3.1 Water Service & Distribution Sizing: WSFU, Demand, Pressure & Friction
Key Takeaways
The water service pipe must be at least 3/4 inch (IPC 603.1), and a pressure-reducing valve with a strainer is required where static pressure in the building exceeds 80 psi (IPC 604.8).
IPC Table 604.5 sets minimum fixture supply sizes: 1 inch for a flushometer-valve water closet, 3/4 inch for a flushometer-valve urinal, 1/2 inch for most sinks, tubs and showers, and 3/8 inch for lavatories and flush-tank water closets.
In Appendix E Table E103.3(2), a public flushometer-valve water closet is 10 fixture units, a private flushometer-valve water closet is 6, a public flush-tank water closet is 5, and a private flush-tank water closet is 2.2.
Appendix E Table E103.3(3) converts 100 fixture units to 43.5 gpm for a system mostly on flush tanks, but 67.5 gpm for a system mostly on flushometer valves.
The friction allowance per 100 feet equals the pressure left after elevation, meter, device and fixture flow-pressure losses, divided by the developed length and multiplied by 100.
Why this section matters
Sizing and Design is the second-largest area on the exam, with 9 questions. Water sizing problems combine several tables. Appendix E of the 2021 IPC lays out a method, and section 604.1 says any approved, accepted engineering method may be used. Exam problems normally follow Appendix E, so tab Tables 604.3, 604.4, 604.5, E103.3(2), E103.3(3) and the friction charts.
Pressure and size limits in Chapter 6
| Rule | Requirement |
|---|---|
| 603.1 | Water service pipe at least 3/4 inch, sized for required flows and pressures |
| 603.2 | Water service may share a trench with the building sewer only if the sewer is a Table 702.2 material. Otherwise keep them 5 feet apart horizontally, or keep the water pipe 12 inches above the top of the sewer, or sleeve it 5 feet each side of a crossing |
| 604.6 | Where street pressure varies, design for the minimum pressure |
| 604.7 | If the supply cannot deliver the Table 604.3 flow pressures, install a booster system (606.5) |
| 604.8 | Where static pressure in the building exceeds 80 psi, install a pressure-reducing valve to ASSE 1003 or CSA B356 with a strainer to hold the system at 80 psi or less. Lines to sillcocks and outside hydrants are exempt. The valve must fail open (604.8.1) and be repairable without removing it from the line (604.8.2) |
| 604.9 | Control velocity to limit water hammer. Install ASSE 1010 water-hammer arrestors at quick-closing valves |
| 607.2 | No more than 50 feet of developed length from the hot water source to a fixture that needs hot or tempered water. A recirculating loop or heat-traced pipe counts as a source |
Table 604.3: flow and pressure at the fixture
| Fixture outlet | Flow (gpm) | Flow pressure (psi) |
|---|---|---|
| Lavatory, private | 0.8 | 8 |
| Sink, residential | 1.75 | 8 |
| Shower | 2.5 | 8 |
| Shower or tub with pressure-balance or thermostatic valve | 2.5 (shower), 4 (tub) | 20 |
| Sillcock, hose bibb | 5 | 8 |
| Water closet, tank, close coupled | 3 | 20 |
| Water closet, flushometer tank | 1.6 | 20 |
| Urinal, flushometer valve | 12 | 25 |
| Water closet, siphonic, flushometer valve | 25 | 35 |
| Water closet, blowout, flushometer valve | 25 | 45 |
Table 604.5: minimum fixture supply pipe
| Fixture | Minimum size |
|---|---|
| Lavatory, drinking fountain, flush-tank or flushometer-tank water closet, bidet | 3/8 in |
| Kitchen sink, bathtub, shower, laundry, service sink, domestic dishwasher, hose bibb, wall hydrant, one-piece water closet | 1/2 in |
| Urinal, flushometer valve; flushing-rim sink | 3/4 in |
| Water closet, flushometer valve | 1 in |
A fixture supply must end within 30 inches of the fixture connection (604.5).
Water supply fixture units (Appendix E)
A water supply fixture unit (wsfu) weights each fixture by how much water it uses, for how long and how often. Public fixtures get higher values because they are used more often. Table E103.3(2) lists separate cold, hot and total loads. For a fixture with both, each side is about three-quarters of the total. Size cold-only or hot-only piping with the cold or hot value, and size piping that carries both with the total.
| Fixture (Table E103.3(2)) | Occupancy | Cold | Hot | Total |
|---|---|---|---|---|
| Water closet, flushometer valve | Public | 10.0 | — | 10.0 |
| Water closet, flushometer valve | Private | 6.0 | — | 6.0 |
| Water closet, flush tank | Public | 5.0 | — | 5.0 |
| Water closet, flush tank | Private | 2.2 | — | 2.2 |
| Water closet, flushometer tank | Either | 2.0 | — | 2.0 |
| Urinal, 3/4-inch flushometer valve | Public | 5.0 | — | 5.0 |
| Urinal, 1-inch flushometer valve | Public | 10.0 | — | 10.0 |
| Lavatory | Private | 0.5 | 0.5 | 0.7 |
| Lavatory | Public | 1.5 | 1.5 | 2.0 |
| Bathtub or shower head | Private | 1.0 | 1.0 | 1.4 |
| Bathtub or shower head | Public | 3.0 | 3.0 | 4.0 |
| Kitchen sink | Private | 1.0 | 1.0 | 1.4 |
| Kitchen sink | Hotel or restaurant | 3.0 | 3.0 | 4.0 |
| Service sink | Offices | 2.25 | 2.25 | 3.0 |
| Bathroom group, flush tank | Private | 2.7 | 1.5 | 3.6 |
| Dishwashing machine | Private | — | 1.4 | 1.4 |
| Drinking fountain | Offices | 0.25 | — | 0.25 |
Demand: Table E103.3(3)
Fixture units are converted to probable peak flow. Use the flushometer-valve column whenever the system is mainly flushometer valves.
| WSFU | Flush tanks (gpm) | Flushometer valves (gpm) |
|---|---|---|
| 5 | 9.4 | 15.0 |
| 10 | 14.6 | 27.0 |
| 20 | 19.6 | 35.0 |
| 30 | 23.3 | 42.0 |
| 40 | 26.3 | 46.0 |
| 50 | 29.1 | 50.0 |
| 60 | 32.0 | 54.0 |
| 70 | 35.0 | 58.0 |
| 80 | 38.0 | 61.2 |
| 100 | 43.5 | 67.5 |
| 120 | 48.0 | 73.0 |
| 140 | 52.5 | 77.0 |
| 160 | 57.0 | 81.0 |
| 200 | 65.0 | 90.0 |
| 300 | 85.0 | 108.0 |
The two columns become equal at 1,000 wsfu (208 gpm). Above that, flush valves no longer dominate the demand.
The friction-loss method
- Static pressure at the main or meter, using the lowest expected pressure (604.6).
- Elevation loss: vertical rise to the highest fixture × 0.433 psi per foot.
- Losses through the meter and devices, such as the meter, backflow assembly and PRV, from manufacturer data.
- Required flow pressure at the critical fixture, from Table 604.3.
- Pressure left for friction = static − elevation − meter and devices − fixture pressure.
- Developed length = measured length + equivalent length of fittings and valves. Appendix E's equivalent-length table gives values. For example, a 90-degree elbow counts as 2.0 feet in 1/2-inch pipe, 3.0 feet in 1-inch and 7.0 feet in 2-inch. A tee through the branch counts as 3.0, 5.0 and 10.0 feet in those sizes.
- Friction allowance per 100 feet = pressure left for friction ÷ developed length × 100.
- Pick the smallest pipe whose friction loss at the design flow stays within the allowance. Then check the velocity.
Velocity. The IPC sets no fixed velocity number. Section 604.9 only requires velocity to be controlled, and Appendix E tells you to choose a design velocity. The Copper Development Association recommends no more than about 8 ft/s for cold water and 5 ft/s for hot water up to 140°F in copper. Treat those as design guidance, not code.
Worked example: two-story medical office (flushometers)
- Static pressure: 68 psi. Highest fixture: 22 feet above the meter.
- Meter loss 4.5 psi, RPZ assembly loss 9.5 psi.
- Critical fixture: siphonic flushometer water closet, which needs 35 psi (Table 604.3).
- Piping: 110 feet measured plus 40 feet of fitting allowance, so 150 feet developed.
- Load: 65 wsfu, mainly flush valves.
- Demand: halfway between 60 wsfu (54 gpm) and 70 wsfu (58 gpm) in the flushometer column gives about 56 gpm.
- Elevation loss: psi.
- Pressure left for friction: psi.
- Allowance: psi per 100 feet.
- Type L copper at 56 gpm (Hazen-Williams, C = 150):
| Size | Friction loss (psi per 100 ft) | Velocity (ft/s) | Result |
|---|---|---|---|
| 1-1/2 in | about 10.1 | about 10.1 | Fails friction (and velocity) |
| 2 in | about 2.6 | about 5.8 | Passes |
The building main must be 2 inches. If the design had wrongly used 15 or 20 psi for the flush valve, the allowance would have looked large enough for 1-1/2-inch pipe. The flush valve would then starve at peak demand.
Exam traps
- Wrong demand column: 100 wsfu is 43.5 gpm on flush tanks but 67.5 gpm on flush valves.
- Wrong fixture pressure: a flush valve needs 35 or 45 psi, not 8 psi.
- PRV trigger: static pressure over 80 psi, not 100 psi.
- Hot and cold loads: each is about 3/4 of the total for a fixture with both. Do not simply add the hot and cold values together.
Under IPC 604.8, when is a pressure-reducing valve required on a building water supply?
When the static pressure in the building exceeds 80 psi
When the static pressure in the building exceeds 65 psi
When the static pressure at the main exceeds 100 psi
When the residual pressure at any fixture exceeds 45 psi
A system supplies mostly flushometer valves and carries 100 water supply fixture units. What design demand does Appendix E Table E103.3(3) give?
100 gpm
29.1 gpm
67.5 gpm
43.5 gpm
What is the minimum fixture supply pipe size for a flushometer-valve water closet under IPC Table 604.5?
1 inch
1-1/4 inches
1/2 inch
3/4 inch
Sections you finish are checked off in the contents.