4.1 Drainage Fixture Units & Sizing Branches, Stacks and Building Drains

Key Takeaways

  • In IPC Table 709.1, a 1.6-gallon-per-flush water closet is 3 dfu in private use and 4 dfu in public use, a lavatory is 1 dfu, a bathtub or 5.7-gpm shower is 2 dfu, and a bathroom group with a 1.6-gpf water closet is 5 dfu.

  • IPC 709.3 counts continuous or semicontinuous flow as 2 dfu for each gpm.

  • In Table 710.1(2), a 3-inch horizontal branch carries up to 20 dfu, and a 3-inch stack carries 20 dfu per branch interval, 48 dfu total with three or fewer branch intervals, or 72 dfu with more.

  • In Table 710.1(1), a 3-inch building drain carries 36 dfu at 1/8 inch per foot, 42 dfu at 1/4 inch per foot and 50 dfu at 1/2 inch per foot, and a 4-inch building drain carries 180, 216 and 250 dfu.

  • Any building drain serving a water closet must be at least 3 inches (Table 710.1(1), note a), and a clothes washer standpipe drain must be at least 2 inches and connect to a branch or stack of 3 inches or more (IPC 406.2).

Last updated: October 2026

Why this section matters

Drain sizing is the core of Sizing and Design and many plan-reading questions. The method is: assign fixture units, add them up in the direction of flow, then choose the correct table. Most mistakes come from reading the wrong table, such as using the building drain table for a horizontal branch.

Drainage fixture units (709)

A drainage fixture unit (dfu) is a load factor that reflects how much a fixture discharges, how fast and how often. It is a probability weighting, not a flow rate. Hunter's original work was based on a lavatory discharging about 1 cubic foot per minute, but on the exam you use only the table values.

Selected values from Table 709.1

FixturedfuMinimum trap
Automatic clothes washer, residential22 in
Automatic clothes washer, commercial32 in
Bathroom group, 1.6-gpf water closet5—
Bathroom group, water closet over 1.6 gpf6—
Bathtub (with or without shower head or whirlpool)21-1/2 in
Bidet, lavatory, dental lavatory11-1/4 in
Dishwasher, domestic21-1/2 in
Drinking fountain1/21-1/4 in
Emergency floor drain02 in
Floor drain22 in
Kitchen sink, domestic (with or without disposer and dishwasher)21-1/2 in
Laundry tray, combination sink and tray, service sink, sink21-1/2 in
Shower, total flow 5.7 gpm or less21-1/2 in
Shower, over 5.7 to 12.3 gpm32 in
Shower, over 12.3 to 25.8 gpm53 in
Urinal4Match outlet
Urinal, 1 gallon per flush or less2Match outlet
Urinal, nonwater1/2Match outlet
Water closet, private, 1.6 gpf3Integral
Water closet, public, 1.6 gpf4Integral
Water closet, flushometer tank, public or private4Integral
Water closet, private, over 1.6 gpf4Integral
Water closet, public, over 1.6 gpf6Integral

Notes to the table:

  • For drains and sewers, water closets and urinals may not be given lower values unless testing proves them.
  • Fixtures added to a bathroom group add their own dfu.
  • 709.2: Fixtures not listed use Table 709.2, based on drain or trap size: 1-1/4 in = 1, 1-1/2 in = 2, 2 in = 3, 2-1/2 in = 4, 3 in = 5, 4 in = 6.
  • 709.3: Where only a gpm flow is known, count 1 gpm as 2 dfu. A pump discharging 15 gpm adds 30 dfu.
  • 709.4: An indirect waste receptor carries the total dfu of the fixtures that drain into it, but no less than its own table value. 709.4.1: A receptor taking only clear water from display cases, ice bins, coolers and freezers is 1/2 dfu.

Choosing the right table (710)

Pipe being sizedTable
Horizontal fixture branch, vertical soil or waste stackTable 710.1(2)
Building drain, building sewer, horizontal branch of the building drainTable 710.1(1) (by slope)
Horizontal stack offsetSized like a building drain (710.1.1)

Table 710.1(2): horizontal branches and stacks

DiameterHorizontal branchOne branch intervalStack, 3 intervals or fewerStack, more than 3 intervals
1-1/2 in3248
2 in661024
2-1/2 in1292042
3 in20204872
4 in16090240500
5 in3602005401,100
6 in6203509601,900
8 in1,4006002,2003,600
  • A stack must meet both its total limit and its per-interval limit.
  • A branch interval is at least 8 feet of stack between branch connections (Section 202).
  • A stack may get smaller higher up as its load drops, but never smaller than half the largest size required.

Table 710.1(1): building drains and sewers

Diameter1/16 in/ft1/8 in/ft1/4 in/ft1/2 in/ft
2 in——2126
2-1/2 in——2431
3 in—364250
4 in—180216250
5 in—390480575
6 in—7008401,000
8 in1,4001,6001,9202,300
10 in2,5002,9003,5004,200

Note a to the table says any building drain serving a water closet must be at least 3 inches. The 2021 IPC tables do not limit how many water closets a 3-inch branch or stack may carry. The dfu columns govern. (Some older codes had such limits; the single-stack vent system in Section 917 still limits a 3-inch stack to two water closets.)

Other sizing rules:

  • 704.2: Drain piping may not be reduced in size in the direction of flow. A 4 × 3-inch closet flange or closet bend is not a reduction.
  • 704.3: Horizontal branches connect to the base of a stack at least 10 stack diameters downstream.
  • 710.2: Pipe sizes must include the load of any roughed-in future fixtures.

Clothes washer standpipes (406.2 and 802.4.3)

  • A washer must discharge through an air break into a standpipe or into a laundry sink.
  • The trap and fixture drain must be at least 2 inches, and the fixture drain must connect to a 3-inch or larger branch or stack.
  • The standpipe must be individually trapped and extend 18 to 42 inches above the trap weir (802.4.3).
  • Gravity-discharge washers may drain to a waste receptor or approved trench drain.

Worked example: four-story office stack

Each floor has 2 public 1.6-gpf water closets (4 dfu each), 2 lavatories (1 each), 1 urinal at 1 gpf or less (2) and 1 service sink (2).

  1. Load per floor: 2(4)+2(1)+2+2=142(4) + 2(1) + 2 + 2 = 14 dfu.
  2. Branch on each floor: water closets need at least 3 inches, and a 3-inch branch carries 20 dfu, so 14 dfu fits. Use 3 inches.
  3. Stack: 4 floors means 4 branch intervals, which is more than 3, and 4×14=564 \times 14 = 56 dfu. A 3-inch stack allows 72 dfu total and 20 per interval, and 14 per interval passes. Use a 3-inch stack.
  4. Building drain at 1/4 inch per foot: 56 dfu exceeds the 42-dfu limit for 3 inches, so the drain must be 4 inches (216 dfu).

Lesson: the stack can legally be smaller than the building drain it feeds, because the two are sized from different tables.

Exam traps

  • Washer dfu: 2 residential, 3 commercial. Both need a 2-inch trap.
  • Public 1.6-gpf water closet = 4 dfu. The 6-dfu value is for public water closets flushing more than 1.6 gallons.
  • No "two water closets per 3-inch branch" rule in the 2021 IPC Table 710.1(2).
  • Branch vs. building drain: a 3-inch horizontal branch carries 20 dfu, but a 3-inch building drain at 1/4 inch per foot carries 42.
Loading diagram...
Which drainage table applies
Test Your Knowledge

What are the minimum trap size and drainage fixture unit value for a commercial automatic clothes washer under IPC Table 709.1?

A

2-inch trap and 2 dfu

B

1-1/2-inch trap and 2 dfu

C

3-inch trap and 5 dfu

D

2-inch trap and 3 dfu

Test Your Knowledge

What is the maximum drainage fixture unit load for a 3-inch horizontal fixture branch under IPC Table 710.1(2)?

A

48 dfu

B

42 dfu

C

36 dfu

D

20 dfu

Test Your Knowledge

A horizontal building drain at 1/4 inch per foot must carry 180 drainage fixture units. What is the minimum size under IPC Table 710.1(1)?

A

5 inches

B

2-1/2 inches

C

4 inches

D

3 inches

Sections you finish are checked off in the contents.