14.2 Key Indiana Amendments to the 2006 IPC (675 IAC 16-1.4)
Key Takeaways
- 675 IAC 16-1.4-1 adopts the 2006 International Plumbing Code, second printing, as the 2012 Indiana Plumbing Code, save and except the amendments made in the rule.
- Indiana Section 101.2 states that the plumbing code does not regulate plumber licensure, which is set out in IC 25-28.5, and Section 101.3 makes appendix provisions unenforceable unless specifically adopted: only Appendix C (gray water) and Appendix E (water pipe sizing) are adopted.
- 675 IAC 16-1.4-4 adds Section 305.6.2 and Table 305.6.2, setting exterior water supply bury depth by county at 36, 42 or 48 inches measured from finished grade to the top of the pipe.
- 675 IAC 16-1.4-5 deletes IPC Sections 403, 404, 405.2, 405.3, 405.3.1, 410.1 and 410.2 and inserts 'See Chapter 29 of the Indiana Building Code.'
- 675 IAC 16-1.4-10 fills the blank in Section 904.1 with six inches and bars air admittance valves from serving as the vent terminal for vent stacks or stack vents and from venting sump pits, but the rule makes no amendment to Section 312.3, so Indiana does not prohibit pneumatic testing of plastic DWV piping.
14.2 Key Indiana Amendments to the 2006 IPC (675 IAC 16-1.4)
Core Principle: The technical baseline for plumbing in Indiana is the 2006 International Plumbing Code, 2nd printing, adopted by reference and amended by the Fire Prevention and Building Safety Commission at 675 IAC 16-1.4, titled the 2012 Indiana Plumbing Code. The rule is short — twenty-two numbered sections — and it is free online. Print it, tab it, and bring it. The Prov Candidate Information Bulletin expressly permits candidate-printed copies in the testing room.
Indiana Code Adoption Architecture
675 IAC 16-1.4-1 adopts "the International Plumbing Code, 2006 edition, second printing, published by the International Code Council... save and except those amendments made in this rule," and provides that wherever the term "this code" appears it means the 2012 Indiana Plumbing Code.
+-------------------------------------------------------------------------+
| INDIANA PLUMBING CODE LEGAL STRUCTURE |
+-------------------------------------------------------------------------+
| Model Building Code | 2006 International Plumbing Code, 2nd printing |
| State Adopting Agency | Fire Prevention & Building Safety Commission |
| Administrative Rule | 675 IAC 16-1.4 (2012 Indiana Plumbing Code) |
| Statutory Authority | Indiana Code Title 22, Article 13 (IC 22-13) |
| Administrative Parent | 675 IAC 12 (General Administrative Rules - GAR)|
| Licensure | NOT in this code - see IC 25-28.5 and 860 IAC |
| Legal Hierarchy | The Indiana amendment overrides the model text |
| | wherever the rule edits, adds, or deletes |
+-------------------------------------------------------------------------+
An answer taken from the unamended model IPC is wrong wherever Indiana has edited that section. The reverse is also true, and it is the more common exam trap: do not invent Indiana amendments that do not exist. The list below is the complete set, section by section, as the rule is written.
Section-by-Section Analysis of the Indiana Amendments
1. Chapter 1 Replaced — 675 IAC 16-1.4-2
Indiana deletes model Chapter 1 and inserts its own Chapter 1, Sections 101.1 through 101.9. Three provisions carry real exam weight:
- 101.2 Scope: the code applies to Class 1 structures except townhouses, within the structure and up to five (5) feet outside any portion of it. Compliance for Class 2 structures or Class 1 townhouses is evidence of compliance with the Indiana Residential Code (675 IAC 14). And: "This code does not regulate licensure requirements for plumbers. Such licensure requirements are set out in IC 25-28.5."
- 101.3 Appendices and Standards: "Provisions in the appendices are not enforceable unless specifically adopted."
- 101.5 through 101.9: plans go to 675 IAC 12-6, existing construction and code conflicts to 675 IAC 12-4, alternative methods to 675 IAC 12-6-11, and appeals to IC 4-21.5 and IC 22-12-7.
2. Chapter 2 Definitions — 675 IAC 16-1.4-3
Indiana rewrites 201.3 to route undefined terms to the Indiana Building, Electrical, Mechanical, Fire and Fuel Gas Codes, and edits twenty-six definitions in Section 202. The ones worth tabbing:
- BACKPRESSURE is added: any elevation of the pressure in the downstream piping system above the supply pressure at the point of consideration, which would cause or tend to cause reversal of normal flow.
- DEAD END becomes "a pipe that is terminated at a developed length of two (2) feet or more by means of a plug or other closed fitting, except where serving a clean out extension to an accessible area."
- CODE OFFICIAL becomes the Division of Fire and Building Safety or the local building official authorized under IC 36-7-2-9.
- GRAY WATER is added: waste water discharged from lavatories, bathtubs, showers, clothes washers, laundry trays, condensate cooling coils, and evaporators.
- WATER CLOSET is added, and WATER MAIN is redefined as water supply pipe or system of pipes for public or community use.
3. Chapter 3 General Regulations — 675 IAC 16-1.4-4
This is the single most productive amendment section for the exam.
| Change | Effect |
|---|---|
| 305.3 | Third sentence added: "No plumbing pipes shall be directly embedded in concrete or masonry." |
| 305.6 | The word "water" deleted from the first sentence and the last sentence deleted, leaving a soil-and-waste freezing rule |
| 305.6.1 | Text replaced: waterlines not outside, in attics or crawlspaces, or anywhere subject to freezing without insulation, ambient heat or an alternate heat source; and "No waterlines shall be concealed in outside walls, above grade." |
| 305.6.2 + Table 305.6.2 | Added: minimum depth of exterior water supply piping, finished grade to top of pipe, by county — 36, 42 or 48 inches |
| 305.8 | Shield plate thickness changed from 0.062 inch to five hundred seventy-five ten-thousandths (0.0575) inch, No. 16 gage |
| 308.6 | Deleted without substitution (model sway bracing provision) |
| 311 | Deleted in its entirety without substitution |
| 312.9.1 / 312.9.2 | 312.9.1: "annual" becomes "at the time of installation"; 312.9.2 deleted |
| 314.2.1 | Condensate disposal extended to gray water storage / nonpotable sustainable use, with a minimum slope of 1/8 unit vertical in 12 units horizontal (1 percent) |
| 301.1.1, 301.3, 301.7, 304.4, 306 items | Cross-reference and wording edits |
The bury-depth table is the money item. Table 305.6.2 lists all 92 counties. Generally 48 inches across the northern tier (Allen, Lake, Porter, St. Joseph, LaPorte, Elkhart and neighbors), 42 inches across the central band (Marion, Hamilton, Hendricks, Johnson, Delaware, Tippecanoe and neighbors), and 36 inches across the south (Vanderburgh, Monroe, Floyd, Clark, Vigo and neighbors). If the stem names a county, look it up — do not estimate from a frost map.
What Indiana did NOT do to Chapter 3. 675 IAC 16-1.4-4 makes no change to Section 312.2 (water test) and no change to Section 312.3 (air test). The air test remains 5 psi, or sufficient to balance a 10-inch column of mercury, held 15 minutes. Any claim that Indiana amended 312.3 to ban pneumatic testing of PVC or ABS is false. Avoiding compressed air on plastic DWV is a manufacturer instruction and OSHA safety matter — real, but not a 675 IAC 16-1.4 amendment.
4. Chapter 4 Fixtures — 675 IAC 16-1.4-5
Indiana hands the fixture-count and clearance questions to the building code:
- Section 403 deleted in its entirety → "See Chapter 29 of the Indiana Building Code."
- Section 404 deleted in its entirety → same.
- Sections 405.2, 405.3, 405.3.1, 410.1 and 410.2 deleted → same.
- Section 419.2, last sentence deleted → same. What remains of 419.2: urinals shall not be substituted for more than 67 percent of the required water closets in assembly and educational occupancies.
- Section 413.4 amended: the cold water supply to a food waste grinder must be protected against backflow by an air gap or a backflow preventer in accordance with Section 608.
- Section 416.5 exception added: an ASSE 1070 point-of-use device may be omitted if the public hand-washing fixture is supplied tempered water through an ASSE 1017 master mixing valve.
- Section 419.1 amended: insert ASME A112.19.19, Vitreous China Nonwater Urinals, 2006 edition after ASME A112.19.2M. (675 IAC 16-1.4-22 adopts that ASME standard by reference with its own edits.)
There is no Indiana amendment to Table 403.1, because Indiana deleted Section 403 outright. Any answer that describes Indiana "amending Table 403.1" or "coordinating fixture ratios" is wrong; the correct move is to open Chapter 29 of the Indiana Building Code.
5. Chapter 5 Water Heaters — 675 IAC 16-1.4-6
Four additions and one replacement, all of them testable:
- 502.1.1 added — Elevation of ignition source: appliances with an ignition source in hazardous locations and in public, private, repair and parking garages and automotive motor-fuel-dispensing facilities must be elevated so the ignition source is not less than eighteen (18) inches above the floor surface. Rooms not part of the living space that communicate directly with a private garage through openings are considered part of the private garage.
- 502.1.1.1 added — Parking garages: connection to a room containing a fuel-fired appliance must be through a vestibule providing a two-door separation, except a single door where ignition sources are elevated per Section 304.3 of the Indiana Mechanical Code.
- 502.2.1 added — Prohibited locations: fuel-fired appliances shall not be located in, or obtain combustion air from, sleeping rooms, bathrooms, toilet rooms, storage closets or surgical rooms, with three exceptions (direct-vent appliances, certain solid fuel-fired appliances, and appliances in a dedicated outdoor-air enclosure behind a weather-stripped self-closing solid door).
- 504.2 replaced — Bottom fed water heaters: protected from accidental drainage and negative pressure by either a check valve plus a properly sized expansion tank, or a vacuum relief valve complying with ANSI Z21.22.
- 504.2.1 added: "The cold water piping shall rise above the top of the water heater before connecting to the tank inlet."
6. Chapter 6 Water Supply — 675 IAC 16-1.4-7
Nineteen edits. The high-value ones:
| Change | Effect |
|---|---|
| Table 605.3 | Delete "M or WM" under copper or alloy tubing → Type M copper is not approved for water service |
| 604.9 | Add "An air chamber is not a water hammer arrestor"; delete the last sentence |
| 607.3.2 | Add: "When thermal expansion tanks are used for this purpose, there shall be no valves installed between the water heating appliance and the expansion tank." |
| Table 608.1 | Carbonated beverage machine backflow preventer reclassified low hazard → high hazard |
| 608.1.1 (new) | The owner shall have the backflow prevention assembly tested at the time of installation and after relocation |
| 608.1.2 (new) | Backflow preventers for hot water over 110°F shall be a listed type designed to operate at 110°F or more |
| 608.14.1 | Replaced: access and clearance for testing; minimum 12 inches between the lowest portion of the assembly and grade, floor or platform; permanent platform where elevated more than 5 feet; RPZ and RPDA installed horizontally unless otherwise listed, where relief-port leakage will be noticed and not subject to flooding |
| 608.15.4 | Replaced: AVB critical level minimum 6 inches above the flood level rim; PVB minimum 12 inches above all downstream piping and outlets; fill valves per 425.3.1; vacuum breakers not under exhaust hoods |
| 608.16.1 | Beverage dispenser supply protected by a listed RPZ; copper shall not be used downstream of the backflow preventer |
| 608.16.5 | After "A valve," insert "including system zone valves" — no valve downstream of an atmospheric vacuum breaker |
| 602.3, 605.3.1, 606.4, 608.17 | Deleted without substitution |
| 605.22.2 | "Purple" and "not purple in color" deleted (CPVC primer color) |
| 607.1 | ASSE 1070 / ASSE 1017 exception added, mirroring 416.5 |
7. Chapter 7 Sanitary Drainage — 675 IAC 16-1.4-8
| Change | Effect |
|---|---|
| 710.3 (new) | "The minimum pipe size installed underground in a sanitary drainage system within a building shall be two (2) inch nominal." |
| Table 710.1(2) | Second column: delete 2,900, insert 3,900 |
| Table 702.2 | Delete "M or DWV" under copper or copper alloy tubing → not approved for underground sanitary drainage |
| 705.8.2 and 705.14.2 | Delete "purple" and "not purple in color and" → an ASTM F 656 primer is required, color unspecified |
| 706.3 | Delete "side inlets or" from the change-in-direction fitting rule |
| 708.3.5 | Fourth sentence deleted → the exception letting a nearby stack cleanout substitute for the building drain / building sewer junction cleanout is gone; the junction cleanout is always required |
| Table 704.1 | SI units typographical correction |
8. Chapter 8 Indirect/Special Waste — 675 IAC 16-1.4-9
A single sentence added to 802.4: "A trap for a clothes-washer standpipe receptor shall not be installed below the floor." That is the whole of Indiana's Chapter 8 amendment.
9. Chapter 9 Vents — 675 IAC 16-1.4-10
| Change | Effect |
|---|---|
| 901.2.1 | Exception added: floor drains |
| 904.1 | The model code's blank is filled: open vent pipes terminate at least six (6) inches (152.4 mm) above the roof |
| 917.1 | Delete "Stack type air admittance valves shall conform to ASSE 1050" |
| 917.3 | Text replaced: individual and branch-type AAVs vent only fixtures on the same floor level connecting to a horizontal branch drain |
| 917.3.3 | Text replaced: "Air admittance valves shall not serve as the vent terminal for vent stacks or stack vents." |
| 917.4 | Delete the stack-type AAV six-inch location sentence |
| 917.8 | Add: "Air admittance valves shall not be used to vent sump pits." |
| 918.2 | Equation 9-1 exponent typesetting correction |
Frost closure is not on this list. The 3-inch frost closure rule is base IPC Section 904.2, unamended by Indiana, and it is triggered by a 97.5-percent outside design temperature of 0°F or less — not by being in Indiana. Section 904.1's Indiana amendment is about the 6-inch roof extension height, nothing more.
10. Chapter 10 Traps and Interceptors — 675 IAC 16-1.4-11
- 1002.1, exception 2: after "fixture," insert "up to three (3) compartments" — a combination fixture of up to three compartments may share one trap.
- 1003.1, second sentence added: "A cleanout shall be installed immediately downstream of the interceptor or separator."
11. Chapter 11 Storm Drainage — 675 IAC 16-1.4-12
- 1107.2 deleted without substitution (the model "Separate Systems Required" provision for secondary roof drainage).
- 1113.1.5 added: "Water powered sump pumps. Water powered sump pumps shall comply with Section 608 of this code."
12. Chapter 12 and Chapter 13 — 675 IAC 16-1.4-13 and -14
- Chapter 12 (Special Piping and Storage Systems): text deleted and replaced with "See the Indiana Fire Code (675 IAC 22)."
- Chapter 13 (Referenced Standards): the first paragraph's reference to Section 102.8 becomes "See Section 101.3"; ASSE 1050 (Stack Air Admittance Valves) is deleted from the ASSE list; and NFPA 50, NFPA 51 and NFPA 70 editions are replaced with pointers to 675 IAC 28-1-16, 675 IAC 28-1-18 and 675 IAC 17 respectively.
13. The Appendices — 675 IAC 16-1.4-15 through -21
| Appendix | Subject | Indiana Status |
|---|---|---|
| A | Plumbing Permit Fee Schedule | Text deleted; "See local ordinance" |
| B | Rates of Rainfall for Various Cities | Not adopted, informational only |
| C | Gray Water Recycling Systems | Adopted, with the gray water definition replaced and Section C103 deleted |
| D | Degree Day and Design Temperatures | Not adopted, informational only |
| E | Sizing of Water Piping System | Adopted, with two cross-reference corrections in Section E201.1 |
| F | Structural Safety | Not adopted; for cutting, notching and boring in wood members see the Indiana Building Code (675 IAC 13) or Indiana Residential Code (675 IAC 14) |
| G | Vacuum Drainage System | Not adopted, informational only |
Read that table against Section 101.3 — appendices are unenforceable unless specifically adopted — and the result is clean: only Appendix C and Appendix E are enforceable in Indiana.
A Note on Cross-Connection Control and IDEM
Section 608 is the plumbing code's cross-connection chapter, and Indiana amended it substantially as shown above. Separately, the Indiana Department of Environmental Management administers 327 IAC 8-10 (Cross-Connection Control), which governs public water supply systems and obliges water utilities to operate cross-connection control programs and to require protection at the service connection for hazardous facilities. Two things follow:
- Two different rulebooks, two different enforcers. The plumbing inspector enforces 675 IAC 16-1.4 Section 608 inside the building. The water utility, under IDEM's 327 IAC 8-10, enforces containment at the service connection. A commercial job can be required to satisfy both.
- Testing frequency differs. The plumbing code as amended requires testing at the time of installation (312.9.1) and after relocation (608.1.1) — Indiana deleted the model code's annual requirement. Utility cross-connection control programs under 327 IAC 8-10 commonly impose their own periodic testing, frequently annual. If a stem asks what the plumbing code requires, answer "at installation and after relocation." If it asks what the water utility requires, that is a program question, so check the utility's rule.
Indiana Amendment Cross-Reference Matrix
| Code Section | Model 2006 IPC Text | 2012 Indiana Amendment (675 IAC 16-1.4) | Practical Jobsite Impact |
|---|---|---|---|
| Chapter 1 | Model administrative rules and permit procedures | Deleted and replaced with Indiana 101.1–101.9 | Plan review and variances follow 675 IAC 12; licensure is in IC 25-28.5 |
| 305.3 | Stress and strain | Sentence added | No plumbing pipe directly embedded in concrete or masonry |
| 305.6.2 / Table 305.6.2 | Not present | Added | Exterior water supply bury depth 36, 42 or 48 inches by county |
| 305.8 | 0.062-inch shield plate | Amended | 0.0575 inch, No. 16 gage steel shield plate |
| 312.9.1 / 312.9.2 | Annual backflow testing | Amended / deleted | Test at installation; with 608.1.1, also after relocation |
| 403, 404, 405.3, 410 | Fixture counts, clearances, fountains | Deleted | "See Chapter 29 of the Indiana Building Code" |
| 502.1.1 | Not present in IPC Ch. 5 | Added | Ignition source 18 inches above the garage floor |
| Table 605.3 / Table 702.2 | Copper types listed | Amended | Type M struck from water service; M and DWV struck from underground drainage |
| 608.14.1 / 608.15.4 | Model location and vacuum breaker text | Replaced | 12-inch clearance, platform above 5 ft, RPZ horizontal; AVB 6 in / PVB 12 in |
| 710.3 | Not present | Added | 2-inch nominal minimum underground sanitary drainage in a building |
| 708.3.5 | Junction cleanout with a stack exception | Fourth sentence deleted | Building drain / building sewer junction cleanout always required |
| 802.4 | Standpipe rules | Sentence added | No clothes-washer standpipe trap below the floor |
| 904.1 | Blank roof extension height | Blank filled | Six (6) inches above the roof |
| 917.3.3 / 917.8 | Stack-type AAVs permitted | Replaced / amended | No AAV on a vent stack or stack vent; no AAV on a sump pit |
| 1002.1 / 1003.1 | Traps and interceptors | Amended | Three-compartment combination fixture on one trap; cleanout downstream of every interceptor |
| 1107.2 | Separate secondary systems required | Deleted | Not part of the Indiana Plumbing Code |
| 1113.1.5 | Not present | Added | Water powered sump pumps comply with Section 608 |
| Chapter 12 | Special piping and storage | Deleted | "See the Indiana Fire Code (675 IAC 22)" |
| Appendices A, B, D, F, G | Model appendices | Not adopted | Only Appendix C and Appendix E are enforceable |
Which of the following is an actual amendment made by 675 IAC 16-1.4 to the 2006 IPC?
Under 675 IAC 16-1.4, what is the status of the appendices to the 2006 IPC in Indiana?
Which Indiana amendment changes how a building drain to building sewer junction cleanout is handled?