                        |
                        v
          To Public Combined Sewer Main

Trapping the Building Storm Sewer (IPC Section 1109.1)

When stormwater connects to a combined public sewer, sewer gas containing toxic hydrogen sulfide ($H_2S$), methane, and volatile organics can travel upstream. If untrapped, these foul gases will discharge out of roof drains into fresh-air HVAC intakes or spew from exterior downspouts at pedestrian grade.

  • Trap Requirement: Under IPC Section 1109.1, where the building storm drain connects to a combined sewer, a single building trap must be installed in the horizontal building storm drain or building storm sewer.
  • Trap Construction (1103.2, 1103.3, 1103.4): the trap must be of the materials approved for the storm drainage system, not less than the diameter of the drain it serves, and provided with an accessible cleanout located upstream of the trap.
  • Fresh Air Inlet — not an IPC 2006 requirement: older codes and some municipal ordinances require a fresh air inlet on the building side of a main trap, sized at roughly one-half the diameter of the sewer and terminating outdoors with a perforated cap or return bend. The 2006 IPC contains no such provision, and there is no Section 1109.2 — Section 1109 is Values for Continuous Flow and consists only of 1109.1. Install one where the local ordinance requires it, but do not cite the IPC for it.

Strictly Prohibited Connections (IPC Section 1101.3 & 1109.3)

  1. Sanitary Into Storm: No sanitary sewage, liquid waste, industrial effluent, or chemical waste may ever discharge into a storm drainage system.
  2. Storm Into Sanitary: No surface runoff, downspout, roof drain, foundation subsoil drain, or groundwater sump pump may ever connect to a dedicated public sanitary sewer. Connecting stormwater into sanitary mains causes hydraulic surging, basement sewage backups, and illicit Combined Sewer Overflows (CSOs) that violate federal Clean Water Act regulations enforced by the Indiana Department of Environmental Management (IDEM).

Approved Piping Materials (IPC Table 1102.4 & 1102.5)

Piping inside and outside the building envelope must comply with rigid ASTM metallurgical and plastic standards:

LocationApproved Piping MaterialsGoverning Standards
Interior Conductors (Above Ground)Cast Iron (Hubless / Hub-and-Spigot)<br/>Schedule 40 PVC DWV<br/>Galvanized Steel<br/>Type DWV, L, or K CopperASTM A888 / CISPI 301<br/>ASTM D2665 / ASTM F891<br/>ASTM A53<br/>ASTM B306 / ASTM B88
Underground Building Storm Drain (Inside Footprint)Service Weight Cast Iron<br/>Schedule 40 PVC (Solid Wall)<br/>Heavy-Wall Copper (Type L or K)ASTM A74<br/>ASTM D2665 / ASTM D1785<br/>ASTM B88
Building Storm Sewer (Exterior, 5' Outside Wall)Schedule 40 PVC<br/>SDR-35 PVC Sewer Pipe<br/>Cast Iron Sewer Pipe<br/>Reinforced Concrete Pipe (RCP)ASTM D2665<br/>ASTM D3034<br/>ASTM A74 / ASTM A888<br/>ASTM C76

[!WARNING] Cellular-core PVC (ASTM F891) is permitted for above-ground DWV and conductors in some jurisdictions, but Indiana contractors must ensure solid-core PVC (ASTM D2665) is installed where underground burial or high-impact physical exposure is anticipated.


Cleanout Requirements (IPC Section 1101.8)

Storm drainage systems accumulate roofing gravel, asphalt granules, leaves and silt. Section 1101.8 handles it by reference: "Cleanouts shall be installed in the storm drainage system and shall comply with the provisions of this code for sanitary drainage pipe cleanouts. Exception: Subsurface drainage system."

So Section 708 governs storm cleanouts too:

  1. Base of stacks (708.3.4): a cleanout at the base of each waste or soil stack — applied to storm work, at the base of each vertical conductor.
  2. Changes of direction (708.3.3): at each change of direction greater than 45 degrees, with only one cleanout required per 40 feet of developed length where multiple changes occur.
  3. Horizontal runs (708.3.1 / 708.3.2): cleanouts not more than 100 feet apart.
  4. Sizing (708.7): the same nominal size as the pipe up to 4 inches; for pipe larger than 4 inches, a minimum 4-inch cleanout.
  5. Clearances (708.8): not less than 18 inches for cleanouts on pipes 6 inches and smaller, and not less than 36 inches for cleanouts on pipes 8 inches and larger.
  6. Exception: subsurface (subsoil) drainage systems are exempt from the cleanout requirement.

Expansion Joints in Tall Vertical Stacks

In multi-story commercial buildings, tall vertical conductors undergo significant thermal elongation and contraction. Plastic piping (PVC) expands at a rate of approximately 3/8 inch per 100 feet per 10°F temperature change.

A vertical conductor installed inside a building where temperatures range from 40°F during construction to 80°F in summer will shift more than an inch over a 100-foot vertical drop. Without engineered expansion joints, rubber-sleeved slip couplings, and rigid thrust hangers, thermal movement will buckle piping, shear off horizontal branch fittings, or pull the roof drain body loose from the roof deck.

Test Your Knowledge

A building storm drainage system discharges into a public combined sewer. Which IPC provision requires trapping, and what does it permit?

A
B
C
D
Test Your Knowledge

Which IPC section governs cleanouts in a storm drainage system, and what does it require?

A
B
C
D
Test Your Knowledge

A horizontal 4-inch building storm drain is installed at a slope of 1/8 inch per foot. If the installation is modified to increase the slope to 1/4 inch per foot, how does this affect the hydraulic carrying capacity of the pipe?

A
B
C
D