13.4 Electrical Measuring Devices: Voltmeter, Ammeter, and Wattmeter
Key Takeaways
- NCEES lists measuring devices, naming the voltmeter, ammeter, and wattmeter, as its own Basic Electrical Engineering sub-topic.
- A voltmeter connects in parallel and must have very high internal resistance; an ammeter connects in series and must have very low internal resistance.
- Connecting an ammeter in parallel across a source creates a near short circuit, which is the most destructive instrument error.
- Loading error occurs when the meter's own impedance alters the circuit being measured, and it is worst when the meter resistance is comparable to the circuit resistance.
- A wattmeter measures true average power including power factor, so on an AC circuit its reading is less than the product of separate voltmeter and ammeter readings whenever the power factor is below unity.
13.4 Electrical Measuring Devices: Voltmeter, Ammeter, and Wattmeter
NCEES lists "Measuring devices (e.g., voltmeter, ammeter, wattmeter)" as one of five Basic Electrical Engineering sub-topics. It is examined conceptually — connection topology, ideal internal impedance, and loading error — with occasional short calculations. Small topic, quick points.
The Two Connection Rules
| Instrument | Measures | Connection | Ideal internal resistance | Why |
|---|---|---|---|---|
| Voltmeter | Potential difference | Parallel (across the element) | Infinite ($\to \infty$) | Must draw no current, so it cannot divert any from the circuit |
| Ammeter | Current | Series (in the current path) | Zero ($\to 0$) | Must drop no voltage, so it cannot reduce the circuit current |
| Ohmmeter | Resistance | Across a de-energized element | Supplies its own source | External voltage corrupts the reading and can destroy the meter |
| Wattmeter | True average power | Current coil in series, voltage coil in parallel | Both, as above | Needs both quantities simultaneously, with their phase relationship |
Memorize the pairing: voltmeter — parallel — high resistance and ammeter — series — low resistance. Everything else in the topic follows from it.
The Consequences of Getting It Wrong
| Error | Result |
|---|---|
| Ammeter in parallel across a source | Its near-zero resistance forms a short circuit — the most destructive instrument mistake, typically destroying the meter and tripping protection |
| Voltmeter in series with a load | Its enormous resistance nearly opens the circuit; the load stops working and the voltmeter reads almost the full source voltage |
| Ohmmeter on an energized circuit | Wrong reading and probable meter damage |
Loading Error
A real meter changes the circuit it measures. The magnitude of the disturbance depends on the ratio of meter resistance to circuit resistance.
Voltmeter Loading
A voltmeter of resistance $R_V$ across a resistor $R$ makes the effective resistance:
The reading is low, and the fractional error is approximately:
where $R_{\text{Th}}$ is the Thevenin resistance seen by the meter.
Worked Example: Voltmeter Loading in a Divider
Two 1.0 MΩ resistors form a divider across 100 V. A voltmeter with $R_V = 10$ MΩ measures across the lower resistor. What does it read?
True value (no meter): $V = 100 \times \frac{1.0}{1.0+1.0} = 50.0$ V.
With the meter, the lower resistor is paralleled by 10 MΩ:
A 4.8% error from a meter whose resistance is 10× the circuit resistance. This is why high-impedance circuits demand high-impedance meters: a modern digital multimeter at 10 MΩ is adequate here, while an old 20 kΩ/V analog meter would read about 2 V and be worthless.
The rule of thumb: keep $R_V \ge 100 R_{\text{Th}}$ for error under 1%. In low-impedance power circuits ($R_{\text{Th}}$ of a few ohms) loading is negligible; in sensor and instrumentation circuits it dominates.
Range Extension: Shunts and Multipliers
Ammeter Shunt (parallel)
To extend an ammeter of full-scale current $I_m$ and resistance $R_m$ to measure $I_{\text{total}}$:
Voltmeter Multiplier (series)
To extend a movement of full-scale voltage $V_m$ to measure $V_{\text{total}}$:
Note the symmetry: the shunt divides $R_m$ by $(n-1)$ and sits in parallel; the multiplier multiplies $R_m$ by $(n-1)$ and sits in series. Both follow directly from the connection rules.
For high AC currents and voltages, instrument transformers replace shunts and multipliers: a current transformer (CT) steps current down to a 5 A or 1 A secondary, and a potential transformer (PT) steps voltage down to 120 V. A CT secondary must never be open-circuited while primary current flows — the core saturates and dangerous voltages appear at the terminals.
The Wattmeter
A wattmeter has two coils and reads the true average power, automatically including the phase relationship:
| Coil | Connection |
|---|---|
| Current coil | In series with the load |
| Voltage (potential) coil | In parallel with the load |
The wattmeter's defining advantage. On an AC circuit, a voltmeter reading times an ammeter reading gives apparent power $S = VI$ in volt-amperes — not real power. The wattmeter multiplies the instantaneous values before averaging, so it captures $\cos\theta$ and reports watts.
This is the standard exam item on this sub-topic, and it also gives you a practical way to determine power factor from three instruments.
Worked Example: Power Factor from Three Meters
A single-phase motor circuit reads 240 V, 18 A, and 3{,}240 W. Find the power factor, apparent power, and reactive power.
Check with the power triangle: $\sqrt{P^2+Q^2} = \sqrt{3{,}240^2 + 2{,}856^2} = \sqrt{1.050\times10^7 + 8.157\times10^6} = \sqrt{1.866\times10^7} = 4{,}320$ VA ✓
Trap: assuming $P = VI = 4{,}320$ W overstates real power by 33%, and a motor sized on that figure would be a third too large. Only the wattmeter reading is power.
Two-Wattmeter Method for Three-Phase Power
Any three-wire three-phase load — balanced or unbalanced, wye or delta — has its total real power measured by just two wattmeters:
For a balanced load, the two readings also yield the power factor:
| Power factor | Reading behavior |
|---|---|
| $pf = 1.0$ | $W_1 = W_2$ (equal readings) |
| $pf = 0.5$ | One wattmeter reads zero |
| $pf < 0.5$ | One wattmeter reads negative — reverse its connection and subtract |
The negative reading at low power factor surprises candidates but is physically correct, and the total is still $W_1 + W_2$ with the sign respected.
True-RMS vs. Average-Responding Meters
| Meter type | Reads correctly for | Error source |
|---|---|---|
| True-RMS | Any waveform | None significant |
| Average-responding, RMS-calibrated | Pure sine waves only | Reads low on distorted waveforms |
Average-responding meters are calibrated by multiplying the rectified average by the sine wave's form factor, 1.11. On the distorted, harmonic-rich currents drawn by variable-frequency drives, switch-mode supplies, and LED lighting, they can read 30–40% low. Where harmonics are present — which is most modern electrical work — a true-RMS instrument is required.
An ammeter is mistakenly connected in parallel across a 24 V source. What is the most likely outcome?
A single-phase load reads 208 V on a voltmeter, 12 A on an ammeter, and 1,996 W on a wattmeter. What is the power factor?
A voltmeter with 10 M-ohm input resistance measures across one leg of a divider made of two 2 M-ohm resistors fed from 60 V. What does it read?
In the two-wattmeter method applied to a balanced three-phase load, one wattmeter reads negative. What does this indicate?